Micromod Micro-DCI: 53SL6000 Single Loop Controller Instrukcja Użytkownika

Przeglądaj online lub pobierz Instrukcja Użytkownika dla Ekwipunek Micromod Micro-DCI: 53SL6000 Single Loop Controller. Micromod Micro-DCI: 53SL6000 Single Loop Controller User Manual Instrukcja obsługi

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 138
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów

Podsumowanie treści

Strona 1 - INSTRUCTION MANUAL

INSTRUCTION MANUALSingle Loop Controller53SL600053SL6000 CONTROLLERPN24991ARev. 1

Strona 2 - MicroMod Automation, Inc

Figure 7-16. Auto Digital Output Path . . . . . . . . . . . . . . . . . . . . . . . . 7-19Figure 7-17

Strona 3 - Table of Contents

8.7 Dual Indicator with Re-Transmitted PVThe Dual Indicator allows two process variables tobe displayed and either one to be selected as theout

Strona 4 - 5.0 Inputs/Outputs (I/O) 5-1

8.8 Proportional Speed Floating ControlThis control output is suitable for any of the controlschemes where the final control element is usually

Strona 5

control element, the period should be set tomatch the end-to-end travel time of the ele-ment. To operate the digital outputs in a timeproportioning m

Strona 6 - 9.0 Commissioning 9-1

8.8.3 Speed Factor Adjusting1.If a slide wire is connected to AI2 instead of theremote setpoint, ensure the remote/local pushbutton is set to local f

Strona 7 - Appendix D: Prompt List D-1

9.1 OverviewCommissioning is an iterative process of refiningthe proportional band - Pb (Pb.2), integral or resettime - tr (tr.2), and derivative tim

Strona 8 - List of Tables

process control element would be moved until tem-perature increased an additional 9° from 410° to419°. Integral action would continue at each repe-ti

Strona 9 - List of Figures

nitude of the step in percent of full signal spanA. Also plot a graph of the resulting transientcurve traced by the controlled variable.3.Draw a stra

Strona 10

Figure 9-2. Easy-Tune ProcessFigure 9-3. Preliminary Step Response -Actual CurveFigure 9-4. Preliminary Step Response - Approximated Curve53

Strona 11 - Safety Summary

9.8.1 Executing Easy-TuneEasy-Tune is executed from the conF-EZ moduleparameters. A typical controller display illustratingEasy-Tune being executed

Strona 12 - READ FIRST

Figure 9-5. Easy-Tune Display53SL6000 Instruction Manual Section 9. Commissioning9-6

Strona 13 - 1.0 Introduction

GENERAL Electric Shock Hazard During MaintenanceWARNINGSDisconnect power or take precautions to ensure that contact withenergized parts is avoided whe

Strona 14

Table 9-2. Easy-Tune ParametersconF → EZPrompt Description DftcMControl ModeSelect the desired control action(s) forthe process: P

Strona 15 - 1.3 Product Specifications

9.8.3.1 out ResponseThis response indicates the controller output wasinitially at extreme maximum or minimum when thepreliminary step change was atte

Strona 16

AdditiveFeedForward(FF)This analog input signal isadded to the PID result toform the control scheme out-put value when auto opera-tion is active.Analo

Strona 17

requiring standard single loopfunctionality.cASc - for control strategiesrequiring cascade functional-ity.L.LiM - for control strategiesrequiring low

Strona 18 - 2DI/2DO Option Module

optimal PID characteristicconstants.FaceplateThe entire visable front of thecontroller casework that con-tains the push buttons andLEDs.FinalControlEl

Strona 19 - Control Ranges

Also, a prompt that can be in-voked on the display in engi-neer mode (e.g., cn.1); ifselected, it provides scrollingcapabilities through a seriesof pa

Strona 20 - 2.4 Power Connections

escent process operatinglevel.(Setpoint)ProgrammerModeAn operating mode of thecharacterizer that allows 13time intervals to be definedwith ProG-chr pa

Strona 21

LinearModeAn operating mode of thecharacterizer whereby valuesare entered into ProG-chr-K1through K26 parameter con-stants as 13 ordered pairs (Ainput

Strona 22 - 2.5 Signal Connections

B.1 OverviewThis section provides a parts list and maintenanceprocedures to replace the display assembly andpower supply board, to execute the self-t

