MOD 30ML™ Functions Data Base Reference Display, Alarm and Built-in I/O Functions for 1800P - MOD 30ML™ Identity Module (Version 2)

Strona 2 - MicroMod Automation, Inc

MOD 30ML Functions MOD 30ML FUNCTION BLOCKS Refer to Section 3 for examples of how these blocks are used. 2-2

Strona 3 - CONTENTS

MOD 30ML Functions CONFIGURATION EXAMPLES Figure 3. 8. Instrument Versions • Select MOD 30ML 2 from this list as our instrument version by clickin

Strona 4 - ILLUSTRATIONS

MOD 30ML Functions CONFIGURATION EXAMPLES • The algorithm blocks belonging to the instrument version selected will be shown as a menu on the left f

Strona 5 - ILLUSTRATIONS (Cont’d)

MOD 30ML Functions CONFIGURATION EXAMPLES 5. Add a loop compound. We will configure our control loop inside this loop compound. • Select the Loop C

Strona 6

MOD 30ML Functions CONFIGURATION EXAMPLES • Select Properties from the menu. The Algorithm Properties of the Loop Cpd block will be displayed next

Strona 7 - INTRODUCTION

MOD 30ML Functions CONFIGURATION EXAMPLES  A loop compound is a compound or group that contains a loop block. You configure other blocks and compo

Strona 8 - 1.5 VERSION IDENTIFICATION

MOD 30ML Functions CONFIGURATION EXAMPLES Figure 3. 16. Accessing the Component Gallery • When the Component Gallery dialog box appears, select the

Strona 9 - DATABASE PARAMETERS

MOD 30ML Functions CONFIGURATION EXAMPLES • Move the cursor to the ML_PID compound and either double-click, or select it and then select the Export

Strona 10

MOD 30ML Functions CONFIGURATION EXAMPLES Figure 3. 19. Loaded ML_PID Compound 10. We will make the following changes to the loaded compound: •

Strona 11 - 2.2 DISPLAY BLOCK (DISP)

MOD 30ML Functions CONFIGURATION EXAMPLES Figure 3. 20. VCI Block Properties • Open the PID block by double-clicking on it. • The General tab wil

Strona 12

MOD 30ML Functions CONFIGURATION EXAMPLES Figure 3. 21.PID Block Properties • The PID block has the most extensive configuration. Select the Setpo

Strona 13

MOD 30ML Functions DISPLAY BLOCK 2.2 DISPLAY BLOCK (DISP) The display block is used to assign display resources and keyboard actions to one user

Strona 14

MOD 30ML Functions CONFIGURATION EXAMPLES Figure 3. 22. PID Block Properties – Setpoint tab • The Formats tab contains formatting information for

Strona 15

MOD 30ML Functions CONFIGURATION EXAMPLES Figure 3. 23. Display block Properties – Formats tab • Click on OK to accept the changes. • We also nee

Strona 16

MOD 30ML Functions CONFIGURATION EXAMPLES Figure 3. 24. Display block Properties – Formats tab • Change the High limit to 200 to match the process

Strona 17

MOD 30ML Functions CONFIGURATION EXAMPLES Figure 3. 25. Display block Properties – Formats tab • Click on OK on the display block configuration to

Strona 18

MOD 30ML Functions CONFIGURATION EXAMPLES Figure 3. 26. PAD block Properties • Change the Trip value to 150 and then click on OK to accept the ch

Strona 19

MOD 30ML Functions CONFIGURATION EXAMPLES Figure 3. 27. PAD block Properties • Click on OK to accept the changes. • Next we will change the displ

Strona 20

MOD 30ML Functions CONFIGURATION EXAMPLES Figure 3. 28. Display block Properties • Click on OK to accept the changes. • Click on a empty are of t

Strona 21

MOD 30ML Functions CONFIGURATION EXAMPLES Figure 3. 29. Close loop compound • Add the Display Tag to the Display Interface Block: The next step i

