Podsumowanie treści

Strona 1 - Training

Command Series Migration to MOD 30ML™ Training Tutorial and Reference Guide for Command Series Migration to MOD 30ML

Strona 2 - MicroMod Automation, Inc

Command Series Migration to MOD 30ML Function Codes – Introduction The user database is configurable and writable to make the instrument perform

Strona 3 - CONTENTS

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control To change the Algorithm Type (S18): Open the PID block and open the C

Strona 4

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control To change the Control Action (S21): Open the PID block and open the G

Strona 5

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control To enable Setpoint Tracking (FC21-S14): Open the PID block and open t

Strona 6

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control Notice that the only setpoint mode allowed is LOCAL: Figure P1.14. P

Strona 7 - INTRODUCTION

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control To change the process variable high alarm (FC21-S7): Open the PAD blo

Strona 8

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control To change the process variable low alarm (FC21-S8): Open the PAD bloc

Strona 9 - Function Codes – Introduction

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control a Refer to the following sections from the Function Codes – Gallery

Strona 10 - Environment Blocks:

Pre-configured Dual Loop PID Control GENERAL DESCRIPTION The advanced PID controller function code implements a proportional integral derivati

Strona 11

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control EXPLANATION Configuration with this compound requires understanding of

Strona 12 - Architecture

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control S11 PID Input – S11 Floating Point Gain Multiplier input for the PID.

Strona 13 - FUNCTION BLOCKS

Command Series Migration to MOD 30ML Function Codes – Introduction Display Interface Block(DIF): This block is used in MOD 30ML only. This block h

Strona 14

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control N PID Output – N Floating Point Output of the compound. PID.N is alre

Strona 15

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control To configure the inputs: Open the AIN block AIN1 for input 1. See figu

Strona 16

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control Figure P2.3. Dual loop PID with Local SP You will need to use a diff

Strona 17 - Function blocks

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control To change the display tag name for the PID: Open the display block PID

Strona 18 - Execution Order

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control To enable feedforward control and change the feedforward type (S6): Op

Strona 19 - COMPOUNDS:

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control To connect / change the value of the Gain Multiplier input (S11): Make

Strona 20 - Bailey FC Gallery

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control To change the value of the Manual Reset input (S5): To enter a local va

Strona 21 - Choose Parameter

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control To change the values of the following: Proportional Gain - S12 Integral

Strona 22 - Cancel Connection

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control To change the value of the Derivative Lag Constant (S15): Open the PID

Strona 23 - LOOP COMPOUNDS

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control To change the value of the Output Limits (S16, S17): Open the PID block

Strona 24 - Algorithms menu

Command Series Migration to MOD 30ML Function Codes – Introduction Figure 1 .1. Instrument Database Architecture 1 - 4

Strona 25

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control To change the Algorithm Type (S18): Open the PID block and open the Con

Strona 26 - THE CONFIGURATION PROCESS

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control To change the Control Action (S21): Open the PID block and open the Gen

Strona 27 - PID Display

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control To enable Setpoint Tracking (FC21-S14): Open the PID block and open the

Strona 28 - DIF block

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control Notice that the only setpoint mode allowed is LOCAL: Figure P2.14. Dua

Strona 29

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control To change the process variable high alarm (FC21-S7): Open the PAD block

Strona 30 - PID CONFIGURATION REFERENCE

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control To change the process variable low alarm (FC21-S8): Open the PAD block

Strona 31 - PID Control Tab

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control a Refer to the following sections from the Function Codes – Gallery Tu

Strona 32

Pre-configured Single Loop PID with Remote SP GENERAL DESCRIPTION The advanced PID controller function code implements a proportional integral

Strona 33

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP EXPLANATION Configuration with this compound requires underst

Strona 34 - PID Setpoint Tab

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP compound or change in the Control tab of the PID block. Change

Strona 35 -  Output Modes in MOD 30ML:

Command Series Migration to MOD 30ML Function Codes – Introduction I/O AND COMMUNICATION MODULE BLOCKS: These blocks specify the physical I/O comp

Strona 36 - PID Options Tab

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP S23 N/A N/A N/A SPTI PID Input – Floating Point Setpoint t

Strona 37 - GALLERY TUTORIAL

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP To configure the inputs: Open the AIN block AIN1 for input 1.

Strona 38

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP Figure P3 .3. PID with Remote SP You will need to use a dif

Strona 39 - OBJECTIVES

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP To change the display tag name for the PID: Open the display

Strona 40 - DOCUMENT

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP To enable feedforward control and change the feedforward type

Strona 41 - New Workspace

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP To connect / change the value of the Gain Multiplier input (S1

Strona 42

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP To change the value of the Manual Reset input (S5): To enter a

Strona 43 - New Project

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP To change the values of the following: Proportional Gain - S12

Strona 44 - Class Workspace

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP To change the value of the Derivative Lag Constant (S15): Open

Strona 45 - New Document

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP To change the value of the Output Limits (S16, S17): Open the

Strona 46 - Default Instrument

Command Series Migration to MOD 30ML Function Codes – Introduction Type Description Availability Input Function Blocks or signal conditioning

Strona 47

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP To change the Algorithm Type (S18): Open the PID block and ope

Strona 48 - Interface Block

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP To change the Control Action (S21): Open the PID block and ope

Strona 49 - CLC 03/04

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP To enable Setpoint Tracking (FC21-S14): Open the PID block and

Strona 50 - Properties

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP Remote Setpoint Configuration Options: Open the PID block and

Strona 51

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP Auto Bias: Bias value of remote setpoint is automatically man

Strona 52 - Open Compound

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP To change the process variable high alarm (FC21-S7): Open the

Strona 53 - Compound

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP To change the process variable low alarm (FC21-S8): Open the P