Strona 23 - 2.5.4 Analog Output AO1

WARNING: Always remove power beforeattempting to install, disassemble, or service thecontroller. Failure to remove power may result inserious persona

Strona 24 - Signal Wiring

READ FIRSTWARNINGINSTRUCTION MANUALSDo not install, maintain, or operate this equipment without reading, understanding andfollowing the proper MicroMo

Strona 25 - 2.7 2DI/2DO Module

cable to new display assembly. To maintain envi-ronmental seal, ensure the rectangular gasket isplaced on the bezel. Slide bezel tabs into case andp

Strona 26 - 2.9 Applying Power

Figure B-3. Confidence Test ConnectionsB.4.2 Starting the Controller Confidence Test via the Faceplate Push ButtonsThe confidence

Strona 27 - 2.9.1 Power-up Sequence

B.4.4 Controller Confidence Test SuiteDuring confidence test execution, both vertical barsare and all annunciator LEDs except WD are lit, thered dro

Strona 28 - 3.0 Display Panel

B.5 Defaulting the DatabaseThe database can be restored to the factory setdefault values by entering a 098 into the ProG-cS-FiX parameter using the f

Strona 29

C.1 OverviewThirty-two addressable controllers (0-31) can beconnected to a datalink for information transferto/from a host, which initiates all trans

Strona 30

Table C-2. Datalink ProtocolSymbol DescriptionCMDCommandIt is the operation to be performed or adescription of the message that followsthe Command-I.

Strona 31 - Underflow Indication

2.Controller sends Response message.01111110 00100011 00000010 00000000 SOH Cmd + I.A. NUM LO ADD00010000 00001000 00001100

Strona 32 - 3.5 Engineer Mode

Table C-5. Datapoint AddressesType BaseAddrAddressCalculationH 09CFHAddress = H Base + (5 X H Number) = 9CFH + (5 X H Number)Address exa

Strona 33 - Backward

C.4.3 Database Prompt-to-Datapoint Cross ReferenceTable C-6 is provided as a parameter prompt-to-datapoint cross reference.Table C-6. Prom

Strona 34

Table C-6. Prompt-to-Datapoint Cross ReferenceDBase Module DBaseParameterNetworkReference cn.1 Adb C005AE L034AiX B011Aut L027b1 C0

Strona 35 - 3.7 Offline Display Pattern

1.1 53SL6000 Controller OverviewThe 53SL6000 controller is a functionally robustinstrument capable of performing any one of manycontrol strategies.

Strona 36

Table C-6. Prompt-to-Datapoint Cross ReferenceDBase Module DBaseParameterNetworkReference cn.2 Adb C037AE L058AiX B014Aut L051b1 C0

Strona 37

Table C-6. Prompt-to-Datapoint Cross ReferenceDBase Module DBaseParameterNetworkReference EZ [Abrt] L074APLd L073cM B016dout C075dP

Strona 38 - 3.10 Engineer Mode Summary

[0]: Logic level zero. 0.0: The value zero. 0.05: Digital filter in seconds. 0.1: Digital filter in seconds. 0.3: Digital filter in se

Strona 39

cSE: Control scheme analog E input. cSF: Control scheme analog F input. cSh: Control scheme digital H input. cSJ: Control scheme digital

Strona 40 - 4.0 Functional Overview

K11: Characterizer constant 11. K12: Characterizer constant 12. K13: Characterizer constant 13. K14: Characterizer constant 14. K15: C

Strona 41 - 4.2 Detailed Block Diagram

\S.tc: Thermocouple type CH_S. Std: Standard setpoint mode. StEP: Programmer step. StoP: Stop. StP.E: Enable oPEr prog step access.

