Function Code 37 – AND (2 input)
GENERAL DESCRIPTION
The 2-input AND function code performs the logical AND function.
The output is logic 1 when both inputs are logic 1.
UTILIZATION
The MOD 30ML/MODCELL compound FC37 uses an EX block with 2 inputs. S1 and
S2 are the inputs for the logical AND function.
Figure 37 .1.
Function Code 37
INPUTS - OUTPUTS
Signal Block Type Description
S1 FC37 Input – S1 Boolean
(Discrete)
Connect to the FC37.S1 signal of the
compound. Input S1 to the AND function.
S2 FC37 Input – S2 Boolean
(Discrete)
Connect to the FC37.S2 signal of the
compound. Input S2 to the AND function.
N FC37 Output – R
Boolean (Discrete)
Connect from the FC.37.N signal of the
compound. Result of the logic.
37 - 1