Single Loop Process Controller Instruction Manual
72 Analog Backup Controller
.
Table 6-4. Contact Input Module (CCI)
Title Symbol
CCI
Datapoint
Default
Contact Input
(Display Only)
CCI L000 0
Contact Input
Invert
IINV L264 0
Tag Name
CITAG A262 CCI0
Table 6-5. Contact Output (CCO) Module
Title Symbol
CCO0
Datapoint
Default
Contact Output
(Display Only)
CCO L024 0
Contact Output
Invert
OINV L288 0
Tag Name
COTAG A280 CCO0
Note Although the Analog Backup Controller has a second CCO (CCO1),
it is not configurable for this control strategy.
Table 6-6. Controller Module (CON-0)
Title Symbol
CON-0
Datapoint
Default
Control Alarm
Mode
AIX B335 1
Control Action
RSW L106 1
Reverse Valve
RSV L109 0
Manual Fallback
Disable
MFD L120 0
Alarm Limit 1
PL1 C103 100
Alarm Limit 2
PL2 C104 0
Alarm Dead Band
ADB C105 2
Proportional Band
PB C106 100
Reset Time
TR C107 0