Strona 44

The Company’s policy is one of continuous product improvement and the rightis reserved to modify the information contained herein without notice, or

Strona 45 - 5.0 Inputs/Outputs (I/O)

Figure 1-1. 53SL6000 Controller53SL6000 Instruction Manual Section 1. Introduction1-2

Strona 46 - Parameter Entries

1.2 Controller Model NumbersThe 53SL6000 controller model numbers are de-scribed in Table 1-1.Table 1-1. 53SL6000 Model Numbers53 SL6♦♦♦A♦♦Controlle

Strona 47 - Table 5-6. RTD Types

Thermal Shock± 66°C/hr ( ± 150.8° F /hr)(storage/transport)Physical Shock15 g 1/2 sine, 11 ms(operation)Physical ShockASTM D4169, DC1(storage/transmit

Strona 48 - 5.4 Analog Output 1 (AO1)

Analog Output 1(referenced to power common)Number1Rated Signal Range0/4 to 20 mAControl Range0 to 21.5 mANo-Load Voltage≤ 24 VLoad Range0 to 750 ohmsF

Strona 49 - 5.6 Discrete Outputs

(-320° to 1560° F)Copper RTDsCopper 10 Ohm RTDα = 0.00427-200° to +260° C(-320° to 500° F)Copper 53 Ohm RTDα = 0.00427-50° to +150° C(-55° to 300° F)C

Strona 50

cal 24 V/4 A ohmic Amp switchingoperationsSpark SuppressorIn series 5nF/51 ohm with varistor420 Veff in parallelElectrical Isolation1000 V contact coi

Strona 51 - 6.2 Characterizer

MicroMod Automation, Inc. The Company MicroMod Automation is dedicated to improving customer efficiency by providing the most ost-effective, applica

Strona 52 - 6.2.2 LSEG Mode

2.1 Inspection Inspect the equipment upon arrival for damage thatmay have occurred during shipment. If damage issuch that faulty operation is like

Strona 53 - 6.2.3 PrGM Mode

Figure 2-1. Panel Cutout and Installation53SL6000 Instruction Manual Section 2. Installation and Power-Up Procedures2-2

Strona 54 - 6.3 Math Function Block

Figure 2-2. Power Plug2.4.1 24 V DC Power ConnectionsFigure 2-3. 24 V DC Power ConnectionsRefer to Figure 2-3 to make the following connec-tions:1.

Strona 55 - 6.3.2 SuMM Mode

Figure 2-5. Signal PlugFigure 2-6. Signal Plug ConnectionsNOTE 1: Shielded signal cable (two-wire) shouldbe used in electrically noisy locations.NOT

Strona 56 - 6.3.6 LiM Mode

2.6 Universal Analog Input ModuleThis information applies to only those controllerswith an optional universal analog input module.2.6.1 Universal An

Strona 57 - 

Figure 2-8. Input Configurations2.7 2DI/2DO ModuleThis information applies to only those controllerswith the optional 2DI/2DO module.2.7.1 2DI/2DO B

Strona 58

Signal input connections for the 2DO six terminalplug are illustrated in Figure 2-11. Both, DO1 andDO2 are Form C relays. The contact load capaci-ti

Strona 59 - 7.0 Control Scheme Block

controller powers up in the last state it was in be-fore power was removed.2.9.1 Power-up SequenceThe power-up sequence is as follows:1.At power-up,

Strona 60

3.1 Display Panel OverviewAs shown in Figure 3-1, the controller display panelcontains three digital read-out (dro) fields, two ver-tical bar indicat

Strona 61

Item/LED Off On Blink-ingDescription8 - R X Remote/Ratio.X Remote requested, butnot granted (RemoteEnable [RE] not true).9 - L X Local Setpoint.X Setp

Strona 62

Table of ContentsSafety Summary IRead First II1.0 Introduction 1-11.1 53SL6000 Controller Overview . . . . . . . . . . . .

Strona 63

Table 3-1. Operator Mode Display ItemsItem Call-Out Description1 PV dro It is the process variablevalue in engineering units.2 PV bar It indicates th

Strona 64 - Schemes

Table 3-1. Operator Mode Display ItemsItem Call-Out Description20Select Modeand Loop 1/2Push ButtonPressing this pushbutton in operatormode with an a

Strona 65 - Control Scheme

3.5 Engineer ModeThe controller parameters and path connectionsare configured in engineer mode. Engineer modeis also used to initiate the Easy-Tune

Strona 66

Figure 3-5. Editing a ParameterNOTE 1: There is a 12.5 second time-out thatoccurs if a parameter prompt is not selected inengineer mode.NOTE 2: oPEr

