Micromod MOD: Remote I/O Modules for use with 2020N Remote Instrukcja Użytkownika Strona 20

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 42
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 19
Remote I/O Modules
ELECTRICAL CONNECTIONS
324
I/O REMOTE UNIT
ICSI08D1 24 VDC
Unit error
Bus error
TEST
0
1
2
3
4
5
6
7
0
1
2
3
1
4
56
7
Input
8
9
10
11
12
13 14 15
Cut Wire
ABB Procontic CS 31
Shield
Bus # 1
Bus # 2
Ground
Common +
Common -
Common -
A
B
C
D
E
F
G
H
Common +
Common +
Common +
Common +
Common +
Not to
be used
Not to
be used
Not to
be used
Technical Characteristics:
Power supply 24 VDC 230 or 120 VAC 50 or 60 Hz
Number of inputs per unit 8 8
Power supply isolation no yes (1500 VAC)
Inputs opto-isolated no no
Supply output regulated 24 VDC (± 5 %) - 100 mA
Signal level of the input, nominal value 24 VDC 24 VDC
Signal level of the input :
0 - OFF signal –3 to +5V –3 to +5V
1 - ON signal +15 to +30V +15 to +30V
Open circuit detection* yes yes
Input current for 24 VDC 6 mA 6 mA
Input delay 8 ms 8 ms
Maximum power consumption 0.2 A 10 VA
Maximum power dissipation 4.5 W 8 W
* A 20 to 30 kOhm resistor must be mounted in parallel of each input captor to get open
circuit detection for that channel. With an inductive captor, the minimal current is 1 mA.
16
Przeglądanie stron 19
1 2 ... 15 16 17 18 19 20 21 22 23 24 25 ... 41 42

Komentarze do niniejszej Instrukcji

Brak uwag