Strona 22

MOD 30ML Functions CONFIGURATION EXAMPLES • Open the DIF (Display Interface) block as shown in the figure above. • Click on the New button on this

Strona 23

MOD 30ML Functions CONFIGURATION EXAMPLES Figure 3. 33. Information Window • You can double-click on an error to open the block that has a confi

Strona 24

MOD 30ML Functions DISPLAY BLOCK 2.2.1 Display Block Operation Moving Between and Within Displays One option for moving between user displays is

Strona 25

MOD 30ML Functions CONFIGURATION EXAMPLES 3.3 CONFIGURATION EXAMPLES USING THE APPLICATION BUILDER SOFTWARE The configurations described in this se

Strona 26

MOD 30ML Functions CONFIGURATION EXAMPLES Loading a Loop Into A Strategy 9. From the library icons on the left side of the workspace, select LP C

Strona 27

MOD 30ML Functions CONFIGURATION EXAMPLES Figure 3. 34. Workspace Displays Appearing During Configuration 3-28

Strona 28

MOD 30ML Functions CONFIGURATION EXAMPLES 3.3.2 BASICPID (PID WITH DISPLAY) COMPOUND The BASICPID compound is a fully functional single PID loop

Strona 29

MOD 30ML Functions CONFIGURATION EXAMPLES 3.3.4 PID Display Configuration Procedure The starting point of this procedure is the loop level of you

Strona 30

MOD 30ML Functions CONFIGURATION EXAMPLES State Table Configuration Example The following is a listing of the state table definitions as included in

Strona 31

MOD 30ML Functions CONFIGURATION EXAMPLES Display Block Configuration for Single PID Example The following is a listing of the display script used t

Strona 32

MOD 30ML Functions CONFIGURATION EXAMPLES 3.3.5 TOTALIZER COMPOUNDS Many flow applications require simultaneous control and totalization of the pr

Strona 33

MOD 30ML Functions CONFIGURATION EXAMPLES Figure 3. 36. Totalizer 1 Compound Totalizer Block Connections PID.PVI -------> Totalizer.ANALINsP

Strona 34

MOD 30ML Functions CONFIGURATION EXAMPLES Display Operation Unless other changes were made in the strategy to cause a different behavior, the instru

Strona 35

MOD 30ML Functions DISPLAY BLOCK When a remote input is 'edited' or written to by a script statement, the remote variable itself will be c

Strona 36

MOD 30ML Functions CONFIGURATION EXAMPLES 3.3.8 PIDTOT2.CSM- Totalizer and PID with Separate Commands Menu This compound includes the totalized val

Strona 37

MOD 30ML Functions CONFIGURATION EXAMPLES Totalizer Block Connections PID.PVI -------> Totalizer.ANALINP (input for totalizing) Totalizer.TC

Strona 38

MOD 30ML Functions CONFIGURATION EXAMPLES 3.3.9 CAS&DSP (CASCADE WITH DISPLAY) COMPOUND The CAS&DSP compound is a fully functional cascade

Strona 39

MOD 30ML Functions CONFIGURATION EXAMPLES Figure 3. 38. Cascade with Display Compound Blocks 3.3.11 Configuration Procedure The starting point

Strona 40

MOD 30ML Functions CONFIGURATION EXAMPLES 2. Double click on the master process input block to access its edit display, then proceed as follows: a

Strona 41

MOD 30ML Functions CONFIGURATION EXAMPLES Configuring DIF, State, and Display Blocks To complete the configuration of the compound, the following ac

Strona 42

MOD 30ML Functions CONFIGURATION EXAMPLES 3.3.12 COLD JUNCTION COMPENSATION (CJC) COMPOUND This compound provides a cold junction compensated the

Strona 43

MOD 30ML Functions CONFIGURATION EXAMPLES The CJC compound resides in the utilities section of the Application Builder software. It is accessed via

Strona 44

MOD 30ML Functions CONFIGURATION EXAMPLES c. Upon completion of required changes for each block, click on the Enter button to input configured valu

Strona 45

MOD 30ML Functions APPENDIX A - ASSIGNMENT STATEMENT REFERENCE APPENDIX A ASSIGNMENT STATEMENT REFERENCE A.1 ASSIGNMENT STATEMENTS The assignmen

Strona 46

MOD 30ML Functions DISPLAY BLOCK 04 Diagnostic Group (SUPPGRP) ...

