Micromod RetroPAK: SLC Configuration Manual Instrukcja Użytkownika Strona 320

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 394
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 319
Command Series Migration to MOD 30ML
Function Code 156 – PID (Cascade)
To change the value of the Derivative Lag Constant (S15):
Open the respective PID block and open the Control tab. Change the Input Filter Type to
Pre-act, User. Type a value in floating point units in the Input Filter Time field.
See figure below:
Figure 156c .7.
Function Code
156
Cascade PID
The filter time in minutes (floating point value) when USER is specified as the filter type.
Otherwise, it is 0.0.
0.0 = no filtering (last sampled value is the input value)
1.0 = 1 minute
1000.0 = 1000 minutes (maximum value)
Note that exceptionally large values tend to maintain the previous value whereas very
small values tend to maintain the most recent sampled value.
156c - 10
Przeglądanie stron 319
1 2 ... 315 316 317 318 319 320 321 322 323 324 325 ... 393 394

Komentarze do niniejszej Instrukcji

Brak uwag