Strona 54 - Loop Block

Pre-configured Dual Loop PID with Remote SP GENERAL DESCRIPTION The advanced PID controller function code implements a proportional integral d

Strona 55 - Gallery Menu

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP reference that includes listing of most commonly used / changed

Strona 56

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP S10 N/A N/A N/A S11 PID Input – S11 Floating Point Gain Mult

Strona 57

Command Series Migration to MOD 30ML Function Codes – Introduction NM Notification Message MOD 30ML and Modcell SM Supervisory Message MOD 30M

Strona 58 - ADDING I/O

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP S21 PID Input – Discreet Controller Action. Choose the action

Strona 59 - AIN Block

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP To configure the inputs: Open the AIN block AIN1 for input 1. S

Strona 60 - VCI Properties

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP Figure P4.3. Dual PID with Remote SP You will need to use a

Strona 61

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP Figure P4.4. Dual PID with Remote SP P4- 7

Strona 62 - MAKING CONNECTIONS

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP To change the display tag name for the PID: Open the display bl

Strona 63 - Choose parameter

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP To enable feedforward control and change the feedforward type (S

Strona 64

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP To connect / change the value of the Gain Multiplier input (S11)

Strona 65

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP To change the value of the Manual Reset input (S5): To enter a l

Strona 66

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP To change the values of the following: Proportional Gain - S12 I

Strona 67

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP To change the value of the Derivative Lag Constant (S15): Open t

Strona 68 - SP) Compound

Command Series Migration to MOD 30ML Function Codes – Introduction A typical instrument database as function block diagram configured in ViZapp i

Strona 69 - ENG block

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP To change the value of the Output Limits (S16, S17): Open the PI

Strona 70

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP To change the Algorithm Type (S18): Open the PID block and open

Strona 71 - Faceplate

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP To change the Control Action (S21): Open the PID block and open

Strona 72 - 100. See the next figure:

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP To enable Setpoint Tracking (FC21-S14): Open the PID block and o

Strona 73

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP Remote Setpoint Configuration Options: Open the PID block and s

Strona 74 - Close Compound

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP Auto Bias: Bias value of remote setpoint is automatically manip

Strona 75

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP To change the process variable high alarm (FC21-S7): Open the PA

Strona 76

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP To change the process variable low alarm (FC21-S8): Open the PAD

Strona 77

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP a Refer to the following sections from the Function Codes – Gal

Strona 78 - SAVING DOCUMENTS

Pre-Configured – Cascade Control GENERAL DESCRIPTION This is a pre-configured loop compound that has inputs, outputs, complete Cascade loop PI

Strona 79

Command Series Migration to MOD 30ML Function Codes – Introduction Figure 1 .3. Function blocks inside a loop compound 1 - 9

Strona 80 - Communication

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control EXPLANATION Configuration with this loop compound requires understanding o

Strona 81 - COMPILING THE DATABASE

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control GAIN MULTIPLIER INPUT. S11 PID2 Input – S11 Floating Point Gain Multiplie

Strona 82 - Options for Modbus

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control S18 PID1, PID2, PIDFAIL Input – S18 Count Algorithm Type. Choose the type

Strona 83 - Information Window

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control To configure the inputs: Open the AIN block AIN1 for input 1. See figure b

Strona 84

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control Figure P5.3. Cascade PID You will need to use a different input function

Strona 85 - STRATEGIES

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control To change the display tag name for the PID: Open the display block Display

Strona 86

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control To enable feedforward control and change the feedforward type (S6): Open t

Strona 87

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control To connect / change the value of the Gain Multiplier input (S11): Make a co

Strona 88

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control To change the value of the Manual Reset input (S5): To enter a local value,

Strona 89

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control To change the values of the following: Proportional Gain - S12 Integral Res

Strona 90

Command Series Migration to MOD 30ML Function Codes – Introduction FUNCTION BLOCK EXECUTION ORDER: The order in which the blocks in the database

Strona 91

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control To change the value of the Derivative Lag Constant (S15): Open the respecti

Strona 92

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control To change the value of the Output Limits (S16, S17): Open the respective PI

Strona 93

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control To change the Algorithm Type (S18): Open the respective PID block and open

Strona 94

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control To change the Control Action (S21): Open the respective PID block and open

Strona 95

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control To enable Setpoint Tracking (FC21-S14): Open the respective PID block and o

Strona 96

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control To change the process variable high alarm (FC21-S7): Open the desired PAD b

Strona 97

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control To change the process variable low alarm (FC21-S8): Open the desired PAD bl

Strona 98

Pre-configured PID Ratio with Remote SP GENERAL DESCRIPTION The advanced PID controller function code implements a proportional integral deriv

Strona 99

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP reference that includes listing of most commonly used / changed attr

Strona 100 - PID with Local SP

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP S12 ENG Input – GAIN Floating Point Proportional Gain Kp. Enter in

Strona 101 - See figure below:

Command Series Migration to MOD 30ML Function Codes – Introduction COMPOUNDS: Function blocks in a database can be compounded (grouped) into a si

Strona 102

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP N PID Output – N Floating Point Output of the compound. PID.N is a

Strona 103

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP To configure the inputs: Open the AIN block AIN1 for input 1. See f

Strona 104

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP Figure P6.3. PID Ratio with Remote SP You will need to use a dif

Strona 105

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP To change the display tag name for the PID: Open the display block

Strona 106

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP To enable feedforward control and change the feedforward type (S6):

Strona 107 - UTILIZATION

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP To connect / change the value of the Gain Multiplier input (S11): Ma

Strona 108 - INPUTS – OUTPUTS

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP To change the value of the Manual Reset input (S5): To enter a local

Strona 109

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP To change the values of the following: Proportional Gain - S12 Integ