Strona 47 - 2.4 STATE TABLE BLOCK

MOD 30ML Functions APPENDIX A - ASSIGNMENT STATEMENT REFERENCE Table A-1. Assignment Statement Results of Type ‘srcname1 = srcname2' (Cont’d)

Strona 48

MOD 30ML Functions APPENDIX A - ASSIGNMENT STATEMENT REFERENCE Table A-1. Assignment Statement Results of Type ‘srcname1 = srcname2' (Cont’d)

Strona 49

MOD 30ML Functions APPENDIX A - ASSIGNMENT STATEMENT REFERENCE Table A-2. Assignment statements of type 'display_resource = source_name'

Strona 50

MOD 30ML Functions APPENDIX A - ASSIGNMENT STATEMENT REFERENCE Table A-2. Assignment statements of type 'display_resource = source_name'

Strona 51 - 2.5 TUNE LIST BLOCK

MOD 30ML Functions APPENDIX A - ASSIGNMENT STATEMENT REFERENCE Table A-3. Assignment statements of type 'display_resource = constant' - e

Strona 52

MOD 30ML Functions APPENDIX A - ASSIGNMENT STATEMENT REFERENCE Table A-4. Assignment statements of type 'display_resource.SRC = source_name&ap

Strona 53

MOD 30ML Functions APPENDIX A - ASSIGNMENT STATEMENT REFERENCE Table A-4. Assignment statements of type 'display_resource.SRC = source_name&ap

Strona 54

MOD 30ML Functions APPENDIX A - ASSIGNMENT STATEMENT REFERENCE Table A-4. Assignment statements of type 'display_resource.SRC = source_name&ap

Strona 55

MOD 30ML Functions APPENDIX A - ASSIGNMENT STATEMENT REFERENCE A-10

Strona 56

MOD 30ML Functions APPENDIX B - DISPLAYED CHARACTER SET APPENDIX B DISPLAYED CHARACTER SET The Application builder allows any character in the ASCII

Strona 57

MOD 30ML Functions DISPLAY BLOCK 20 to 59 Input 1 through Input 800 (I1 to I800)...

Strona 58

MOD 30ML Functions APPENDIX B - DISPLAYED CHARACTER SET Decimal Keyboard Display 57 † 9 58 : 59 ; 60 † < 61 † = 62 † > 63 ? 64 @ 65 †

Strona 60

The Company’s policy is one of continuous product improvement and the right is reserved to modify the information contained herein without notice,

Strona 61

MOD 30ML Functions DISPLAY BLOCK Display tag: (DISPTAG) Up to 8 ASCII characters identifying display. Characters displayed on line 1 when the displa

Strona 62

MOD 30ML Functions DISPLAY BLOCK Display Block Page 2 Use this display page to configure initial values for bars and segments. Figure 2-4. Displa

Strona 63

MOD 30ML Functions DISPLAY BLOCK Display Block Inputs Use this display page to configure up to 800 inputs for a display block. Inputs are configured

Strona 64

MOD 30ML Functions DISPLAY BLOCK Name: The user name is an eight (8) character alphanumeric used to identify the input. The name must start with a

Strona 65

MicroMod Automation, Inc. The Company MicroMod Automation is dedicated to improving customer efficiency by providing the most cost-effective, applic

