3.4.8 PARAMETER DISPLAY MODULE
Eight Parameter Display Modules are present in the controller. Each module provides display and
pushbutton access to any three parameters in the database.
TITLE:
This is a 10 character name which is associated with the module.
POINT NAME 1, 2 and 3:
Each module allows three 10 character names to be associated with the three individual parame-
ters of the module.
POINT DESIGNATOR 1, 2 and 3:
These designates the three datapoints to be included in this module. Any database datapoint speci-
fier is allowed.
MODIFY DISABLE:
When this value is "1" the members of this module can not be changed through the pushbutton
activity. The values of these parameters are only for display purposes. When this value is "0" the
values of the module members can be altered by the operator when the module is displayed.
DISPLAY:
This is the index number for the display that provides access through the parameter module.
MODULAR CONTROLLER QUICK START
3-40