FLEXIBLE CONTROL STRATEGIESMulti-Loop Process Controller53MC5000FLEXIBLE CONTROL STRATEGY GUIDEPN24568A Rev. 1

Strona 2 - MicroMod Automation, Inc

Figure 2-1. One-Loop FCS ModulesSection 2. FCS Modules3-1TXT2–3

Strona 3 - Table of Contents

A.1.2 CS2 - ANALOG BACKUP CONTROLLERThe analog backup controller is used in operations where a remote computer normally controls thefinal element dir

Strona 4

Figure A-2. CS2 Block DiagramAppendix A. Control Strategy Wirelists412-TXTA-11

Strona 5 - List of Figures

Table A-2. CS2 WirelistANO LOAD OUTPUTONE, TWO, AND FOUR LOOPSCOMMENTS: ANO = (INPUT) x (SCALER) + BIAS W/L DEFLT VALUE NAMEB100 000 (C) 102 ANO0 OZ

Strona 6 - READ FIRST

Table A-2. CS2 WirelistSDT0 LOAD OUTPUTONE, TWO, AND FOUR LOOPSCOMMENTS: W/L DEFLT VALUE NAMEB111 097 SDT-0A STA0 NAME1A055ALARMASMA0MODE0L3520SAA0AEN

Strona 7

Table A-2. CS2 WirelistEXTENDED MATH AONE LOOPCOMMENTS:W/L DEFLT VALUE NAMEB119 255 A K12C3650K11C3640K10C3630K9C3620K8C3610B120 254 BB121 253 C K1C3

Strona 8 - 2.0 FCS MODULES

Table A-2. CS2 WirelistB136 070 AB137 070 BB138 255 CPARAMETER LOADER CONE LOOPCOMMENTS:W/L DEFLT VALUE NAMEB139 070 (L) 108 AB140 255 (C) 078 BB141

Strona 9

Table A-2. CS2 WirelistB152 100 (C) 020 PV0B153 101 SP0T1-0C1170CZ0C1140PL1-0C103100PL2-0C1040ADB0C1052AIX0B3351PID 0ONE LOOPCOMMENTS:W/L DEFLT VALUE

Strona 10 - Section 2. FCS Modules

Table A-2. CS2 WirelistB170 093 (L) 107 AB171 093 (L) 108 BB172 000 005 FCAppendix A. Control Strategy WirelistsCS2WKS1A-17

Strona 11

A.1.3 CS3 - RATIO CONTROLLERThe ratio PID controller is used where a controlled variable must automatically be maintained indefinite proportion to an

Strona 12

Figure A-3. CS3 Block DiagramAppendix A. Control Strategy Wirelists413-TXTA-19

Strona 13 - FCS WORKSHEET

Figure 2-2. Two-Loop Extended FCS ModulesFCS 53MC5000 Flexible Control Strategies2–43-1TXT

Strona 14 - 2.7 FCS MODULE DESCRIPTIONS

Table A-3. CS3 WirelistANO LOAD OUTPUTONE, TWO, AND FOUR LOOPSCOMMENTS: ANO = (INPUT) x (SCALER) + BIAS W/L DEFLT VALUE NAMEB100 000 (C) 102 ANO0 O

Strona 15

Table A-3. CS3 WirelistSDT0 LOAD OUTPUTONE, TWO, AND FOUR LOOPSCOMMENTS: W/L DEFLT VALUE NAMEB111 097 SDT-0A STA0 NAME1A055ALARMASMA0MODE0L3520SAA0AE

Strona 16

Table A-3. CS3 WirelistEXTENDED MATH AONE LOOPCOMMENTS:W/L DEFLT VALUE NAMEB119 255 A K12C3650K11C3640K10C3630K9C3620K8C3610B120 254 BB121 253 C K1C

Strona 17 - 2.7.3 ANALOG INPUT LOADER

Table A-3. CS3 WirelistB136 070 AB137 070 BB138 255 CPARAMETER LOADER CONE LOOPCOMMENTS:W/L DEFLT VALUE NAMEB139 070 AB140 255 (C) 031 BB141 255 (L

Strona 18 - 2.7.4 EXTENDED MATH A

Table A-3. CS3 WirelistB152 100 (C) 020 PV0B153 101 SP0T1-0C1170CZ0C1140PL1-0C103100PL2-0C1040ADB0C1052AIX0B3351PID 0ONE LOOPCOMMENTS:W/L DEFLT VALU

Strona 19

Table A-3. CS3 WirelistB170 093 (L) 108 AB171 093 (L) 107 BB172 000 130 FCAppendix A. Control Strategy WirelistsCS3WKS1A–25

Strona 20 - A.G.A. report

A.1.4 CS4 - AUTOMATIC/MANUAL STATIONThe automatic/manual station configures the controller into a conventional single station automat-ic/manual selec

Strona 21 - 2.7.5 MATH A

Figure A-4. CS4 Block DiagramAppendix A. Control Strategy Wirelists414-TXTA–27

Strona 22 - 2.7.7 LOGIC B

Table A-4. CS4 WirelistANO LOAD OUTPUTONE, TWO, AND FOUR LOOPSCOMMENTS: ANO = (INPUT) x (SCALER) + BIAS W/L DEFLT VALUE NAMEB100 000 (C) 102 ANO0 OZ

Strona 23 - Opposite last value

Table A-4. CS4 WirelistSDT0 LOAD OUTPUTONE, TWO, AND FOUR LOOPSCOMMENTS: W/L DEFLT VALUE NAMEB111 097 SDT-0A STA0 NAME1A055ALARMASMA0MODE0L3520SAA0AE