Strona 110

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP To change the value of the Derivative Lag Constant (S15): Open the P

Strona 111 - Dual loop

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP To change the value of the Output Limits (S16, S17): Open the PID bl

Strona 112

MicroMod Automation, Inc. The Company MicroMod Automation is dedicated to improving customer efficiency by providing the most cost-effective, applic

Strona 113 - Display Block

Command Series Migration to MOD 30ML Function Codes – Introduction Figure 1 .6. Inside a Compound • You can ungroup a compound by un-compoundin

Strona 114

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP To change the Algorithm Type (S18): Open the PID block and open the

Strona 115

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP To change the Control Action (S21): Open the PID block and open the

Strona 116

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP To enable Setpoint Tracking (FC21-S14): Open the PID block and open

Strona 117

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP Remote Setpoint Configuration Options: Open the PID block and select

Strona 118

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP Auto Bias: Bias value of remote setpoint is automatically manipulat

Strona 119

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP To change the process variable high alarm (FC21-S7): Open the PAD bl

Strona 120

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP To change the process variable low alarm (FC21-S8): Open the PAD blo

Strona 121

BOOK 2 REFERENCE SECTION 2 FUNCTION CODE COMPOUNDS

Strona 123

Function Code 1- Function Generator GENERAL DESCRIPTION This function approximates a nonlinear output to input relationship. The input range i

Strona 124

Command Series Migration to MOD 30ML Function Codes – Introduction • This will un-group the function blocks and place them where the grouped comp

Strona 125

Command Series Migration to MOD 30ML Function Code 1- Function Generator Figure 1 .2.Function Generator compound INPUTS - OUTPUTS INPUTS - OUT

Strona 126

Function Code 2- Manual Set Constant GENERAL DESCRIPTION The output of the Manual Set Constant or the Signal Generator is an analog signal dev

Strona 127

Command Series Migration to MOD 30ML Function Code 2- Manual Set Constant Millisecond time Format: hh:mm:ss.xxx (xxx in millisecond) Hex Hexadec

Strona 128 - INPUTS - OUTPUTS

Command Series Migration to MOD 30ML Error! No text of specified style in document. APPLICATIONS This compound is meant for storing of values that

Strona 129

Command Series Migration to MOD 30ML Function Code 2- Manual Set Constant 2 - 4

Strona 130

Function Code 3 - Lead / Lag GENERAL DESCRIPTION The output of a lead/lag function code equals the product of the time function and the input

Strona 131 - PID with Remote

Command Series Migration to MOD 30ML Function Code 3 - Lead / Lag EXPLANATION Function code 3 causes the output of the function block to lead or

Strona 132

Command Series Migration to MOD 30ML Function Code 3 - Lead / Lag Lag Function : To select the lag function, leave S3 at its initial value (0) and

Strona 133

Command Series Migration to MOD 30ML Function Code 3 - Lead / Lag 3 - 4

Strona 134

Function Code 6 – High / Low Limiter GENERAL DESCRIPTION This block limits the output signal to a range that lies between a specified high and

Strona 135

Command Series Migration to MOD 30ML Function Codes – Introduction • You can also double-click on the Compound Internals and then select from th

Strona 136

Command Series Migration to MOD 30ML Function Code 6 – High / Low Limiter 6 - 2

Strona 137

Function Code 7 – Square Root GENERAL DESCRIPTION This function computes the square root of the input signal in engineering units. The output

Strona 138

Command Series Migration to MOD 30ML Function Code 7 – Square Root N Output – R Floating Point Connect from the FC7.N signal of the compound.

Strona 139

Command Series Migration to MOD 30ML Function Code 7 – Square Root Figure 7 .3. LN block used for linearizing 7 - 3

Strona 140

Command Series Migration to MOD 30ML Function Code 7 – Square Root 7 - 4

Strona 141

Function Code 8 – Rate Limiter GENERAL DESCRIPTION The output of this block equals the input until the input rate of change exceeds the limit

Strona 142

Command Series Migration to MOD 30ML Function Code 8 – Rate Limiter INPUTS - OUTPUTS Signal Block Type Description S1 RATELIM Input – S1 Floa

Strona 143

Command Series Migration to MOD 30ML Function Code 8 – Rate Limiter To verify this, check the execution order of the blocks. Select Objects – Set

Strona 144

Command Series Migration to MOD 30ML Function Code 8 – Rate Limiter To change the Increase Rate Limit S3: Open the EX block INCLIM. Select the In

Strona 145

Command Series Migration to MOD 30ML Function Code 8 – Rate Limiter Figure 8 .5. Blocks Execution Order after rearranging 8 - 5

Strona 146 - Low Alarm

Command Series Migration to MOD 30ML Function Codes – Introduction LOOP COMPOUNDS Loop compound is a special compound that contains a loop block.

Strona 147

Command Series Migration to MOD 30ML Function Code 8 – Rate Limiter 8 - 6

Strona 148

Function Code 9 – Analog Transfer GENERAL DESCRIPTION This function selects one of two inputs depending on Boolean input <S3>. The outpu

Strona 149

Command Series Migration to MOD 30ML Function Code 9 – Analog Transfer S2 S1/S2 Input – S2 Floating Point Connect to the S1/S2.S2 signal of the

Strona 150

Command Series Migration to MOD 30ML Function Code 9 – Analog Transfer Figure 9 .2. Blocks Execution Order You can change the execution order of

Strona 151 - Remote SP

Command Series Migration to MOD 30ML Function Code 9 – Analog Transfer Figure 9 .4. Timer block S4 To change the transfer time (S5) for S2: Ope

Strona 152

Command Series Migration to MOD 30ML Function Code 9 – Analog Transfer Figure 9 .5. Timer Block S5 9 - 5

