Command Series Migration to MOD 30ML
Pre-Configured – Cascade Control
Figure P5.3.
Cascade PID
You will need to use a different input function block if the input selected in the AIN block
is other than voltage / current. Use the following rule:
Input Type Input Function block Type
Current, Voltage, Milli voltage VCI (voltage or current input)
TTI (thermocouple transmitter input)
RTTI (RTD transmitter input)
Thermocouple TI (thermocouple input)
RTD RTI (RTD Input)
Resistance RI (resistance Input)
Configuration of Input 2 (for the Remote setpoint PID.S2) is similar to this. The function
blocks for input2 are AIN2 and ENG UNITS 2.
P5- 6