Strona 24 - 2.7.9 PARAMETER LOADER B

Figure 2-3. Four-Loop Extended FCS ModulesSection 2. FCS Modules3-1TXT2–5

Strona 25 - 2.7.11 PARAMETER LOADER D

Table A-4. CS4 WirelistEXTENDED MATH AONE LOOPCOMMENTS:W/L DEFLT VALUE NAMEB119 255 A K12C3650K11C3640K10C3630K9C3620K8C3610B120 254 BB121 253 C K1C

Strona 26 - 2.7.12 PARAMETER LOADER E

Table A-4. CS4 WirelistB136 070 AB137 070 BB138 255 CPARAMETER LOADER CONE LOOPCOMMENTS:W/L DEFLT VALUE NAMEB139 070 AB140 255 BB141 255 CPARAMETER

Strona 27 - 2.7.13 SETPOINT GENERATOR 0

Table A-4. CS4 WirelistB152 100 (C) 022 PV0B153 101 (C) 020 SP0T1-0C1170CZ0C1140PL1-0C103100PL2-0C1040ADB0C1052AIX0B3351PID 0ONE LOOPCOMMENTS:W/L DE

Strona 28 - ASSIGNED VALUE

Table A-4. CS4 WirelistB170 093 AB171 093 BB172 000 FCAppendix A. Control Strategy WirelistsCS4WKS1A–33

Strona 29

A.1.5 CS5 - RATIO AUTOMATIC/MANUAL STATIONThe ratio automatic/manual station configures the controller into a ratio automatic/manual selectorwith man

Strona 30

Figure A-5. CS5 Block DiagramAppendix A. Control Strategy Wirelists415-TXTA–35

Strona 31 - 2.7.16 AUTO/MANUAL SWITCH 0

Table A-5. CS5 WirelistANO LOAD OUTPUTONE, TWO, AND FOUR LOOPSCOMMENTS: ANO = (INPUT) x (SCALER) + BIAS W/L DEFLT VALUE NAMEB100 000 (C) 102 ANO0 O

Strona 32 - 2.7.17 MATH B

Table A-5. CS5 WirelistSDT0 LOAD OUTPUTONE, TWO, AND FOUR LOOPSCOMMENTS: W/L DEFLT VALUE NAMEB111 097 SDT-0A STA0 NAME1A055ALARMASMA0MODE0L3520SAA0AE

Strona 33 - 2.7.18 MATH C

Table A-5. CS5 WirelistEXTENDED MATH AONE LOOPCOMMENTS:W/L DEFLT VALUE NAMEB119 255 A K12C3650K11C3640K10C3630K9C3620K8C3610B120 254 BB121 253 C K1C

Strona 34 - 2.7.19 LOGIC C

Table A-5. CS5 WirelistB136 070 AB137 070 BB138 255 CPARAMETER LOADER CONE LOOPCOMMENTS:W/L DEFLT VALUE NAMEB139 070 (L) 001 AB140 255 (C) 021 BB14

Strona 35

2.4 ASSIGNING WORKSHEET VALUESFor single loop controllers the flexible control strategy wirelist datapoint range is from B100 toB172. Two loop and f

Strona 36 - 2.7.20 EXTENDED MATH B

Table A-5. CS5 WirelistB152 100 (C) 022 PV0B153 101 SP0T1-0C1170CZ0C1140PL1-0C103100PL2-0C1040ADB0C1052AIX0B3351PID 0ONE LOOPCOMMENTS:W/L DEFLT VALU

Strona 37

Table A-5. CS5 WirelistB170 093 AB171 093 BB172 000 FCAppendix A. Control Strategy WirelistsCS5WKS1A–41

Strona 38

A.1.6 CS20 - TWO-LOOP CONTROLLERThe two-loop controller provides two standard PID controllers in a single cabinet enclosure.Loading CS20 initializes

Strona 39 - 2.7.21 MATH D

Figure A-6. CS20 Block DiagramAppendix A. Control Strategy Wirelists416-TXTA–43

Strona 40 - 2.7.23 LOGIC E

Table A-6. CS20 WirelistANO LOAD OUTPUTONE, TWO, AND FOUR LOOPSCOMMENTS: ANO = (INPUT) x (SCALER) + BIASW/L DEFLT VALUE NAMEB100 000 (C) 031 ANO0 O

Strona 41

Table A-6. CS20 WirelistSDT0 LOAD OUTPUTONE, TWO, AND FOUR LOOPSCOMMENTS: W/L DEFLT VALUE NAMEB111 097 SDT-0A STA0 NAME1A055ALARMASMA0MODE0L3520SAA0A

Strona 42 - 2.7.24 SETPOINT GENERATOR 1

Table A-6. CS20 WirelistEXTENDED MATH AONE LOOPCOMMENTS:W/L DEFLT VALUE NAMEB119 255 (C) 020 A K12C3650K11C3640K10C3630K9C3620K8C3610B120 254 (C) 02

Strona 43

Table A-6. CS20 WirelistB136 070 AB137 070 BB138 255 (L) 136 CPARAMETER LOADER CONE LOOPCOMMENTS:W/L DEFLT VALUE NAMEB139 070 AB140 255 (C) 030 BB1

Strona 44

Table A-6. CS20 WirelistB152 100 (C) 029 PV0B153 101 SP0T1-0C1170CZ0C1140PL1-0C103100PL2-0C1040ADB0C1052AIX0B3351PID 0ONE LOOPCOMMENTS:W/L DEFLT VAL

