Output Holder Instructions
CONFIGURATION
4.3 LOADING THE COMPOUND FOR MODCELL
The PID_OH compound has a fully functional PID, with I/O and also the logic for bumpless
transfer of output.
If you already have your PID configured, you can delete the blocks that are not required from
this compound after loading.
1. Launch the ViZapp Software and open your workspace, project and the instrument
database.
2. The PID_OH1 compound can only be loaded inside a loop compound. Open the loop
compound where you want to load the PID_OH compound.
3. Select Project – Gallery – Component Gallery from the menu bar as shown in the
figure below:
Figure 4 .7. Opening the Component Gallery
4. The Component Gallery dialog will be displayed as shown in the next figure. Select the
Compounds tab and click on the PID_OH_MCELL compound from the list of compounds
as shown and then click on the Export button.
4 -8