Command Series Migration to MOD 30ML
Error! No text of specified style in document.
EXPLANATION
I/O Elapsed Time < S3 Elapsed Time > S3
INPUT
OUTPUT
The output becomes logic 1 whenever the input becomes logic 1. If the input returns to
logic 0 before the time delay (S3) ends, the output will remain logic 1 for the entire
interval. If the input remains a logic 1 after the time delay expires, the output will return to
a logic 0 at the end of the time delay, and remain a logic 0 until there is another 0 to 1
transition of the input. Despite how long the input value remains in the logic 1 state, the
output remains in the logic 1 state for the duration of the time delay specified in S3. The
characteristic of the pulse output mode is often called one shot.
35 - 3