Strona 66

MOD 30ML Functions DISPLAY BLOCK Display Block Formats Use this display page to configure up to 512 format types for a display block. Multiple input

Strona 67

MOD 30ML Functions DISPLAY BLOCK Format type: Table 2-2 lists the different display format types and what fields are active for each type. A refer

Strona 68

MOD 30ML Functions DISPLAY BLOCK Table 2-2. Display Formats, Supported Data Types and Active Fields Display Format Supported Data Types* Entry Meth

Strona 69

MOD 30ML Functions DISPLAY BLOCK Display Script Editing Use the internal editor or an external file for the default and user display scripts. When e

Strona 70

MOD 30ML Functions DISPLAY BLOCK Event Scripts Each state consists of up to 27 event scripts, the names of which are predefined. Key event scripts,

Strona 71

MOD 30ML Functions DISPLAY BLOCK 000: Statement1; BREAK; 001: Statement2; BREAK;

Strona 72

MOD 30ML Functions DISPLAY BLOCK Display Language Format The display block display language has the following general format: Defaults: {

Strona 73 - COMMERRA

MOD 30ML Functions DISPLAY BLOCK Display Language Grammar The grammar rules that follow describe the display language. 1. The display language can

Strona 74

MOD 30ML Functions DISPLAY BLOCK 8. Assignment to display resources: Line1 - Line6 can be assigned values of any type. Bars & Segments can on

Strona 75

MOD 30ML Functions DISPLAY BLOCK 13. Unary operations (unary_op) are: Precedence Symbol Operation 1 + Unary Plus (for floating point constants o

Strona 76

MOD 30ML Data Base Reference CONTENTS CONTENTS Page SECTION 1 - INTRODUCTION 1.1 GENERAL ...

Strona 77

MOD 30ML Functions DISPLAY BLOCK 17. Display state names can appear in any expression, where they are treated as long state variables, but they can

Strona 78

MOD 30ML Functions DISPLAY BLOCK 2.2.5 Typical Block Connections for Display Block Typical block connections for the display block are shown belo

Strona 79

MOD 30ML Functions DISPLAY BLOCK "HEX & ASCII data not allowed in expression." HEX and ASCII data can't appear in an expression b

Strona 80

MOD 30ML Functions DISPLAY INTERFACE BLOCK 2.3 DISPLAY INTERFACE BLOCK (DIF) The Display Interface block is a repository for all instrument displ

Strona 81

MOD 30ML Functions DISPLAY INTERFACE BLOCK Display List Access to different displays in the display list is controlled locally through the TAG key o

Strona 82 - BUILT-IN ANALOG INPUT BLOCK

MOD 30ML Functions DISPLAY INTERFACE BLOCK Field Mnemonic Valid Values CWR Data Type Attr Port 3 Noise Counter NOISECTR – WR Count 28 Po

Strona 83

MOD 30ML Functions DISPLAY INTERFACE BLOCK 05 Faceplate Comm Error (FPCOMS) ...

Strona 84

MOD 30ML Functions DISPLAY INTERFACE BLOCK Choose a display to appear on the instrument front face at power up. DEVICE 0 Power up display is the *

Strona 85

MOD 30ML Functions DISPLAY INTERFACE BLOCK 22 High Priority Process Alarms: Display Flash (FLSHHIPR)... CWR

Strona 86 - BUILT-IN ANALOG OUTPUT BLOCK

MOD 30ML Functions DISPLAY INTERFACE BLOCK 30 Port 3 Communications Error Counter (CMERRCTR)...– WR

Strona 87

MOD 30ML Data Base Reference CONTENTS CONTENTS (Cont’d) Page SECTION 3 - CONFIGURATION EXAMPLES 3.1 GENERAL...