Strona 45

Table A-6. CS20 WirelistB170 093 (L) 110 AB171 093 (L) 111 BB172 000 001 FCEXTENDED MATH BTWO LOOPCOMMENTS:W/L DEFLT VALUE NAMEB173 255 (C) 021 A K

Strona 46 - 2.7.27 AUTO/MANUAL SWITCH 1

2.5 EXECUTING AN FCS WIRELISTThe procedure to execute the FCS wirelist is provided in the table that follows:Executing an FCS WirelistSTEP PROCEDURE1

Strona 47 - 2.7.28 MATH E

Table A-6. CS20 WirelistSETPOINT GENERATOR 1TWO LOOPCOMMENTS:W/L DEFLT VALUE NAMEB187 164 (C) 033 STV1 SWR1L1370B188 140 (L) 131 SWSPT1B189 156 (C

Strona 48 - 2.7.29 MATH F

Table A-6. CS20 WirelistMATH FTWO LOOPCOMMENTS:W/L DEFLT VALUE NAMEB205 091 (C) 102 AB206 092 (C) 138 BB207 093 C K1C0910K2C0920K3C0930B208 000 FC

Strona 49 - 2.7.30 LOGIC F

A.1.7 CS21 - TWO-LOOP CASCADE CONTROLLERThe two-loop cascade controller consists of two standard PID control loops, arranged in a cascadesetup whereb

Strona 50

Figure A-7. CS21 Block DiagramAppendix A. Control Strategy Wirelists417-TXTA–53

Strona 51 - 2.7.31 SETPOINT GENERATOR 2

Table A-7. CS21 WirelistANO LOAD OUTPUTONE, TWO, AND FOUR LOOPSCOMMENTS: ANO = (INPUT) x (SCALER) + BIASW/L DEFLT VALUE NAMEB100 000 (C) 138 ANO0 O

Strona 52 - 2.7.32 CONTROL 2

Table A-7. CS21 WirelistSDT0 LOAD OUTPUTONE, TWO, AND FOUR LOOPSCOMMENTS: W/L DEFLT VALUE NAMEB111 097 SDT-0A STA0 NAME1A055ALARMASMA0MODE0L3520SAA0A

Strona 53

Table A-7. CS21 WirelistEXTENDED MATH AONE LOOPCOMMENTS:W/L DEFLT VALUE NAMEB119 255 A K12C3650K11C3640K10C3630K9C3620K8C3610B120 254 BB121 253 C K1

Strona 54 - 2.7.33 AUTO/MANUAL SWITCH 2

Table A-7. CS21 WirelistB136 070 AB137 070 BB138 255 CPARAMETER LOADER CONE LOOPCOMMENTS:W/L DEFLT VALUE NAMEB139 070 AB140 255 BB141 255 CPARAMETE

Strona 55 - 2.7.34 LOGIC G

Table A-7. CS21 WirelistB152 100 (C) 020 PV0B153 101 SP0T1-0C1170CZ0C1140PL1-0C103100PL2-0C1040ADB0C1052AIX0B3351PID 0ONE LOOPCOMMENTS:W/L DEFLT VAL

Strona 56

Table A-7. CS21 WirelistB170 093 (L) 110 AB171 093 (L) 111 BB172 000 001 FCEXTENDED MATH BTWO LOOPCOMMENTS:W/L DEFLT VALUE NAMEB173 255 A K12C3770K

Strona 57 - 2.7.35 SETPOINT GENERATOR 3

2.7.1 STATUS DISPLAY 1 LOADERThe Status Display 1 (SDT1) Loader module allows operator push button inputs to be acted uponby the FCS function block b

Strona 58 - 2.7.36 CONTROL 3

Table A-7. CS21 WirelistSETPOINT GENERATOR 1TWO LOOPCOMMENTS:W/L DEFLT VALUE NAMEB187 164 STV1 SWR1L1370B188 140 SWSPT1B189 156 (C) 102 RSP1 IR1C1

Strona 59

Table A-7. CS21 WirelistB205 091 AB206 092 BB207 093 C K1C0910K2C0920K3C0930B208 000 FCLOGIC FTWO LOOPCOMMENTS:W/L DEFLT VALUE NAMEB209 086 (L) 134

Strona 60 - 2.7.37 AUTO/MANUAL SWITCH 3

A.1.8 CS22 - TWO-LOOP OVERRIDE CONTROLLERThe two-loop override controller has two standard PID control loops. Override control is usedwhen two inter

Strona 61 - 2.7.38 LOGIC H

Figure A-8. CS22 Block DiagramAppendix A. Control Strategy Wirelists418-TXTA–63

Strona 62

Table A-8. CS22 WirelistANO LOAD OUTPUTONE, TWO, AND FOUR LOOPSCOMMENTS: ANO = (INPUT) x (SCALER) + BIASW/L DEFLT VALUE NAMEB100 000 (C) 035 ANO0 O

Strona 63 - 2.7.39 ANALOG OUTPUT LOADER

Table A-8. CS22 WirelistSDT0 LOAD OUTPUTONE, TWO, AND FOUR LOOPSCOMMENTS: W/L DEFLT VALUE NAMEB111 097 SDT-0A STA0 NAME1A055ALARMASMA0MODE0L3520SAA0A

Strona 64 - POINTS TO

Table A-8. CS22 WirelistEXTENDED MATH AONE LOOPCOMMENTS:W/L DEFLT VALUE NAMEB119 255 A K12C3650K11C3640K10C3630K9C3620K8C3610B120 254 BB121 253 C K1

