IB-23C650
SETUP
Table 12. Tune Menu
Step Step Description
Top
Display
7
Reset Enable.
UP
selects YES or
DN
selects NO.
SCRL
to advance to:
Step 7.1 from YES if output type is HEAT/COOL,
or
Step 7.3 from YES if output type is any other, or
Step 7.4 from NO.
RESET
7.1
Reset Value Heat.
UP
or
DN
sets value.
SCRL
to advance to Step 7.2.
RESET
7.2
Reset Value Cool.
UP
or
DN
sets value.
SCRL
to advance to Step 8.
RESET
7.3
Reset Value.
UP
or
DN
sets value.
SCRL
to advance to Step 8.
7.4 Fixed Manual Reset.
UP
selects YES or
DN
selects NO.
SCRL
to advance to:
Step 7.4.1 from YES, or
Step 8 from NO.
FIXED
7.4.1
Manual Reset Value.
UP
or
DN
sets value.
SCRL
to advance to Step 8.
MANUAL
8
Preact Value.
UP
or
DN
sets value.
SCRL
to advance to:
Step 11 if A/M ratio bias is enabled and type is
RATIO ONLY or RATIO AND BIAS, or
Step 12 if A/M ratio bias is enabled and type is
BIAS ONLY, or
Step 9 if A/M ratio bias is not enabled and input
2 is enabled, or
116