Strona 153

Command Series Migration to MOD 30ML Function Code 9 – Analog Transfer 9 - 6

Strona 154

Function Code 10 – High Select GENERAL DESCRIPTION This function selects and outputs the input with the highest algebraic value. UTILIZATION

Strona 155

Command Series Migration to MOD 30ML Function Code 10 – High Select S4 FC10 Input – S4 Floating Point Connect to the FC10.S4 signal to the Hig

Strona 156

Function Code 11 – Low Select GENERAL DESCRIPTION This function selects and outputs the input with the lowest algebraic value. UTILIZATION Th

Strona 157

Command Series Migration to MOD 30ML Function Codes – Introduction Figure 1 .13. Cancel Connection To add a loop compound: Select the Loop Cpd (

Strona 158

Command Series Migration to MOD 30ML Function Code 11 – Low Select N FC11 Output – R Floating Point Connect from the FC11.N output signal from

Strona 159

Function Code 12 – High / Low Compare GENERAL DESCRIPTION This function has two outputs. When the input is equal to or exceeds the high limit,

Strona 160

Command Series Migration to MOD 30ML Function Code 12 – High / Low Compare INPUTS - OUTPUTS Input Block Type Description S1 HIGHLIM Input –

Strona 161

Command Series Migration to MOD 30ML Function Code 12 – High / Low Compare NOTES To change the High alarm point / high limit: Open the HIGHLIM exp

Strona 162

Command Series Migration to MOD 30ML Function Code 12 – High / Low Compare Figure 12 .3. High Select Function Inputs 12 - 4

Strona 163

Function Code 14 - Summer GENERAL DESCRIPTION This function computes the algebraic sum of up to four inputs with unity gain. The output equati

Strona 164 - Hi Alarm

Command Series Migration to MOD 30ML Function Code 14 - Summer Figure 14 .2. Function Code 14 Input Configuration INPUTS - OUTPUTS Signal Bloc

Strona 165

Function Code 15 – Summer (2 Inputs) GENERAL DESCRIPTION This function performs a weighted sum of two inputs. By choosing the proper gains and

Strona 166

Command Series Migration to MOD 30ML Function Code 15 – Summer (2 Inputs) Figure 15 .2. Function Code 15 INPUTS - OUTPUTS Signal Block Type

Strona 167

Function Code 16 – Multiply GENERAL DESCRIPTION This function performs a multiplication of two input signals (S1 by S2) with the result multip

Strona 168

Command Series Migration to MOD 30ML Function Codes – Introduction • Loop compounds also have jump objects when connections are made from or to t

Strona 169

Command Series Migration to MOD 30ML Function Code 16 – Multiply Figure 16 .2. Function Code 16 INPUTS - OUTPUTS Signal Block Type Descripti

Strona 170

Function Code 17 – Divide GENERAL DESCRIPTION This function causes one input S1 to be divided by a second input S2 and the quotient to be mult

Strona 171

Command Series Migration to MOD 30ML Function Code 17 – Divide Figure 17 .2. Function Code 17 INPUTS - OUTPUTS Signal Block Type Description

Strona 172

Function Code 20 – Indicator Station GENERAL DESCRIPTION This function displays 3 inputs in one display one at a time. UTILIZATION The MOD

Strona 173 - Cascade PID

Command Series Migration to MOD 30ML Function Code 20 – Indicator Station Figure 20 .2. Function Code 14 Input Configuration Add the Display

Strona 174

Command Series Migration to MOD 30ML Error! No text of specified style in document. Figure 20 .3. Closing Compound • Click on the New button on t

Strona 175

Command Series Migration to MOD 30ML Function Code 20 – Indicator Station • A text edit box will appear in the area below and you will see a te

Strona 176

Command Series Migration to MOD 30ML Error! No text of specified style in document. INPUTS - OUTPUTS Signal Block Type Description S1 DISPLAY

Strona 177

Command Series Migration to MOD 30ML Function Code 20 – Indicator Station 20 - 6

Strona 178

Function Codes 25 and 41 – Analog/Digital Input GENERAL DESCRIPTION This function can be used to acquire an input (analog, digital or any othe

Strona 179

Command Series Migration to MOD 30ML Function Codes – Introduction THE CONFIGURATION PROCESS The steps involved configuring a MOD 30ML or Modcell

Strona 180

Command Series Migration to MOD 30ML Function Codes 25 and 41 – Analog/Digital Input   To configure the ICN communication in an instrument data

Strona 181

Command Series Migration to MOD 30ML Function Codes 25 and 41 – Analog/Digital Input Figure 25 .3. Function Code 25 and 41 To configure the sourc

Strona 182

Command Series Migration to MOD 30ML Function Codes 25 and 41 – Analog/Digital Input Figure 25 .4. IC Block INPUTS - OUTPUTS Signal Block Typ

Strona 183

Function Code 28 – Analog/Digital Output GENERAL DESCRIPTION This function can be used to send an output (analog, digital or any other data ty

Strona 184

Command Series Migration to MOD 30ML Function Code 28 – Analog/Digital Output   To configure the ICN communication in an instrument database, y

Strona 185

Command Series Migration to MOD 30ML Function Code 28 – Analog/Digital Output Instrument Number – This is the ICN address of the instrument wher

Strona 186 - Low Alarm

Command Series Migration to MOD 30ML Function Code 28 – Analog/Digital Output 28 - 4

Strona 187

Function Code 33 – NOT GENERAL DESCRIPTION Function code 33 performs a logical negation of the input (the output is the opposite of the input)

Strona 188

Command Series Migration to MOD 30ML Function Code 33 – NOT 33 - 2

Strona 189

Function Code 34 – Memory (RS Flip Flop) GENERAL DESCRIPTION This function memorizes its previous output when both inputs are logic 0. S1 is t