Strona 65

Table A-8. CS22 WirelistB136 070 AB137 070 BB138 255 CPARAMETER LOADER CONE LOOPCOMMENTS:W/L DEFLT VALUE NAMEB139 070 (L) 088 AB140 255 (C) 078 BB1

Strona 66 - 3.0 FCS WIRELIST EXAMPLES

Table A-8. CS22 WirelistB152 100 (C) 020 PV0B153 101 SP0T1-0C1170CZ0C1140PL1-0C103100PL2-0C1040ADB0C1052AIX0B3351PID 0ONE LOOPCOMMENTS:W/L DEFLT VAL

Strona 67 - Figure 3-1. Logical Oneshot

Table A-8. CS22 WirelistB170 093 (L) 110 AB171 093 (L) 111 BB172 000 001 FCEXTENDED MATH BTWO LOOPCOMMENTS:W/L DEFLT VALUE NAMEB173 255 A K12C3770K

Strona 68 - ORIGINATOR: John Doe

2.7.2 CONTACT CLOSURE INPUT LOADERThe Contact Closure Input (CCI0-17) Loader module generates a logic level (0/1) L-value outputfor each connected CC

Strona 69 - EX1WKS2L

Table A-6. CS20 WirelistSETPOINT GENERATOR 1TWO LOOPCOMMENTS:W/L DEFLT VALUE NAMEB187 164 (C) 033 STV1 SWR1L1370B188 140 (L) 131 SWSPT1B189 156 (C

Strona 70

Table A-6. CS20 WirelistMATH FTWO LOOPCOMMENTS:W/L DEFLT VALUE NAMEB205 091 (C) 102 AB206 092 (C) 138 BB207 093 C K1C0910K2C0920K3C0930B208 000 FC

Strona 71

A.1.9 CS40 - DUAL TWO-LOOP CASCADE CONTROLLERThe dual two-loop cascade controller consists of four standard PID control loops, arranged as twocascade

Strona 72

Figure A-9. CS40 Block DiagramAppendix A. Control Strategy Wirelists419-TXTA–73

Strona 73

Table A-9. CS40 WirelistANO LOAD OUTPUTONE, TWO, AND FOUR LOOPSCOMMENTS: ANO = (INPUT) x (SCALER) + BIASW/L DEFLT VALUE NAMEB100 000 (C) 174 ANO0 O

Strona 74 - EX2WKS2L

Table A-9. CS40 WirelistSDT0 LOAD OUTPUTONE, TWO, AND FOUR LOOPSCOMMENTS: W/L DEFLT VALUE NAMEB111 097 SDT-0A STA0 NAME1A055ALARMASMA0MODE0L3520SAA0A

Strona 75

Table A-9. CS40 WirelistEXTENDED MATH AONE LOOPCOMMENTS:W/L DEFLT VALUE NAMEB119 255 A K12C3650K11C3640K10C3630K9C3620K8C3610B120 254 BB121 253 C K1

Strona 76

Table A-9. CS40 WirelistPARAMETER LOADER BONE LOOPCOMMENTS:W/L DEFLT VALUE NAMEB136 070 AB137 070 BB138 255 CPARAMETER LOADER CONE LOOPCOMMENTS:W

Strona 77

Table A-9. CS40 WirelistDEVIATION/ALARM CALC 0ONE LOOPCOMMENTS:W/L DEFLT VALUE NAMEB152 100 (C) 020 PV0B153 101 SP0T1-0C1170CZ0C1140PL1-0C103100PL2

Strona 78

Table A-9. CS40 WirelistLOGIC CONE LOOPCOMMENTS:W/L DEFLT VALUE NAMEB170 093 AB171 093 BB172 000 FCEXTENDED MATH BTWO LOOPCOMMENTS:W/L DEFLT VALUE

Strona 79

2.7.3 ANALOG INPUT LOADERThe Analog Input (ANI0-8) Loader module maps the ANI outputs into the FCS program. The out-put signal is the numeric value

Strona 80

Table A-9. CS40 WirelistSETPOINT GENERATOR 1TWO LOOPCOMMENTS:W/L DEFLT VALUE NAMEB187 164 (C) 021 STV1 SWR1L1370B188 140 (L) 090 SWSPT1B189 156 RS

Strona 81 - EX3WKS2L

Table A-9. CS40 WirelistMATH FTWO LOOPCOMMENTS:W/L DEFLT VALUE NAMEB205 091 AB206 092 BB207 093 C K1C0910K2C0920K3C0930B208 000 FCLOGIC FTWO LOO

Strona 82

Table A-9. CS40 WirelistLOGIC GFOUR LOOPCOMMENTS:W/L DEFLT VALUE NAMEB223 085 (L) 158 AB224 085 (L) 159 BB225 000 001 FCSETPOINT GENERATOR 3FOUR

Strona 83

A.1.10 CS41 - FOUR-LOOP CONTROLLERThe four-loop controller provides four independent PID controllers. Loading CS41 initializes theANI1–7 engineering

Strona 84

Figure A-10. CS41 Block DiagramFCS 53MC5000 Flexible Control StrategiesA–844110-TXT

Strona 85

Table A-10. CS41 WirelistANO LOAD OUTPUTONE, TWO, AND FOUR LOOPSCOMMENTS: ANO = (INPUT) x (SCALER) + BIASW/L DEFLT VALUE NAMEB100 000 (C) 102 ANO0

Strona 86

Table A-10. CS41 WirelistSDT0 LOAD OUTPUTONE, TWO, AND FOUR LOOPSCOMMENTS: W/L DEFLT VALUE NAMEB111 097 SDT-0A STA0 NAME1A055ALARMASMA0MODE0L3520SAA0