Strona 88

MOD 30ML Functions DISPLAY INTERFACE BLOCK 2.3.3 Display Interface Block Configuration Screens The displays used to configure the display block a

Strona 89

MOD 30ML Functions DISPLAY INTERFACE BLOCK Remote display input: (See attribute 60 description.) A count type input can be made to REMDISP, or it ca

Strona 90

MOD 30ML Functions DISPLAY INTERFACE BLOCK Display Interface Block Page 2 Use this page to set values for timeouts and passwords. Figure 2-10. D

Strona 91

MOD 30ML Functions DISPLAY INTERFACE BLOCK Display Interface Block Page 3 Use this page to set values for display flash periods, and set values for

Strona 92

MOD 30ML Functions DISPLAY INTERFACE BLOCK Action on diagnostic event Display Flash (See attribute 19 description.) Use to specify if an unacknowle

Strona 93

MOD 30ML Functions DISPLAY INTERFACE BLOCK Event Code Type Description 4 Ack Only Diag FACEPLATE COMMUNICATIONS ERROR. An error occurred when

Strona 94

MOD 30ML Functions DISPLAY INTERFACE BLOCK 2.3.5 Typical Block Connections for Display Interface Block Typical block connections for the display in

Strona 95 - CONFIGURATION EXAMPLES

MOD 30ML Functions STATE TABLE BLOCK 2.4 STATE TABLE BLOCK The State Table block is a data only block used by the various display blocks, such a

Strona 96

MOD 30ML Functions STATE TABLE BLOCK 2.4.2 State Table Block Configuration Screens The displays used to configure the state table block are descri

Strona 97

MOD 30ML Functions STATE TABLE BLOCK State Table Block Page 2 Use this page to edit state tables. The same editing rules as described in the Display

Strona 98

MOD 30ML Data Base Reference CONTENTS ILLUSTRATIONS (Cont’d) Figure Page 2-20 Example of Process Alarm Tripping (Floating Point Data) ...

Strona 99

MOD 30ML Functions STATE TABLE BLOCK Default An ASCII string enclosed in double quotes (can contain any displayable character, see Appendix B). Stri

Strona 100

MOD 30ML Functions TUNE LIST BLOCK 2.5 TUNE LIST BLOCK The tune list block contains a list of attributes accessible as tunable parameters from o

Strona 101

MOD 30ML Functions TUNE LIST BLOCK 2.5.2 Tune List Block Configuration Screens The displays used to configure the tune list block are described be

Strona 102

MOD 30ML Functions TUNE LIST BLOCK Select Add to browse for and add a group of tags to the tune list and then select Modify to specify input data fo

Strona 103

MOD 30ML Functions TUNE LIST BLOCK Tune List Display Formats Use this display page to configure up to 512 format types for a tune list block. Multip

Strona 104

MOD 30ML Functions TUNE LIST BLOCK Low Limit: Numeric entry that is the minimum allowed operator entry. Low limit must not exceed high limit. For l

Strona 105

MOD 30ML Functions TUNE LIST BLOCK Display State Table: Name of a state table to be used for display of a variable. The value of the variable is c

Strona 106

MOD 30ML Functions PROCESS ALARM DISPLAY BLOCK 2.6 PROCESS ALARM DISPLAY BLOCK (PAD) The process alarm block is used to initiate a discrete alar

Strona 107

MOD 30ML Functions PROCESS ALARM DISPLAY BLOCK 2.6.1 Process Alarm Block Operation Active alarms are determined by comparing the value of the al

Strona 108

MOD 30ML Functions PROCESS ALARM DISPLAY BLOCK Alarm ClearTime (Group Scan Cycles)7505002500.000000032520151053051000TRUEFALSEAlarmActiveHIGH ALARM

Strona 109

MOD 30ML Data Base Reference CONTENTS TABLES Table Page 2-1 Display Block Attributes,Valid Values,Mnemonics, and Data Types ...

