Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller Instrukcja Użytkownika Strona 82

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 99
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 81
4.2.4 CONTROL OPTIONS - REMOTE SETPOINT
The 53MC5000 is capable of accepting a setpoint from a remote instrument for loop #1 through
AI2.
1. Configure the RSP input signal parameters:
Set C258 to the span (in Engineering Units) and C278 to the minimum (in
Engineering Units) of the RSP range.
The 53MC5000 is set to accept a 1-5 V RSP signal. If 0-5 V is required, set
L487=1. The 53MC5000 is set to accept a linear PV signal. If square root extraction
is required, set L442=1.
2. Enable the Remote Setpoint capability by setting L115=1. The 53MC5000 will permit remote set-
point operation if DI0 is closed.
The 53MC5000 is capable of accepting a setpoint from a remote instrument for Loop #2 through
AI3.
1. Configure the RSP input signal parameters:
Set C259 to the span (in Engineering Units) and C279 to the minimum (in
Engineering Units) of the RSP range.
The 53MC5000 is set to accept a 1-5 V RSP signal. If 0-5 V is required, set
L497=1. The 53MC5000 is set to accept a linear PV signal. If square root extraction
is required, set L443=1.
2. Enable the Remote Setpoint capability by setting L139=1. The 53MC5000 will permit remote set-
point operation if DI1 is closed.
MODULAR CONTROLLER QUICK START
4-12
Przeglądanie stron 81
1 2 ... 77 78 79 80 81 82 83 84 85 86 87 ... 98 99

Komentarze do niniejszej Instrukcji

Brak uwag