Strona 87 - EX5WKS2L

Table A-10. CS41 WirelistEXTENDED MATH AONE LOOPCOMMENTS:W/L DEFLT VALUE NAMEB119 255 A K12C3650K11C3640K10C3630K9C3620K8C3610B120 254 BB121 253 C K

Strona 88

Table A-10. CS41 WirelistPARAMETER LOADER BONE LOOPCOMMENTS:W/L DEFLT VALUE NAMEB136 070 AB137 070 BB138 255 CPARAMETER LOADER CONE LOOPCOMMENTS:

Strona 89

Table A-10. CS41 WirelistDEVIATION/ALARM CALC 0ONE LOOPCOMMENTS:W/L DEFLT VALUE NAMEB152 100 (C) 020 PV0B153 101 SP0T1-0C1170CZ0C1140PL1-0C103100PL

Strona 90

2.7.4 EXTENDED MATH AThe Extended Math A (Emath A) module executes a selected function on three input variables A,B, and C. The function to be execut

Strona 91 - APPENDIX A: CONTROL STRATEGY

Table A-10. CS41 WirelistLOGIC CONE LOOPCOMMENTS:W/L DEFLT VALUE NAMEB170 093 (L) 110 AB171 093 (L) 111 BB172 000 001 FCEXTENDED MATH BTWO LOOPCOM

Strona 92

Table A-10. CS41 WirelistSETPOINT GENERATOR 1TWO LOOPCOMMENTS:W/L DEFLT VALUE NAMEB187 164 STV1 SWR1L1370B188 140 (L) 005 SWSPT1B189 156 (C) 023 R

Strona 93

Table A-10. CS41 WirelistMATH FTWO LOOPCOMMENTS:W/L DEFLT VALUE NAMEB205 091 AB206 092 BB207 093 C K1C0910K2C0920K3C0930B208 000 FCLOGIC FTWO LO

Strona 94 - Table A-1. CS1 Wirelist

Table A-10. CS41 WirelistLOGIC GFOUR LOOPCOMMENTS:W/L DEFLT VALUE NAMEB223 085 (L) 158 AB224 085 (L) 159 BB225 000 001 FCSETPOINT GENERATOR 3FOUR

Strona 95

This page intentionally left blank.Appendix A. Control Strategy WirelistsCS41WKS2A–94

Strona 96

APPENDIX B: MASTER WORKSHEETSThis appendix contains blank master worksheets for photocopying. Entries are not made on themaster worksheets. FCS wir

Strona 97

ApplicableLoop Number 1, 2, 4DatapointRangeFCS Module2 B197 - B200 Auto/Manual Switch 12 B201 - B204 Math E2 B205 - B208 Math F2 B209 - B211 Logic F4

Strona 98

FCS WORKSHEET PAGE ___ OF ___ TITLE:

Strona 99

FCS WORKSHEET PAGE ___ OF ___ CCI LOAD INPUTONE, TWO, AND FOUR LOOPSCOMMENTS:W/L DEFLT VALUE NAM

Strona 100

FCS WORKSHEET PAGE ___ OF ___ SDT1 LOAD INPUTONE, TWO, AND FOUR LOOPSCOMMENTS:W/L DEFLT VALUE NAM

Strona 101

2.7.4.1 PIECEWISE CHARACTERIZER/FUNCTION GENERATOR (FC=15)This FC permits linearization of input signal A or the generation of a function based on th

Strona 102 - Table A-2. CS2 Wirelist

FCS WORKSHEET PAGE ___ OF ___ANO LOAD OUTPUTONE, TWO, AND FOUR LOOPSCOMMENTS: ANO = (INPUT x SC

Strona 103

FCS WORKSHEET PAGE ___ OF ___SDT0 LOAD OUTPUTONE, TWO, AND FOUR LOOPSCOMMENTS:W/L DEFLT VALUE NA

Strona 104

FCS WORKSHEET PAGE ___ OF ___ EXTENDED MATH AONE LOOPCOMMENTS: Output datapoints for this modul

Strona 105

FCS WORKSHEET PAGE ___ OF ___ B136 070 L AB137 070 L BB138 255 L CPARAMETER LOADER CONE LOOPCOM

Strona 106

FCS WORKSHEET PAGE ___ OF ___ B152 100 C PV0B153 101 C SP0T1-0C1170CZ0C1140PL1-0C103100PL2-0C1040

Strona 107

FCS WORKSHEET PAGE ___ OF ___ B170 093 L AB171 093 L BB172 000 FCEXTENDED MATH BTWO LOOPCOMMENT

Strona 108 - A.1.3 CS3 - RATIO CONTROLLER

FCS WORKSHEET PAGE ___ OF ___SETPOINT GENERATOR 1TWO LOOPCOMMENTS: Output datapoints for this

Strona 109

FCS WORKSHEET PAGE ___ OF ___B205 091 C AB206 092 C BB207 093 C C K1C0910K2C0920K3C0930B208 000 F

Strona 110 - Table A-3. CS3 Wirelist

FCS WORKSHEET PAGE ___ OF ___B223 085 L AB224 085 L BB225 000 FCSETPOINT GENERATOR 3FOUR LOOPC

Strona 111

FCS WORKSHEET PAGE ___ OF ___MISCELLANEOUS DATAPOINTSDatapoint ValueEnteredTitle/CommentsAppend

Strona 112

MicroMod Automation, Inc. The Company MicroMod Automation is dedicated to improving customer efficiency by providing the most ost-effective, applica

Strona 113

2.7.4.3 COMPENSATED GAS FLOW (FC = 18 OR FC = 19)Pressure and temperature compensated gas flow equations for both linear and square root flow ele-men

