Command Series Migration to MOD 30ML
Pre-configured PID Ratio with Remote SP
To change the process variable low alarm (FC21-S8):
Open the PAD block LOW ALARM. Change the value of the Trip Value by typing.
See figure below:
Figure P6.17.
Process Variable
Low Alarm
PID Ratio with
Remote SP
a Refer to the following sections from the Function Codes – Gallery Tutorial chapter:
Saving Documents
Setting up communications
Compiling the database
a Refer to chapter 4 in the ViZapp Training manual (IB-VIZAPP-TUT) after completing
the above sections for setting up the OPC Server and downloading the database to the
MOD 30ML Controller.
P6- 20
Przeglądanie stron 205