Strona 110 - Figure 3. 22

MOD 30ML Functions PROCESS ALARM DISPLAY BLOCK 2.6.2 Process Alarm Display Block Parameters The mnemonics, valid values, and data types for all

Strona 111

MOD 30ML Functions PROCESS ALARM DISPLAY BLOCK Block Type PAD This is the Process Alarm Display Block type. Block type address code is 52. 00

Strona 112

MOD 30ML Functions PROCESS ALARM DISPLAY BLOCK GREATER OR 3 Alarm becomes active when the Alarm Input is GREATER OR EQUAL EQUAL than (>=)

Strona 113

MOD 30ML Functions PROCESS ALARM DISPLAY BLOCK 09 Alarm Active (A) ...

Strona 114

MOD 30ML Functions PROCESS ALARM DISPLAY BLOCK 12 Alarm Activate Value (TRIPVAL) ...

Strona 115

MOD 30ML Functions PROCESS ALARM DISPLAY BLOCK 2.6.3 Process Alarm Display Block Configuration Screen The displays used to configure the process

Strona 116

MOD 30ML Functions PROCESS ALARM DISPLAY BLOCK Alarm input (See attribute 17 description) This is the alarm value that is compared with the trip va

Strona 117

MOD 30ML Functions PROCESS ALARM DISPLAY BLOCK Figure 2-22. Process Alarm Display Block (PAD), Display Page Line 6 display format This field defi

Strona 118

MOD 30ML Functions PROCESS ALARM DISPLAY BLOCK Bar display format This field defines the alarm bar display format. Valid entries are as follows: No

Strona 119

MOD 30ML Functions PROCESS ALARM DISPLAY BLOCK Bar Format (Normal) Lo Range The alarm input value which corresponds to 0% indication on the bar d

Strona 120 - SOFTWARE

MOD 30ML Functions INTRODUCTION SECTION 1 INTRODUCTION 1.1 GENERAL This document includes database reference information and application examples to

Strona 121

MOD 30ML Functions PROCESS ALARM DISPLAY BLOCK 2.6.4 Typical Block Connections for Process Alarm Display Block Typical softwiring connections ar

Strona 122

MOD 30ML Functions BUILT-IN ANALOG INPUT BLOCK 2.7 BUILT-IN ANALOG INPUT BLOCK (AIN) The built-in analog input block is used to gather signals f

Strona 123

MOD 30ML Functions BUILT-IN ANALOG INPUT BLOCK +VOLTSMILLIVOLTSCURRENTTCTC+CJCRTDRESISTANCEUnlockAutoMODEBuilt-inAnalog InputI/OCommunications Erro

Strona 124

MOD 30ML Functions BUILT-IN ANALOG INPUT BLOCK Figure 2-26 Built-In Analog Input Block (AIN), Edit Display 2.7.2 Built-in Analog Input Block

Strona 125

MOD 30ML Functions BUILT-IN ANALOG INPUT BLOCK Table 2-9. Built-In Analog Input Block Attributes, Valid Values, Mnemonics, and Data Types (Cont’d)

Strona 126

MOD 30ML Functions BUILT-IN ANALOG INPUT BLOCK Table 2-9. Built-In Analog Input Block Attributes, Valid Values, Mnemonics, and Data Types (Cont’d.)

Strona 127 - 3.3.5 TOTALIZER COMPOUNDS

MOD 30ML Functions BUILT-IN ANALOG INPUT BLOCK 06 Unacked I/O communications error (COMMERRU) ...

Strona 128

MOD 30ML Functions BUILT-IN ANALOG INPUT BLOCK 13 Input Type (INTYPE)...

Strona 129

MOD 30ML Functions BUILT-IN ANALOG INPUT BLOCK 15 Initial Result (R) ...

Strona 130

MOD 30ML Functions BUILT-IN ANALOG INPUT BLOCK 40 CJC Mode (CJCMODE) ...

Strona 131

MOD 30ML Functions INTRODUCTION To simplify configuration, the instrument has resident templates that can be used to configure basic control schemes

Strona 132

MOD 30ML Functions BUILT-IN ANALOG INPUT BLOCK 43 CJC Field Result (FCJC) ...