Strona 114

FCS WORKSHEET PAGE ___ OF ___MISCELLANEOUS DATAPOINTSDatapoint ValueEnteredTitle/CommentsFCS 53

Strona 115

The Company’s policy is one of continuous product improvement and the rightis reserved to modify the information contained herein without notice, or

Strona 116

2.7.5 MATH AThe Math A module executes a selected function on three input variables A, B, and C. The func-tion to be executed by Math A is selected

Strona 117

2.7.6 LOGIC AThe Logic A module executes a selected function on two input variables A and B to produce an out-put. Input variables A and B, as well

Strona 118 - Table A-4. CS4 Wirelist

Logic FunctionsFC OUTPUT FC OUTPUT0A4A OR NOT B1 A OR B 5 A AND NOT B2 A AND B 6 J-K LATCH3 A XOR B 7 D LATCHInvert output if FC = FC + 128Expanded Lo

Strona 119

2.7.8 PARAMETER LOADER AThe Parameter Loader A (PLoad A) module passes a logic value (0/1) from the input B to the out-put C whenever the A input val

Strona 120

2.7.10 PARAMETER LOADER CThe Parameter Loader C (PLoad C) module passes a numeric value from the input B to the outputC whenever the A input value is

Strona 121

2.7.12 PARAMETER LOADER EThe Parameter Loader E (PLoad E) module passes a numeric value from the input B to the outputC whenever the A input value is

Strona 122

2.7.13 SETPOINT GENERATOR 0The Setpoint Generator 0 (SPG 0) module provides a continuous output signal that is derived fromone of three sources which

Strona 123

2.7.14 DEVIATION/ALARM CALCULATION 0The Deviation/Alarm Calculation 0 (D/C 0) module calculates and loads a Deviation Value (DV),based upon the Setpo

Strona 124

2.7.15 PROPORTIONAL INTEGRAL DERIVATIVE 0The Proportional Integral Derivative 0 (PID 0) module (which is part of the CON module) performsan interacti

Strona 125

Table of Contents1.0 INTRODUCTION 1-11.1 OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . .

Strona 126 - Table A-5. CS5 Wirelist

CO0...control outputCTC0...control track commandDV0...deviationFF0...feed forwardIR0...controller spanMR0...manual resetOH0...output high limitOL0...o

Strona 127

2.7.16 AUTO/MANUAL SWITCH 0The Auto/Manual Switch 0 (AMS 0) module provides a continuous output signal that is derivedfrom one of three sources which

Strona 128

2.7.17 MATH BThe Math B module executes a selected function on three input variables A, B, and C. The func-tion to be executed by Math B is selected

Strona 129

2.7.18 MATH CThe Math C module executes a selected function on three input variables A, B, and C. The func-tion to be executed by Math C is selected

Strona 130

2.7.19 LOGIC CThe Logic C module executes a selected function on two input variables A and B to produce an out-put. Input variables A and B, as well

Strona 131

Expanded Logic FunctionsINPUTS OUTPUT INPUTS INVERTED OUTPUTFC A B A FC A B A0 0 1 0 128 0 1 10 1 1 1 128 1 1 00 0 0 0 128 0 0 10 1 0 1 128 1 0 0FC A

Strona 132

2.7.20 EXTENDED MATH BThe Extended Math B (Emath B) module executes a selected function on three input variables A,B, and C. The function to be execu

Strona 133

2.7.20.1 PIECEWISE CHARACTERIZER/FUNCTION GENERATOR (FC=15)This FC permits linearization of input signal A or the generation of a function based on t

Strona 134 - Table A-6. CS20 Wirelist

2.7.20.3 COMPENSATED GAS FLOW (FC = 18 OR FC = 19)Pressure and temperature compensated gas flow equations for both linear and square root flow ele-me

Strona 135

2.7.21 MATH DThe Math D module executes a selected function on three input variables A, B, and C. The func-tion to be executed by Math D is selected

Strona 136

2.7.32 CONTROL 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-452.7.33 AUTO/MA

Strona 137

2.7.22 LOGIC DThe Logic D module executes a selected function on two input variables A and B to produce an out-put. Input variables A and B, as well

Strona 138

Logic FunctionsFC OUTPUT FC OUTPUT0A4A OR NOT B1 A OR B 5 A AND NOT B2 A AND B 6 J-K LATCH3 A XOR B 7 D LATCHInvert output if FC = FC + 128Expanded Lo

Strona 139

2.7.24 SETPOINT GENERATOR 1The Setpoint Generator 1 (SPG 1) module provides a continuous output signal that is derived fromone of three sources which

Strona 140

2.7.25 DEVIATION/ALARM CALCULATION 1The Deviation/Alarm Calculation 1 (D/C 1) module calculates and loads a Deviation Value (DV),based upon the Setpo

Strona 141

2.7.26 PROPORTIONAL INTEGRAL DERIVATIVE 1The Proportional Integral Derivative 1 (PID 1) module (which is part of the CON module) performsan interacti

Strona 142

CO1...control outputCTC1...control track commandDV1...deviationFF1...feed forwardIR1...controller spanMR1...manual resetOH1...output high limitOL1...o

Strona 143

2.7.27 AUTO/MANUAL SWITCH 1The Auto/Manual Switch 1 (AMS 1) module provides a continuous output signal that is derivedfrom one of three sources which

Strona 144 - Table A-7. CS21 Wirelist

2.7.28 MATH EThe Math E module executes a selected function on three input variables A, B, and C. The func-tion to be executed by Math E is selected

Strona 145

2.7.29 MATH FThe Math F module executes a selected function on three input variables A, B, and C. The func-tion to be executed by Math F is selected

Strona 146

2.7.30 LOGIC FThe Logic F module executes a selected function on two input variables A and B to produce an out-put. Input variables A and B, as well

Strona 147

List of TablesTable 3-1. Logical Oneshot Wirelist . . . . . . . . . . . . . . . . . . . . . . . . .