Strona 190

Command Series Migration to MOD 30ML Function Codes – Introduction Procedure for adding the Display Tag to the Display Interface Block Each displa

Strona 191 - PID Ratio with

Command Series Migration to MOD 30ML Function Code 34 – Memory (RS Flip Flop) Figure 34 .2. Function Code 34 S3 INPUTS - OUTPUTS Truth Table f

Strona 192

Function Code 35 – Timer GENERAL DESCRIPTION The timer function code performs pulsed timing function. The duration of time delay is specified

Strona 193

Command Series Migration to MOD 30ML Function Code 35 – Timer Figure 35 .2. Function Code 35 S3 INPUTS – OUTPUTS Signal Block Type Descript

Strona 194

Command Series Migration to MOD 30ML Error! No text of specified style in document. EXPLANATION I/O Elapsed Time < S3 Elapsed Time > S3 IN

Strona 195

Command Series Migration to MOD 30ML Function Code 35 – Timer 35 - 4

Strona 196

Function Code 36 – Qualified OR GENERAL DESCRIPTION The qualified OR function code monitors the status of up to eight digital inputs and produ

Strona 197

Command Series Migration to MOD 30ML Function Code 36 – Qualified OR To specify the value of S9, open the EX block and click on the Inputs tab. D

Strona 198

Command Series Migration to MOD 30ML Function Code 36 – Qualified OR Figure 36 .3. INPUTS - OUTPUTS Signal Block Type Description S1 FC36

Strona 199

Command Series Migration to MOD 30ML Function Code 36 – Qualified OR S7 FC36 Input – S7 Boolean (Discrete) Connect to the FC36.S7 signal of the

Strona 200

Function Code 37 – AND (2 input) GENERAL DESCRIPTION The 2-input AND function code performs the logical AND function. The output is logic 1 wh

Strona 201

Command Series Migration to MOD 30ML Function Codes – Introduction Figure 1 .16. DIF block Click on the New button on this block as shown in fig

Strona 202

Command Series Migration to MOD 30ML Function Code 37 – AND (2 input) Truth Table Figure 37 .2. Function Code 37 Truth Table 37 - 2

Strona 203

Function Code 38 – AND (4 input) GENERAL DESCRIPTION The 4-input AND function code performs the logical AND function. The output is logic 1 wh

Strona 204

Command Series Migration to MOD 30ML Function Code 38 – AND (4 input) N FC38 Output – R Boolean (Discrete) Connect from the FC.38.N signal of t

Strona 205

Function Code 39 – OR (2 input) GENERAL DESCRIPTION The 2-input OR function code performs the logical OR function. The output is logic 1 if ei

Strona 206

Command Series Migration to MOD 30ML Function Code 39 – OR (2 input) 39 - 2

Strona 207 - FUNCTION CODE COMPOUNDS

Function Code 40 – OR (4 input) GENERAL DESCRIPTION The 4-input OR function code is used to perform the logical OR function. The output is log

Strona 208

Command Series Migration to MOD 30ML Function Code 40 – OR (4 input) Truth Table Figure 40 .2. Function Code 40 Truth Table 40 - 2

Strona 209

Function Code 51- Manual Set Constant GENERAL DESCRIPTION The output of the Manual Set Constant or the Signal Generator is an analog signal de

Strona 210 - APPLICATIONS

Command Series Migration to MOD 30ML Function Code 51- Manual Set Constant INPUTS - OUTPUTS Signal Type Block Description S1 Input – S1 Float

Strona 211

Function Code 59- Digital Transfer GENERAL DESCRIPTION This function code selects one of two digital inputs, depending on a transfer switch si

Strona 212

Command Series Migration to MOD 30ML Function Codes – Introduction A text edit box will appear in the area below and you will see a text edit curs

Strona 213

Command Series Migration to MOD 30ML Function Code 59- Digital Transfer 59 - 2

Strona 214

Function Code 65 – Digital Sum with Gain GENERAL DESCRIPTION This function computes the weighted sum of up to four Boolean inputs. The output

Strona 215 - Function Code 3 - Lead / Lag

Command Series Migration to MOD 30ML Function Code 65 – Digital Sum with Gain Figure 65 .2. Function Code 65 Input Configuration INPUTS - OUTP

Strona 216

Command Series Migration to MOD 30ML Function Code 65 – Digital Sum with Gain S6 FC65 Input gain parameter – S6 Floating Point Connect to the F

Strona 217

Command Series Migration to MOD 30ML Function Code 65 – Digital Sum with Gain 65 - 4

Strona 218

Function Code 156 – PID with Local SP GENERAL DESCRIPTION The advanced PID controller function code implements a proportional integral derivat

Strona 219

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP EXPLANATION Configuration with this compound requires understanding o

Strona 220

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP GAIN to change the value. S13 ENG Input – RESET Floating Point Integra

Strona 221 - Function Code 7 – Square Root

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP S23 N/A N/A N/A SPTI PID Input – Floating Point Setpoint track inp

Strona 222 - VCI block used for

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP To enable feedforward control and change the feedforward type (S6): Ope

Strona 223 - LN block used for

Command Series Migration to MOD 30ML CONTENTS CONTENTS Page BOOK 1 SECTION 1 – FUNCTIONCODES - INTRODUCTION HOW TO USE THIS BOOK ...

