F-CIM 63
AUTO/MANUAL SWITCH - 2
NOT REUSABLE
INPUTS NAME SYMBOL DATAPOINT
S
n-1
CONTROL OUTPUT CO2 C195
A AUTO ENABLE AE2 L162
B OUTPUT TRACK VALVE OTV2 C201
C OUTPUT TRACK SWITCH SWOTV2 L165
PARAMETERS OUTPUT TRACK ENABLE OTE2 L167
HARD MANUAL LIMIT HML2 L170
OUTPUT HIGH LIMIT OH2 C181
OUTPUT LOW LIMIT OL2 C182
OUTPUT SLEW RATE T32 C190
OUTPUTS
S
n
OUTPUT OUT2 C174
OUTPUT TRACK STATUS OVTS2 L153
AUTO STATUS AUT2 L155
Description:
This module selects one of three signals to load into OUT and become its output
(S
n
). The signal selected is either the Output Tracking Value (B), the Auto Value
(S
n-1
) or the Manual Pushbutton Value. If the Output Tracking Switch (C) is less
than 1, then S
n
= B when Output Tracking is enabled (OTE = 1). When the pre-
vious condition is not in effect S
n
will equal S
n-1
if Auto Enable (A) is 1 and the
A/M pushbutton has set the Auto Switch to 1. When neither previous condition is
in effect the selected signal comes directly from the output increase and decrease
pushbuttons.
MODULAR CONTROLLER CUSTOMIZATION GUIDE