Strona 148

Expanded Logic FunctionsINPUTS OUTPUT INPUTS INVERTED OUTPUTFC A B A FC A B A0 0 1 0 128 0 1 10 1 1 1 128 1 1 00 0 0 0 128 0 0 10 1 0 1 128 1 0 0FC A

Strona 149

2.7.31 SETPOINT GENERATOR 2The Setpoint Generator 2 (SPG 2) module provides a continuous output signal that is derived fromone of three sources which

Strona 150

2.7.32 CONTROL 2The Control 2 (CON 2) module combines the operations of Deviation/Alarm Calculation (D/C) andProportional Integral Derivative (PID) m

Strona 151

ADB2...alarm dead bandAIX2...control alarm modeCO2...control outputCTC2...control track commandCZ2...control zoneDV2...deviationFF2...feed forwardIR2.

Strona 152

2.7.33 AUTO/MANUAL SWITCH 2The Auto/Manual Switch 2 (AMS 2) module provides a continuous output signal that is derivedfrom one of three sources which

Strona 153

2.7.34 LOGIC GThe Logic G module executes a selected function on two input variables A and B to produce an out-put. Input variables A and B, as well

Strona 154 - Table A-8. CS22 Wirelist

Expanded Logic FunctionsINPUTS OUTPUT INPUTS INVERTED OUTPUTFC A B A FC A B A0 0 1 0 128 0 1 10 1 1 1 128 1 1 00 0 0 0 128 0 0 10 1 0 1 128 1 0 0FC A

Strona 155

2.7.35 SETPOINT GENERATOR 3The Setpoint Generator 3 (SPG 3) module provides a continuous output signal that is derived fromone of three sources which

Strona 156

2.7.36 CONTROL 3The Control 3 (CON 3) module combines the operations of Deviation/Alarm Calculation (D/C) andProportional Integral Derivative (PID) m

Strona 157

ADB3...alarm dead bandAIX3...control alarm modeCO3...control outputCTC3...control track commandCZ3...control zoneDV3...deviationFF3...feed forwardIR3.

Strona 158

READ FIRSTWARNINGINSTRUCTION MANUALSDo not install, maintain, or operate this equipment without reading, understanding andfollowing the proper MicroMo

Strona 159

2.7.37 AUTO/MANUAL SWITCH 3The Auto/Manual Switch 3 (AMS 3) module provides a continuous output signal that is derivedfrom one of three sources which

Strona 160

2.7.38 LOGIC HThe Logic H module executes a selected function on two input variables A and B to produce an out-put. Input variables A and B, as well

Strona 161

Expanded Logic FunctionsINPUTS OUTPUT INPUTS INVERTED OUTPUTFC A B A FC A B A0 0 1 0 128 0 1 10 1 1 1 128 1 1 00 0 0 0 128 0 0 10 1 0 1 128 1 0 0FC A

Strona 162

2.7.39 ANALOG OUTPUT LOADERThe Analog Output (ANO0-4) Loader module has parameters which allow an FCS signal to bescaled to the proper units before i

Strona 163

2.7.40 CONTACT CLOSURE OUTPUT LOADERThe Contact Closure Output (CCO0-5) Loader module responds to the logic level L-value (0/1) in-puts for each CCO0

Strona 164 - Table A-9. CS40 Wirelist

2.7.41 STATUS DISPLAY 0 LOADERThe Status Display 0 (SDT0A-0H) Loader module allows FCS logic signals to be tied to SDT0 sothat configured messages ca

Strona 165

3.0 FCS WIRELIST EXAMPLES3.1 OVERVIEWThis section provides four Flexible Control Strategy wirelist examples. Each example has a brieffunctional des

Strona 166

3.2 EXAMPLE 1 - LOGICAL ONESHOTA logical oneshot can be used to toggle a Contact Closure Output (CCO) or reset a totalizer. Asshown in Figure 3-1, a

Strona 167

The wirelist is provided in Table 3-1, which is an example worksheet of this control strategy.Wirelist datapoint values and associated module paramete

Strona 168

Table 3-1. Logical Oneshot WirelistFCS WORKSHEET Oneshot PAGE 2 OF 2EXTENDED MATH AONE LOOPCOMMENTS

Strona 169

1.0 INTRODUCTION1.1 OVERVIEWThe 53MC5000 Process Control Station (PCS) can be easily adapted to serve in a variety of con-trol applications common t

Strona 170

3.3 EXAMPLE 2 - LOGIC OPERATED SWITCHSignal switching is built into the Setpoint Generator and Auto/Manual Selector modules, and condi-tional signal

Strona 171

Table 3-2. Logic Operated Switch - CCI0 = 1Step Module Input(s) Output(s) Comments5 DatapointC005C005 = B144 (ANI1)6ANO’s B100 = C005 (ANI1). ANO0 =

Strona 172

The wirelist is provided in Table 3-4, which is an example worksheet of this control strategy.Wirelist datapoint values and associated module paramete

Strona 173 - 4110-TXT

Table 3-4. Logic Operated Switch WirelistFCS WORKSHEET Switch PAGE 2 OF 4ANO LOAD OUTPUTONE, TWO,