Strona 224

Command Series Migration to MOD 30ML Function Codes – Introduction PID CONFIGURATION REFERENCE The PID block in the MOD 30ML/Modcell is versatile

Strona 225

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP To connect / change the value of the Gain Multiplier input (S11): Make

Strona 226

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP To change the value of the Manual Reset input (S5): To enter a local val

Strona 227 - Order after

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP To change the values of the following: Proportional Gain - S12 Integra

Strona 228

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP To change the value of the Derivative Lag Constant (S15): Open the PID b

Strona 229

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP To change the value of the Output Limits (S16, S17): Open the PID bloc

Strona 230

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP To change the Algorithm Type (S18): Open the PID block and open the Cont

Strona 231

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP To change the Control Action (S21): Open the PID block and open the Ge

Strona 232

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP To enable Setpoint Tracking (FC21-S14): Open the PID block and open the

Strona 233

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP Notice that the only setpoint mode allowed is LOCAL: Figure 156 .12.

Strona 234 - Timer block S4

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP To change the process variable high alarm (FC21-S7): Open the PAD block

Strona 235 - Timer Block S5

Command Series Migration to MOD 30ML Function Codes – Introduction Figure 1 .20. PID Control Tab • Select the Algorithm Type and change it to ES

Strona 236

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP To change the process variable low alarm (FC21-S8): Open the PAD block

Strona 237

Function Code 156 – PID (Cascade) GENERAL DESCRIPTION The advanced PID controller function code implements a proportional integral derivative

Strona 238

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) EXPLANATION Configuration with this compound requires understanding of th

Strona 239 - Function Code 11 – Low Select

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) of the PID2 block. Change the value for GAIN MULTIPLIER INPUT. S11 PIDFA

Strona 240

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) S19 N/A N/A N/A S21 PID1, PID2, PIDFAIL Input – S21 Discreet Controller

Strona 241

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) To change the display tag name for the PID: Open the display block Displ

Strona 242

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) To enable feedforward control and change the feedforward type (S6): Open

Strona 243 - Function Inputs

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) To connect / change the value of the Gain Multiplier input (S11): Make a

Strona 244

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) To change the value of the Manual Reset input (S5): To enter a local value

Strona 245 - Function Code 14 - Summer

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) To change the values of the following: Proportional Gain - S12 Integral R

Strona 246

Command Series Migration to MOD 30ML Function Codes – Introduction M 8 MICRO-SCAN. Reset response is turned on and is operating with MICRO-SCAN a

Strona 247

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) To change the value of the Derivative Lag Constant (S15): Open the respect

Strona 248

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) To change the value of the Output Limits (S16, S17): Open the respective

Strona 249 - Function Code 16 – Multiply

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) To change the Algorithm Type (S18): Open the respective PID block and open

Strona 250

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) To change the Control Action (S21): Open the respective PID block and ope

Strona 251 - Function Code 17 – Divide

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) To enable Setpoint Tracking (FC21-S14): Open the respective PID block and

Strona 252

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) To change the process variable high alarm (FC21-S7): Open the desired PAD

Strona 253

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) To change the process variable low alarm (FC21-S8): Open the desired PAD b

Strona 254 - Configuration

Function Code 156 – PID with Remote SP GENERAL DESCRIPTION The advanced PID controller function code implements a proportional integral deriva

Strona 255 - Closing Compound

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP EXPLANATION Configuration with this compound requires understanding

Strona 256

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP Floating Point GAIN to change the value. S13 ENG Input – RESET Flo

Strona 257 - OPERATION

Command Series Migration to MOD 30ML Function Codes – Introduction  The valid actions for CATYPE are: EOOO Gain on error, Reset off, Pre-Act of

Strona 258

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP N PID Output – N Floating Point Output of the compound. Connect fro

Strona 259

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP To change the display tag name for the PID: Open the display block

Strona 260 - Function Code 25

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP To enable feedforward control and change the feedforward type (S6):

Strona 261

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP To connect / change the value of the Gain Multiplier input (S11): Ma

Strona 262

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP To change the value of the Manual Reset input (S5): To enter a local

Strona 263

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP To change the values of the following: Proportional Gain - S12 Integ

Strona 264 - Function Code 28

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP To change the value of the Derivative Lag Constant (S15): Open the PI

Strona 265

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP To change the value of the Output Limits (S16, S17): Open the PID bl

Strona 266

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP To change the Algorithm Type (S18): Open the PID block and open the C

Strona 267 - Function Code 33 – NOT

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP To change the Control Action (S21): Open the PID block and open the

Strona 268

Command Series Migration to MOD 30ML Function Codes – Introduction • Click on the Setpoint tab to select the Setpoint configuration options. See

Strona 269

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP To enable Setpoint Tracking (FC21-S14): Open the PID block and open t

Strona 270

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP Remote Setpoint Configuration Options: Open the PID block and selec

Strona 271 - Function Code 35 – Timer

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP Auto Bias: Bias value of remote setpoint is automatically manipulate

Strona 272

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP To change the process variable high alarm (FC21-S7): Open the PAD bl

Strona 273

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP To change the process variable low alarm (FC21-S8): Open the PAD bloc

Strona 274

Function Code 156 – PID Ratio with Remote SP GENERAL DESCRIPTION The advanced PID controller function code implements a proportional integral

Strona 275

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP reference that includes listing of most commonly used / changed

Strona 276 - Function Code 36

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP Floating Point Inputs tab and select the input RESET to change

Strona 277

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP To change the display tag name for the PID: Open the display b

Strona 278

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP To enable feedforward control and change the feedforward type

Strona 279

Command Series Migration to MOD 30ML Function Codes – Introduction • Click on the Output tab to select the output configuration options. See the

Strona 280 - Truth Table

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP To connect / change the value of the Gain Multiplier input (S11

Strona 281

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP To change the value of the Manual Reset input (S5): To enter a

Strona 282

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP To change the values of the following: Proportional Gain - S12

Strona 283

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP To change the value of the Derivative Lag Constant (S15): Open

Strona 284

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP To change the value of the Output Limits (S16, S17): Open the P

Strona 285

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP To change the Algorithm Type (S18): Open the PID block and ope

