2.7.20 EXTENDED MATH B
The Extended Math B (Emath B) module executes a selected function on three input variables A,
B, and C. The function to be executed by Emath B is selected by entering a function code (FC)from
the table below into datapoint B176. Numeric values for parameter constants K1 through K12 can
also be entered into their respective datapoints, which may affect the output as determined by the
function code selected. The output can be a numeric (C033) and/or a logic (L092) value.
The tables that follow list the function codes, input variables, and parameters. An illustration of the
Emath module follows the tables. Complex function codes 15-19, which are listed in the table, are
described in Sections 2.7.20.1 through 2.7.20.3.
Extended Math Functions
FC C OUTPUT L OUTPUT FC C OUTPUT L OUTPUT
0 A No change 15 Piecewise characterizer No change
1(K1
×
A) + K2 No change 16 3rd order polynomial No change
2(K1
×
A) + (K2
×
B) + (K3
×
C) No change 17 11th order polynomial No change
3(K1
×
A
×
B
×
C) + K2 No change 18 Linear flow compensation No change
4(K1
×
[A
/
B]) + (K2
×
C) No change 19 Square root flow
compensation
No change
5([K1
×
A] + [K2
×
B]
/
C) + K3 No change 20 Limit to constant
(K1 < A < K2)
1 if A
K2 or K1
A
6([K1
×
A
×
B]
/
C) + K2 No change 0 otherwise
7([K1 + A]
/
[K2 + B])
×
K3 No change 21 Limit to variable
(K1
×
C < A < K2
×
B)
1 if A
K2
×
B or K1
×
C
A
8(K1
×
abs[A]) + K2 No change 0 otherwise
9K1
×
A
([K2
×
B] + K3)
No change 22 Compare to constant 1 if A
K1
10 K1
×
2
([K2
×
A] + K3)
No change 0 if A < K1 - K2
11 K1
×
log([K2
×
A] + K3) No change 23 Compare to variable 1 if A
(K1
×
B) + K2
FC + 128 yields square root of C output
0 if A < (K1
×
B) + K2 - K3
Inputs Inputs
WIRELIST SYMBOL DATA
TYPE
ASSIGNED VALUE WIRELIST SYMBOL DATA
TYPE
ASSIGNED VALUE
B173 A C B175 C C
B174 B C B176 FC N/A
OUTPUT DATAPOINTS:
C033, L092
Parameters Parameters
SYMBOL DATAPOINT ASSIGNED VALUE SYMBOL DATAPOINT ASSIGNED VALUE
K1 C366 K7 C372
K2 C367 K8 C373
K3 C368 K9 C374
K4 C369 K10 C375
K5 C370 K11 C376
K6 C371 K12 C377