53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
Table C-2. Database
Title Symbol Datapoint Default Attribute
Control Tag Name
CTAG A000 CON-0
Assignable 10 character name that appears with the
control strategy (CS1-4) displays.
Engineering Units
CEU A001 PERCENT
The default is
PERCENT, but is assignable as units of
measure the Process Variable represents.
System Module Tag
Name
TAG A008 SL5100
Assignable 10 character name for the system
module.
Parameter Title
PTAG A014
CON-0
TUNE
Assignable 10 character name for the parameter
display.
Parameter Point 1
Name
PNA A015
PROP.
BAND
Assignable 10 character name for the Point 1
Designator of the parameter display.
Parameter Point 2
Name
PNB A016 RESET
Assignable 10 character name for the Point 2
Designator of the parameter display.
Parameter Point 3
Name
PNC A017 RATE
Assignable 10 character name for the Point 3
Designator of the parameter display.
ANI0 Tag Name
AITAG A224 ANI0
Assignable 10 character name for analog input 0.
ANI1 Tag Name
AITAG A225 ANI1
Assignable 10 character name for analog input 1.
ANO0 Tag Name
AOTAG A244 ANO0
Assignable 10 character name for analog output 0.
CCI Tag Name
CITAG A262 CCI0
Assignable 10 character name for the contact
control input.
CCO Tag Name
COTAG A280 CCO0
Assignable 10 character name for the contact
control output.
ANI0 Engineering
Units
AIEU A298 PERCENT
Assignable for units of meature ANI0 represents
(e.g., GPM for gallons/minute).
ANI1 Engineering
Units
AIEU A299 PERCENT
Assignable for units of meature ANI1 represents
(e.g., GPM for gallons/minute).
Function
Index
FIX B000 0
The operational algorithm of the unit is selected by
the
value of this parameter:
0 = Suspend Mode; no control algorithm execution.
The logo is displayed.
1 = CS1, Single Loop PID Controller operation.
2 = CS2, Analog Backup Controller operation.
3 = CS3, Ration Controller operation.
4 = CS4, Automatic/Manual Station operation.
97 = Display Test. The entire display alternately
flashes on and off. When off, a border around the
display perimeter remains lit.
98 = Default Database. Defaults the database, then
sets FIX 0 for suspend mode, which displays the
logo.
Datalink Instrument
Address
IA B001 0
It identifies the address of this instrument on the
Datalink network. Each unit connected to the
Datalink network must have its own unique address.
Valid addresses are from 0 to 31.
Datalink Baud Rate
BR B002 253
This datapoint value designates the baud rate (data
transfer rate) of the Datalink network. The baud rate
must be the same for all of the instruments
connected to the same Datalink network. Datapoint
values and their corresponding baud rates are as
follows:
102