MODBUS RTU
COMMUNICATIONS GUIDE
22
WIRE CONNECTIONS
Table 13. Wire Connections for RS-232 Devices
PC Serial Port MOD30ML Mod RS-232 MOD30ML Modcell
25-Pin 9-Pin Port 1 Port 2 cell Port 1 Port 2
BI 9&10 7&8 MLP Master Slave BI 9&10 7&8 MLP
2 3 3 9 13 Hi-1 Tx
⇒
Rx 2 8 12 Hi-2
3 2 2 8 12 Hi-2 Rx
⇐
Tx 3 9 13 Hi-1
7 5 1 10 14 Lo-2 Gnd
⇔
Gnd 1 10 14 Lo-2
Table 14. Wire Connections for RS-485 (4 or 5-Wire) Devices
B&B Quatech OPTO-22 MOD30ML Mod RS-485 MOD30ML Modcell
3PXOCC2A
DSP-225 AC 24 AT Port 1 Port 2 cell
(4 or 5-Wire)
Port 1 Port 2
3PXCC2A DS-300 or AC 34 BI 9&10 7&8 MLP Master Slave BI 9&10 7&8 MLP 2050R
2 2 4 3 9 13 Hi-1 Tx+
⇒
Rx+ 5 11 15 Lo-1 35
3 7 5 2 8 12 Hi-2 Tx-
⇒
Rx- 4 10 14 Lo-2 34
9 4 8 5 11 15 Lo-1 Rx+
⇐
Tx+ 3 9 13 Hi-1 33
1 8 9 4 10 14 Lo-2 Rx-
⇐
Tx- 2 8 12 Hi-2 32
5331 Gnd
⇔
Gnd 1 29
B&B Quatech OPTO-22 RS-485 Commander
3PXOCC2A
DSP-225 AC 24 AT
(4 or 5-Wire)
C100
3PXCC2A DS-300 or AC 34 Master Slave MR250 C1900 C150 C200 C300 C310 C500 PR100
224Tx+
⇒
Rx+ 7 7 22 7 9 21 34 3
375Tx-
⇒
Rx- 8 6 23 6 102235 2
948Rx+
⇐
Tx+ 3 4 20 4 111832 5
189Rx-
⇐
Tx- 2 5 21 5 121933 6
533Gnd
⇔
Gnd 12 8 24 Gnd 8 20 36 8
Table 15. Wire Connections for RS-485 (2 or 3-Wire) Devices
B&B Quatech OPTO-22 MOD30ML Mod RS-485 MOD30ML Modcell
3PXOCC2A
DSP-225 AC 24 AT Port 1 Port 2 cell
(2 or 3-Wire)
Port 1 Port 2
3PXCC2A DS-300 or AC 34 BI 9&10 7&8 MLP Master Slave BI 9&10 7&8 MLP 2050R
2&9 2&4 4-8 3&5 9&11 13&15 Hi&Lo-1 RxTx+
⇔
RxTx+ 3&5 9 13 -1 33&35
3&1 7&8 5-9 2&4 8&10 12&14 Hi&Lo-2 RxTx-
⇔
RxTx- 2&4 8 12 -2 32&34
5331 Gnd
⇔
Gnd 1 29
B&B Quatech OPTO-22 RS-485 Commander
3PXOCC2A
DSP-225 AC 24 AT
(2 or 3-Wire)
C100
3PXCC2A DS-300 or AC 34 Master Slave MR250 C1900 C150 C200 C300 C310 C500 PR100
2&9 2&4 4-8 RxTx+
⇔
RxTx+ 3&7 4 22 4 34
3&1 7&8 5-9 RxTx-
⇔
RxTx- 2&8 5 23 5 35
533Gnd
⇔
Gnd 12 8 24 7 36
* NOTES: 1. MOD30ML and Modcell do not support MODBUS Master
communications with a 2-wire RS-485 module.
2. On Modcell MLP and MOD30ML, 4-wire modules are recommended for
all applications, even for 2-wire installations.
WARNING Incorrect wiring can damage communication hardware.
∆