Strona 286

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP To change the Control Action (S21): Open the PID block and open

Strona 287

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP To enable Setpoint Tracking (FC21-S14): Open the PID block and

Strona 288

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP Remote Setpoint Configuration Options: Open the PID block and s

Strona 289

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP Auto Bias: Bias value of remote setpoint is automatically man

Strona 290

Command Series Migration to MOD 30ML Function Codes – Introduction block or it can be an internal value in the PID block that can be manually cha

Strona 291

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP To change the process variable high alarm (FC21-S7): Open the P

Strona 292

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP Figure 156rr .15. Process Variable Low Alarm PID Ratio with R

Strona 293

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP 156rr - 18

Strona 294

Function Code 156 – PID with Manual/Auto Station GENERAL DESCRIPTION The PID with Manual/Auto station function basically performs Manual / Aut

Strona 295

Command Series Migration to MOD 30ML Function Code 156 – PID with Manual/Auto Station EXPLANATION Configuration with this compound requires unde

Strona 296

Command Series Migration to MOD 30ML Function Code 156 – PID with Manual/Auto Station S12 M/A Input – GAIN Floating Point Proportional Gain Kp. E

Strona 297 - 156 - 3

Command Series Migration to MOD 30ML Function Code 156 – PID with Manual/Auto Station To change the display tag name for the PID: Open the displ

Strona 298 - Function Code

Command Series Migration to MOD 30ML Function Code 156 – PID with Manual/Auto Station To enable feedforward control and change the feedforward type

Strona 299

Command Series Migration to MOD 30ML Function Code 156 – PID with Manual/Auto Station To connect / change the value of the Gain Multiplier input

Strona 300

Command Series Migration to MOD 30ML Function Code 156 – PID with Manual/Auto Station To change the value of the Manual Reset input (S5): To enter

Strona 301

BOOK 1 SECTION 2 GALLERY TUTORIAL

Strona 302

Command Series Migration to MOD 30ML Function Code 156 – PID with Manual/Auto Station To change the value of the Derivative Lag Constant (S15): O

Strona 303

Command Series Migration to MOD 30ML Function Code 156 – PID with Manual/Auto Station To change the value of the Output Limits (S16, S17): Open the

Strona 304

Command Series Migration to MOD 30ML Function Code 156 – PID with Manual/Auto Station To change the Control Action (S21): Open the PID block and

Strona 305

Command Series Migration to MOD 30ML Function Code 156 – PID with Manual/Auto Station Note that the OP (Output) of the PID block is connected to th

Strona 306

Command Series Migration to MOD 30ML Function Code 156 – PID with Manual/Auto Station Notice that the only setpoint mode allowed is REMOTE: Figur

Strona 307

Function Code 156 – Auto Bias Station GENERAL DESCRIPTION The PID with Auto Bias Station is basically a Manual/Auto station that performs Manu

Strona 308

Command Series Migration to MOD 30ML Function Code 156 – Auto Bias Station EXPLANATION Configuration with this compound requires understanding o

Strona 309

Command Series Migration to MOD 30ML Function Code 156 – Auto Bias Station MULTIPLIER INPUT. S12 AUTO BIAS Input – GAIN Floating Point Proport

Strona 310

Command Series Migration to MOD 30ML Function Code 156 – Auto Bias Station To change the display tag name for the PID: Open the display block PI

Strona 311

Command Series Migration to MOD 30ML Function Code 156 – Auto Bias Station To enable feedforward control and change the feedforward type (S6):

Strona 313

Command Series Migration to MOD 30ML Function Code 156 – Auto Bias Station To connect / change the value of the Gain Multiplier input (S11): Make

Strona 314

Command Series Migration to MOD 30ML Function Code 156 – Auto Bias Station To change the value of the Manual Reset input (S5): To enter a local

Strona 315

Command Series Migration to MOD 30ML Function Code 156 – Auto Bias Station To change the values of the following: Proportional Gain - S12 Integra

Strona 316

Command Series Migration to MOD 30ML Function Code 156 – Auto Bias Station To change the value of the Derivative Lag Constant (S15): Open the PI

Strona 317

Command Series Migration to MOD 30ML Function Code 156 – Auto Bias Station To change the value of the Output Limits (S16, S17): Open the PID bloc

Strona 318

Command Series Migration to MOD 30ML Function Code 156 – Auto Bias Station Note that the OP (Output) of the PID block is connected to the SPTI (

Strona 319

Command Series Migration to MOD 30ML Function Code 156 – Auto Bias Station Notice that the only setpoint mode allowed is REMOTE: Figure 156ab .10

Strona 320

Function Code 165 - Moving Average GENERAL DESCRIPTION The moving average function code computes a moving average from n samples taken at a de

Strona 321

Command Series Migration to MOD 30ML Function Code 165 - Moving Average INPUTS - OUTPUTS Signal Type Block Description S1 Input – S1 Floating

Strona 322

BOOK 2 REFERENCE SECTION 3 EXTRAS

Strona 323

Function Codes – Gallery Tutorial FOREWORD The ViZapp (Visual Application Designer) software has a library of function block compounds that rep

Strona 325

Extras – Reject to Manual GENERAL DESCRIPTION The Reject to Manual compound sends a logical Zero output when its digital input does a low to h

Strona 326

Command Series Migration to MOD 30ML Extras – Reject to Manual INPUTS - OUTPUTS Signal Type Block Description S1 Input – S1 Discrete QUALLOGI

Strona 328

The Company’s policy is one of continuous product improvement and the right is reserved to modify the information

Strona 329

Command Series Migration to MOD 30ML CONTENTS BOOK 2 – FUNCTION CODE GALLERY COMPOUNDS REFERENCE SECTION 1 – PRE-CONFIGURED CONTROL STRATEGIES 1

