Table 6-3. Logic Block Parameters
(ProG Menu
LG Module)
Prompt Description Dft
LG1.M
LG2.M
LG3.M
LG4.M
Logic Blocks 1 - 4 Mode Select
These mode parameters are used to
select the logical operation to be
performed on the inputs of the logic
blocks. Function selections for each
block are as follows:
oFF:
No logical operation
performed.
or:
A OR B.
/or:
NOT A OR B.
And:
A AND B.
/And:
NOT A AND B.
Xor
: A EXCLUSIVE OR B.
/Xor:
NOT A EXCLUSIVE OR B.
or/:
A OR NOT B.
And/:
A AND NOT B.
oFF
oFF
oFF
oFF
LG1.A
LG1.b
LG2.A
LG2.b
A and B Inputs for Logic Blocks 1
and 2
Specifies the connections for the A
and B inputs of logic blocks 1 and 2.
Input selections are as follows:
[1]:
Logical one input.
[0]
: Logical zero input.
di1:
Discrete input 1 logic value.
/di1:
Inverted di1 logic value.
di2:
Discrete input 2 logic value.
/di2:
Inverted di2 logic value.
di3:
Discrete input 3 logic value.
/di3:
Inverted di3 logic value.
di4:
Discrete input 4 logic value.
/di4:
Inverted di4 logic value.
di5:
Discrete input 5 logic value.
/di5:
Inverted di5 logic value.
di6:
Discrete input 6 logic value.
/di6:
Inverted di6 logic value.
di7:
Discrete input 7 logic value.
/di7:
Inverted di7 logic value.
di8:
Discrete input 8 logic value.
/di8:
Inverted di8 logic value.
do7:
Loop-back do7 register value.
/d07:
Inverted loop-back do7
register value.
d08:
Loop-back do8 register value.
/d08:
Inverted loop-back do8
register value.
Fnc:
Math function block digital
output.
chr:
Characterizer output.
[1]
[1]
[1]
[1]
Table 6-3. Logic Block Parameters
(ProG Menu
LG Module)
Prompt Description Dft
LG3.A
LG3.b
LG4.A
LG4.b
A and B Inputs for Logic Blocks 3
and 4
Specifies the connections for the A
and B inputs of logic blocks 3 and 4.
Input selections are as follows:
[1]:
Logical 1 input.
[0]:
Logical 0 input.
PA1:
cn.1 AL1 active.
PA2:
cn.1 AL2 active.
Vup:
Floating control valve up.
Vdn:
Floating control valve down.
SWA:
Auto switch.
SWr:
Remote switch.
Aut:
Loop 1 is in auto control.
rMt:
Remote.
oVtS:
Output track status.
SPtS:
Setpoint track status.
PA1.2:
cn.2 AL1 active.
PA2.2:
cn.2 AL2 active.
Aut.2:
Loop 2 is in auto control.
Fnc:
Math function block digital
output.
chr:
Characterizer output.
LG1:
Logic block 1 output.
LG2:
Logic block 2 output.
[1]
[1]
[1]
[1]
Table 6-4. Discrete Logic Block Functions
A OR B (or) A AND NOT B (And/)
ABLG1-4ABLG1-4
011010
111110
000000
101101
A AND B (And) NOT A OR B (/or)
ABLG1-4ABLG1-4
010010
111110
000001
100100
A XOR B (Xor) NOT A AND B (/And)
ABLG1-4ABLG1-4
011011
110110
000001
101101
A OR NOT B (or/) NOT A XOR B (/Xor)
ABLG1-4ABLG1-4
010010
111111
001001
101100
Micro-DCI
53SL6000 Controller
6-8
Przeglądanie stron 57