Strona 67

Figure 3-6. Deselecting and ScrollingBackwardFigure 3-7. Editing a Red dro ValueFigure 3-8. Moving the Red dro DecimalPoint3.5.2.4 Editing the Tag

Strona 68

Figure 3-9. Editing a tAG3.6 Entering a Pass-KeyIn engineering mode, access to the ProG and conFmenus can be selectively restricted, as each menuhas

Strona 69

• If exiting the conF or ProG menus in engineermode, the controller goes offline and a blinkingoFF prompt appears in the red dro immediatelyafter the

Strona 70

Table 3-3. oPEr Menu SelectionsPrompt Description DftAdbAlarm DeadbandSpecifies the hystersis (gap)between alarm trigger and reset.This value is used

Strona 71

Table 3-3. oPEr Menu SelectionsPrompt Description DftEtrEasy-Tune Reset TimeResultant reset time valuecalculated by Easy-Tune. (It isenabled with c

Strona 72

Figure 3-13. Engineer Mode Prompt Path Summary53SL6000 Instruction Manual Section 3. Display Panel3-12

Strona 73

3.5 Engineer Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-53.5

Strona 74

4.1 Simplified Block DiagramAs shown in Figure 4-1 below, the internal opera-tions of the 53SL6000 Controller can be classifiedinto nine major functio

Strona 75

5.Discrete Input Logic Blocks - two input logicblocks permit discrete input signals to be eventgated with internal controller signals accordingto any

Strona 76

selections are path connections to the controlscheme block inputs A - F.The digital signal selections ([1] - /do8) areavailable to characterizer input

Strona 77

module; otherwise, they will not appear in theoPEr prompt list.7.Discrete output logic blocks (Logic 3 and 4) -parameter inputs to both logic modules(

Strona 78

Figure 4-2. Detailed Functional Controller Block DiagramSection 4. Functional Overview 53SL6000 Instruction Manual4-5

Strona 79

5.1 I/O OverviewThis section provides functional descriptions andapplicable parameter definitions for all of the con-troller inputs and outputs to in

Strona 80

5.3 Universal Analog Input ModuleThe universal analog input module can processone or two inputs, as determined by the type ofoption installed. A sin

Strona 81

Table 5-3. Input Type Prompts(conF Menu → Ai.3, Ai.4 Modules)Prompt Description SeeTabledtotDelta Pulse Totalizer (pulse input,incremental sum) 0-100

Strona 82

Table 5-7. Frequency/Pulse Input Types(conF Menu → Ai.3, Ai.4 Modules)Prompt Description DfttYPEMake prompt selection from Table5-3. Applicable type

Strona 83 - 7.7 Control Loop Parameters

Table 5-10. Analog Output Registers(ProG Menu → Ao Module)Prompt Description DftAo1.iAo2.iAo3.i(cont)Analog Output Connections (cont)Specifies the in

Strona 84

7.0 Control Scheme Block 7-17.1 Control Scheme Block . . . . . . . . . . . . . . . . . . . . . . . .

Strona 85

Table 5-12. Discrete Output Selections(ProG Menu → do Module)Prompt Description DftinV1 -inV8Discrete Output Invert0-on: it indicates a value of zero

Strona 86 - 7.8 Control Scheme Signal

6.1 Section OverviewSignal modification includes the altering, adjusting,selecting, or limiting of the analog input signal val-ues and digital input

Strona 87

Table 6-1. Characterizer Parameters(ProG Menu → chr Module)Prompt Description DftK01 -K26Assignments for K01 through K26 forthe three segment (3SEG)c

Strona 88 - 8.0 Eight Control Strategies

To ensure the piecewise approximation specifies arealizable function, the values for the coordinateinputs, which are stored in characterizer constants

Strona 89

•When engineer mode is exited and run is se-lected, the setpoint will move to the assignedvalue for the duration of its corresponding timeinterval.•To

Strona 90 - 8.2 Analog Back-Up Control

Table 6-2. Math Function Block Parameters(ProG Menu → Fnc Module)Prompt Description DftFnc.MMath Function Block Mode SelectThis mode parameter is use

Strona 91

6.3.3 PoLY ModeThis is a third order polynomial equation which op-erates on an algebraic combination of the four ana-log inputs. The constants K1 th