Strona 133

MOD 30ML Functions BUILT-IN ANALOG INPUT BLOCK 50 Resistance Range (RANGE)...

Strona 134

MOD 30ML Functions BUILT-IN ANALOG INPUT BLOCK 2.7.3 Typical Block Connections for Built-In Analog Input Block Typical softwiring block connecti

Strona 135

MOD 30ML Functions BUILT-IN ANALOG INPUT BLOCK 2.7.4 Built-In Analog Input Block Events The event codes (and their suggested text messages) for t

Strona 136

MOD 30ML Functions BUILT-IN ANALOG INPUT BLOCK 2-76

Strona 137

MOD 30ML Data Base Reference BUILT-IN ANALOG OUTPUT BLOCK 2.8 BUILT-IN ANALOG OUTPUT BLOCK (AOUT) The built-in analog output block serves as th

Strona 138

MOD 30ML Data Base Reference BUILT-IN ANALOG OUTPUT BLOCK Built-in Circuit StatusHOLD0.00DiagnosticGroupSheet 2 of 2PART 2Built-in AnalogOutputSe

Strona 139 - APPENDIX A

MOD 30ML Data Base Reference BUILT-IN ANALOG OUTPUT BLOCK Figure 2-29a. Built-In Analog Output Block (AOUT), Edit Display Figure 2-29b. Built-In

Strona 140

MOD 30ML Data Base Reference BUILT-IN ANALOG OUTPUT BLOCK 2.8.1 Built-In Analog Output Block Operation The Built-In Analog Output block is a da

Strona 141

MOD 30ML Data Base Reference BUILT-IN ANALOG OUTPUT BLOCK 2.8.2 Built-In Analog Output Block Parameters The mnemonics, valid values, and data t

Strona 142

MOD 30ML Functions MOD 30ML FUNCTION BLOCKS SECTION 2 DATABASE PARAMETERS 2.1 MOD 30ML FUNCTION BLOCKS The blocks described in this section are

Strona 143

MOD 30ML Data Base Reference BUILT-IN ANALOG OUTPUT BLOCK Block Type AOUT This is the Analog Output Module Block type. 00 Version (VERSION)...

Strona 144

MOD 30ML Data Base Reference BUILT-IN ANALOG OUTPUT BLOCK 07 Active I/O communications Error (COMMERRA)...

Strona 145

MOD 30ML Data Base Reference BUILT-IN ANALOG OUTPUT BLOCK 13 Mode (MODE) ...

Strona 146

MOD 30ML Data Base Reference BUILT-IN ANALOG OUTPUT BLOCK 21 Restart preset value (PRESET)...

Strona 147

MOD 30ML Data Base Reference BUILT-IN ANALOG OUTPUT BLOCK 2.8.3 Typical Block Connections for Built-In Analog Output Block Typical softwiring b

Strona 148 - MOD 30ML Functions

MOD 30ML Functions CONFIGURATION EXAMPLES SECTION 3 CONFIGURATION EXAMPLES 3.1 GENERAL This section has tutorials for configuring a complete PID

Strona 149 - DISPLAYED CHARACTER SET

MOD 30ML Functions CONFIGURATION EXAMPLES 2. We will create a new Workspace and a new project in this step. Click on the File menu on the menu bar

Strona 150

MOD 30ML Functions CONFIGURATION EXAMPLES Figure 3.4. New Project • The New dialog box will redisplay Figure 3. 5. New Project • Type the name

Strona 151

MOD 30ML Functions CONFIGURATION EXAMPLES • Click on the option Create a new Workspace. This will create a new workspace for us. Click on OK. •

Strona 152

MOD 30ML Functions CONFIGURATION EXAMPLES Figure 3. 7. New Document • The New dialog box shows the Document tab now. Select the type MOD Functi