Strona 330 - Floating Point

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial INSTRUCTIONS – CREATING A NEW WORKSPACE, PROJECT AND DOCUMENT 1. Launch Vi

Strona 331

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .3. New Workspace • By default, the workspace file is created i

Strona 332

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial  • The New dialog box will redisplay Figure 2 .5. New Workspace • T

Strona 333

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial • Notice that the workspace Class is added to the project tree. We will cr

Strona 334

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .9. Class Workspace • The left frame shows the project tree. T

Strona 335

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .10. New Document • The New dialog box shows the Document tab no

Strona 336

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .11. Choose Instrument Version • Select MOD 30ML 2 from this li

Strona 337

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial  Each instrument will have its own database. The databases of the instrum

Strona 338

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial CONFIGURING SCAN GROUPS AND LOOP COMPOUNDS 5. Let us first configure a sc

Strona 339

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial M/A Station – Function Code 21 Analog output AO – Function Code 29 Figure 2

Strona 340

Command Series Migration to MOD 30ML CONTENTS 20 FUNCTION CODE 35 – TIMER...

Strona 341

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial • Select the Loop Cpd (Loop compound) block from the Algorithms window ad

Strona 342

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial • Type a description "This compound is for the Flow Control Loop"

Strona 343

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .19. Open Compound • The loop compound will open as shown below

Strona 344

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .20. Inside the Loop Compound  A loop compound is a compound or

Strona 345

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .21. Loop Block • Close the Loop block by clicking on the OK bu

Strona 346

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial ADDING COMPOUND FROM THE GALLERY 11. We will now use a compound from the B

Strona 347

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .23. Bailey FC Gallery • The compounds in this gallery have be

Strona 348

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .24. Bailey FC Gallery • The exported compound will be placed in

Strona 349

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial ADDING I/O 12. The loaded compound has all the function blocks for doing t

Strona 350

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial • Resize the block by dragging one of the handles (corner or side) Figure

Strona 351

Command Series Migration to MOD 30ML CONTENTS iv

Strona 352

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial • The next function block VCI, is a signal conditioning block. This block

Strona 353

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .29. PID Options Tab • Click on OK to accept the changes and clo

Strona 354

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial MAKING CONNECTIONS 15. The next step is to connect the blocks together.

Strona 355

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .33. Connecting blocks • The connection will now be complete. Th

Strona 356

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .35. Right Angle connection • Click on the output point of the

Strona 357

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .37. Choose Parameter • Select PID.S1 from the list and then cli

Strona 358

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .39. Cancel Connection 17. Connect the PID output from the com

Strona 359

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .41. 2 - 29

Strona 360 - High Alarm

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial CHANGING ENGINEERING RANGES AND ALARM TRIP VALUES 18. The FC156 PID (PV/L

Strona 361

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .44. ENG block • Select the Inputs tab of this block. Double-cl

Strona 362

BOOK 1 SECTION 1 FUNCTION CODES – INTRODUCTION

Strona 363

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .45. ENG block • Repeat the above process to configure the Low

Strona 364

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial  If you press the ALARM key on the faceplate when the alarm is active, th

Strona 365 - 156ma - 3

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial CONFIGURING DISPLAY TAG FOR THE PID DISPLAY 19. Each display configured i

Strona 366

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .48. PID Display • Click on OK to close the block. 2 - 35

Strona 367

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial 20. Close the compound: • First click on a blank area of the function b

Strona 368

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial 21. Add the Display Tag to the Display Interface Block: The next step is t

Strona 369

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .52. Closing Compound • A text edit box will appear in the are

Strona 370

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .53. Closing Compound • Refer back to the figure 1-37 for the di

Strona 371

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial SAVING DOCUMENTS 22. Save your Document. Figure 2 .54. File Menu • I

Strona 372

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial SETTING UP COMMUNICATIONS WITH MODBUS 23. We need to setup communications f

Strona 374

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial  The connections for the port are available in the terminals in the back

Strona 375

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial COMPILING THE DATABASE It is necessary to compile the database without erro

Strona 376

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .60. Interface File Options for Modbus • If the database has er

Strona 377

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .61. Information Window • You can double-click on an error to o

Strona 378 - Auto Bias Station

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial 2 - 46

Strona 379

BOOK 2 REFERENCE SECTION 1 PRE-CONFIGURED CONTROL STRATEGIES

Strona 381

Pre-configured Single Loop PID Control GENERAL DESCRIPTION The advanced PID controller function code implements a proportional integral deriva

Strona 382

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control EXPLANATION Configuration with this compound requires understanding

Strona 383

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control of the PID block. Change the value for GAIN MULTIPLIER INPUT. S12 EN

Strona 384

Function Codes – Introduction HOW TO USE THIS BOOK This book is meant for users of Bailey SLC, CLC controllers who are migrating to the new gen

Strona 385

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control the first loop. S22 N/A N/A N/A S23 N/A N/A N/A SPTI PID Input

Strona 386

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control To configure the inputs: Open the AIN block AIN1 for input 1. See fi

Strona 387

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control Figure P1.3. PID with Local SP You will need to use a different in

Strona 388

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control To change the display tag name for the PID: Open the display block P

Strona 389 - SECTION 3

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control To enable feedforward control and change the feedforward type (S6):

Strona 390

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control To connect / change the value of the Gain Multiplier input (S11): Mak

Strona 391 - Extras – Reject to Manual

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control To change the value of the Manual Reset input (S5): To enter a local

Strona 392

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control To change the values of the following: Proportional Gain - S12 Integr

Strona 393

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control To change the value of the Derivative Lag Constant (S15): Open the PI

Strona 394

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control To change the value of the Output Limits (S16, S17): Open the PID blo