Strona 174

Table 3-4. Logic Operated Switch WirelistFCS WORKSHEET Switch PAGE 3 OF 4EXTENDED MATH AONE LOOP

Strona 175 - Table A-10. CS41 Wirelist

Table 3-4. Logic Operated Switch WirelistFCS WORKSHEET Switch PAGE 4 OF 4PARAMETER LOADER BONE

Strona 176

3.4 EXAMPLE 3 - HIGH/LOW SELECTOR WITH RE-TRANSMISSIONUnder normal operation, the Setpoint Generator module is used to select an operating setpointfr

Strona 177

If ANI0 is greater than or equal to ANI1, the following event sequence occurs as described in Table3-5:Table 3-5. High/Low Selector - ANI0 ≥ ANI1Step

Strona 178

If ANI0 is less than ANI1, the following event sequence occurs as described in Table 3-6:Table 3-6. High/Low Selector - ANI0 < ANI1Step Module Inp

Strona 179

The wirelist is provided in Table 3-7, which is an example worksheet of this control strategy.Wirelist datapoint values and associated module paramete

Strona 180

2.0 FCS MODULES2.1 OVERVIEWThe Flexible Control Strategy (FCS) modules are the building blocks of the controller functionality.The modules are prese

Strona 181

Table 3-7. High/Low Selector WirelistFCS WORKSHEET Selector PAGE 2 OF 5ANO LOAD OUTPUTONE, TWO, AND

Strona 182

Table 3-7. High/Low Selector WirelistFCS WORKSHEET Selector PAGE 3 OF 5EXTENDED MATH AONE LOOPCOMME

Strona 183

Table 3-7. High/Low Selector WirelistFCS WORKSHEET Selector PAGE 4 OF 5PARAMETER LOADER BONE LOOPC

Strona 184 - CS41WKS2

Table 3-7. High/Low Selector WirelistFCS WORKSHEET Selector PAGE 5 OF 5DEVIATION/ALARM CALC 0ONE L

Strona 185

3.5 EXAMPLE 4 - MASTER RATIO CONTROLLERAs shown in Figure 3-4 below, this control strategy accepts two inputs: the Controlled Variable(CV) at ANI0 a

Strona 186

The wirelist is provided in Table 3-8, which is an example worksheet of this control strategy.Wirelist datapoint values and associated module paramete

Strona 187 - N/A — Not applicable

Table 3-8. Master Ratio Controller WirelistFCS WORKSHEET Ratio Controller PAGE 2 OF 6ANO LOAD OUTPUTONE, TWO, AND

Strona 188 - Appendix B. Master Worksheets

Table 3-8. Master Ratio Controller WirelistFCS WORKSHEET Ratio Controller PAGE 3 OF 6EXTENDED MATH AONE LOOPCOM

Strona 189

Table 3-8. Master Ratio Controller WirelistPARAMETER LOADER BONE LOOPCOMMENTS:W/L DEFLT VALUE NAMEB136 070 L AB137 070 L BB138 255 L CPARAMETER LO

Strona 190

Table 3-8. Master Ratio Controller WirelistDEVIATION/ALARM CALC 0ONE LOOPCOMMENTS: Output datapoints for this module are C119, C121, L110, L111.W/

Strona 191

module can not be connected to the numeric input of another (black output circles connect only toblack input diamonds and open output circles connect

Strona 192

Table 3-8. Master Ratio Controller WirelistFCS WORKSHEET Ratio Controller PAGE 6 OF 6MISCELLANEOUS DATAPOINTSData

Strona 193

APPENDIX A: CONTROL STRATEGY WIRELISTSA.1 STANDARD CONTROL STRATEGIESThe wirelists for the ten control strategies of the 53

Strona 194

A.1.1 CS1 - SINGLE-LOOP PID CONTROLLER The PID controller is designed to fulfill the requirements of a majority of process applications. It isused i

Strona 195

Figure A-1. CS1 Block DiagramAppendix A. Control Strategy Wirelists411-TXTA-3

Strona 196

Table A-1. CS1 WirelistANO LOAD OUTPUTONE, TWO, AND FOUR LOOPSCOMMENTS: ANO = (INPUT) x (SCALER) + BIASW/L DEFLT VALUE NAMEB100 000 (C) 031 ANO0 OZB

Strona 197

Table A-1. CS1 WirelistSDT0 LOAD OUTPUTONE, TWO, AND FOUR LOOPSCOMMENTS: W/L DEFLT VALUE NAMEB111 097 (L) 000 SDT-0A STA0 NAME1A055ALARMASMA0MODE0L352

Strona 198

Table A-1. CS1 WirelistEXTENDED MATH AONE LOOPCOMMENTS:W/L DEFLT VALUE NAMEB119 255 (C) 020 A K12C3650K11C3640K10C3630K9C3620K8C3610B120 254 (C) 022

Strona 199 - Title/Comments

Table A-1. CS1 WirelistB136 070 AB137 070 BB138 255 CPARAMETER LOADER CONE LOOPCOMMENTS:W/L DEFLT VALUE NAMEB139 070 AB140 255 (C) 030 BB141 255 (C)

Strona 200

Table A-1. CS1 WirelistB152 100 (C) 029 PV0B153 101 SP0T1-0C1170CZ0C1140PL1-0C103100PL2-0C1040ADB0C1052AIX0B3351PID 0ONE LOOPCOMMENTS:W/L DEFLT VALUE

Strona 201

Table A-1. CS1 WirelistB170 093 (L) 110 AB171 093 (L) 111 BB172 000 FCAppendix A. Control Strategy WirelistsCS1WKS1A-9