Strona 92 - 8.3 Ratio Control

6.3.7 SEL ModeThe selector allows one of four analog input valuesto be passed to the analog output based on thevalues of the two digital inputs (E an

Strona 93

Table 6-3. Logic Block Parameters(ProG Menu → LG Module)Prompt Description DftLG1.MLG2.MLG3.MLG4.MLogic Blocks 1 - 4 Mode SelectThese mode parameters

Strona 94 - 8.4 Auto/Manual Selector

7.1 Control Scheme BlockThe control scheme block, which is the primaryfunctional element of the controller, provides thecapability to select and impl

Strona 95 - 8.4.8 SchM Selection

8.5 Single Station Cascade Control . . . . . . . . . . . . . . . . . . . . . . . . 8-98.5.1 AI1 - S

Strona 96 - 8.5.2 AI2 - Primary PV Input

Figure 7-1. Input Signal Designators by Control Scheme53SL6000 Instruction Manual Section 7. Control Scheme Block7-2

Strona 97

Table 7-1. Control Signal DescriptionsSignal DescriptionAutAuto StatusFor SnGL, cASc, L.LiM, and h.LiM controlschemes, Aut selects the PID algorithmr

Strona 98 - 8.6.1 AI1 - Primary PV Input

Table 7-1. Control Signal DescriptionsSignal DescriptionSPtSSetpoint Track StatusFor the SnGL, cASc, L.LiM, and h.LiMcontrol schemes, SPtS selects th

Strona 99

Figure 7-2. Control Signal Logic PathsSection 7. Control Scheme Block 53SL6000 Instruction Manual7-5

Strona 100 - Re-Transmitted PV

7.4 Signal Paths for the SnGL, cASc, L.LiM, and h.LiM Control SchemesFigure 7-3 is a graphical representation of the con-trol scheme bloc

Strona 101 - Control

• Figure 7-15. Manual Output Path• Figure 7-16. Auto Digital Output Path7.5 Signal Paths for the in.Ld Control SchemeThe indicator/loader (i

Strona 102

Figure 7-3. SnGL, cASc, L.LiM, and h.LiM Signal Paths53SL6000 Instruction Manual Section 7. Control Scheme Block7-8

Strona 103 - 8.8.3 Speed Factor Adjusting

Figure 7-4. Common Setpoint Logic PathsFigure 7-5. Local Standard (Std) Setpoint PathSection 7. Control Scheme Block 53SL6000 Instruction Manual7-9

Strona 104 - 9.0 Commissioning

Figure 7-6. Remote Ratio Setpoint PathFigure 7-7. StV Setpoint Tracking53SL6000 Instruction Manual Section 7. Control Scheme Block7-10

Strona 105

Figure 7-8. PVt Setpoint TrackingSection 7. Control Scheme Block 53SL6000 Instruction Manual7-11

Strona 106 - 9.8 Easy-Tune

9.8.3.11 PidL Response . . . . . . . . . . . . . . . . . . . . . . . 9-89.8.3.12 cM Response . .

Strona 107 - Approximated Curve

Figure 7-9. cASc Control Scheme Setpoint Path53SL6000 Instruction Manual Section 7. Control Scheme Block7-12

Strona 108 - 9.8.1 Executing Easy-Tune

Figure 7-10. Pb, td, and tr PID PathsSection 7. Control Scheme Block 53SL6000 Instruction Manual7-13

Strona 109

Figure 7-11. Pb, td, tr, and FF PID Paths53SL6000 Instruction Manual Section 7. Control Scheme Block7-14

Strona 110

Figure 7-12. Pb, td, tr, and FF PID Paths with EXrFSection 7. Control Scheme Block 53SL6000 Instruction Manual7-15

Strona 111

Figure 7-13. Output Tracking Path53SL6000 Instruction Manual Section 7. Control Scheme Block7-16

Strona 112 - Appendix A: Glossary

Figure 7-14. Auto Output PathSection 7. Control Scheme Block 53SL6000 Instruction Manual7-17

Strona 113

Figure 7-15. Manual Output Path53SL6000 Instruction Manual Section 7. Control Scheme Block7-18

Strona 114

Figure 7-16. Auto Digital Output PathSection 7. Control Scheme Block 53SL6000 Instruction Manual7-19

