F-CIM 53
AUTO/MANUAL SWITCH - 1
NOT REUSABLE
INPUTS NAME SYMBOL DATAPOINT
S
n-1
CONTROL OUTPUT CO1 C159
A AUTO ENABLE AE1 L138
B OUTPUT TRACK VALVE OTV1 C165
C OUTPUT TRACK SWITCH SWOTV1 L141
PARAMETERS OUTPUT TRACK ENABLE OTE1 L143
HARD MANUAL LIMIT HML1 L146
OUTPUT HIGH LIMIT OH1 C145
OUTPUT LOW LIMIT OL1 C146
OUTPUT SLEW RATE T31 C154
OUTPUTS
S
n
OUTPUT OUT1 C138
OUTPUT TRACK STATUS OVTS1 L129
AUTO STATUS AUT1 L131
Description:
This module selects one of three signals to load into OUT and become its output
(S
n
). The signal selected is either the Output Tracking Value (B), the Auto Value
(S
n-1
) or the Manual Pushbutton Value. If the Output Tracking Switch (C) is less
than 1, then S
n
= B when Output Tracking is enabled (OTE = 1). When the pre-
vious condition is not in effect S
n
will equal S
n-1
if Auto Enable (A) is 1 and the
A/M pushbutton has set the Auto Switch to 1. When neither previous condition is
in effect the selected signal comes directly from the output increase and decrease
pushbuttons.