Strona 115

Figure 7-17. in.Ld Control Scheme Alarmed Variable Input53SL6000 Instruction Manual Section 7. Control Scheme Block7-20

Strona 116

Figure 7-18. in.Ld Control Scheme Auto Input with Digital OutputSection 7. Control Scheme Block 53SL6000 Instruction Manual7-21

Strona 117

List of TablesTable 1-1. 53SL6000 Model Numbers . . . . . . . . . . . . . . . . . . . . . . . . 1-3Ta

Strona 118 - B.2 Parts List

Figure 7-19. in.Ld Control Scheme Output Tracking53SL6000 Instruction Manual Section 7. Control Scheme Block7-22

Strona 119 - B.3 Removal and Replacement

Figure 7-20. in.Ld Control Scheme Manual OperationSection 7. Control Scheme Block 53SL6000 Instruction Manual7-23

Strona 120 - Procedure

7.6 Control Scheme ParametersTable 7-2 provides the control scheme ProG-cSmodule parameters. These parameters set the ba-sic operation of the contro

Strona 121

Table 7-2. Control Scheme Parameters(ProG Menu → cS Module)Prompt Description DftcS.hcS.JcS.KcS.LControl scheme cS.h - cS.L DigitalInputsSpecifies pa

Strona 122

Table 7-3. Control Selections(conF Menu → cn.1, cn.2 Modules)Prompt Description DfttrReset Time (see Section 9.3)Specifies the time in minutesrequir

Strona 123 - B.7 Watchdog LED

Table 7-3. Control Selections(conF Menu → cn.1, cn.2 Modules)Prompt Description DftSSrSetpoint Slew RateSpecifies in engineering units persecond the

Strona 124 - C.3 Protocol

Table 7-3. Control Selections(conF Menu → cn.1, cn.2 Modules)Prompt Description DftrSv(cn.1only)Reverse ValveSpecifies whether 100% outputshould be

Strona 125 - C.3.2 Transaction Examples

Figure 7-21. Control Schemes Signal Connector Pin AssignmentsSection 7. Control Scheme Block 53SL6000 Instruction Manual7-29

Strona 126 - Reference

This section provides information to implementeight commonly used control strategies:•Single Loop Control with Remote Setpoint.•Analog Back-up Control

Strona 127

8.1.1 AI1 - Process Variable InputThis analog input signal value is compared to thecontrol setpoint to determine the control outputvalue.Applicable p

Strona 128 - Cross Reference

List of FiguresFigure 1-1. 53SL6000 Controller . . . . . . . . . . . . . . . . . . . . . . . . . .

Strona 129 - Reference

8.2 Analog Back-Up ControlThe direct digital control/analog back-up strategyis used in operations where a remote computer isnormally controlling the

Strona 130

8.2.1 AI1 - Process Variable InputThis analog input signal value is compared to thecontrol setpoint to determine the control outputvalue.Applicable p

Strona 131 - via Datalink

8.3 Ratio ControlRatio control is used where one variable, called thecontrolled variable, must be automatically main-tained in definite proportion to

Strona 132 - Appendix D: Prompt List

Applicable parameter that may require configura-tion change:Section 5.6, ProG-do-inV2.8.3.5 DI1 - Force Control Output Contact Inpu

Strona 133

8.4 Auto/Manual SelectorAn auto/manual selector application is illustrated inFigure 8-8. This application is implemented withthe controller default

Strona 134

8.4.4 D02 - PV1 Low Alarm Contact OutD02 is closed (on) when the alarmed process vari-able value, PV1, is not within the process a

Strona 135

8.5 Single Station Cascade ControlA single station cascade control strategy is illus-trated in Figure 8-10. This control strategy is imple-mented wit

Strona 136

8.5.4 DO2 - Secondary PV Low Alarm Contact OutD02 is closed (on) when the secondary processvariable value is not within the lo

Strona 137

8.6 Single Station Override ControlWith Single Station Override Control, two standardPID control loops function as two interdependentvariables, prima

Strona 138

Applicable parameter that may require configura-tion change:Section 5.6, ProG-do-inV1.8.6.4 DO2 - Primary PV Low Alarm Contact

Komentarze do niniejszej Instrukcji

Brak uwag