MODCELL 2050R User’s Guide Indicating Process Controller 2050R Model B Version 2.8 2051R Model B Version 2.8

Strona 2 - MicroMod Automation, Inc

IB-23C650INTRODUCTIONBlank Page4

Strona 3 - CONTENTS

IB-23C650SETUPTable 9. Ramp/Soak Profile Setup MenuStep Step DescriptionTopDisplay1Ramp/Soak Menu.UP moves to SETPTS **MENU**.DN moves to TOTALIZE **M

Strona 4 - CONTENTS (Cont’d)

IB-23C650SETUPTable 9. Ramp/Soak Profile Setup MenuMiddleDisplayBottomDisplayEntry Description**MENU**None.REPEAT NOYES= Stops ramp/soak cycle after l

Strona 5 - ILLUSTRATIONS

IB-23C650SETUPTable 9. Ramp/Soak Profile Setup MenuStep Step DescriptionTopDisplay7.1.1Segment 1 Start Value.UP or DN sets value.SCRL to advance to St

Strona 6 - ILLUSTRATIONS (Cont’d)

IB-23C650SETUPTable 9. Ramp/Soak Profile Setup MenuMiddleDisplayBottomDisplayEntry DescriptionSTART SP xxxxBetween ‘Local Set-point Low Limit’ and ‘Lo

Strona 7

IB-23C650SETUPTable 9. Ramp/Soak Profile Setup MenuStep Step DescriptionTopDisplay7.1.5Segment 1 Relay A State.UP or DN selects ON or OFF.SCRL to adva

Strona 8 - IDENTIFICATION INFORMATION

IB-23C650SETUPTable 9. Ramp/Soak Profile Setup MenuMiddleDisplayBottomDisplayEntry DescriptionRELAY A ONOFFState of the relay during segment.RELAY B O

Strona 9

IB-23C650SETUPTable 9. Ramp/Soak Profile Setup MenuStep Step DescriptionTopDisplay7.10.2Segment 10 End Value.UP or DN sets value.SCRL to advance to:St

Strona 10 - INTRODUCTION

IB-23C650SETUPTable 9. Ramp/Soak Profile Setup MenuMiddleDisplayBottomDisplayEntry DescriptionEND SP xxxxBetween ‘Local Set-point Low Limit’ and ‘Loca

Strona 11 - INSTALLATION

IB-23C650SETUPTable 9. Ramp/Soak Profile Setup MenuStep Step DescriptionTopDisplay7.10.7Segment 10 Relay C State.UP or DN selects ON or OFF.SCRL to ad

Strona 12

IB-23C650SETUPTable 9. Ramp/Soak Profile Setup MenuMiddleDisplayBottomDisplayEntry DescriptionRELAY C ONOFFState of the relay during segment.GUARANTD

Strona 13 - MOUNTING

IB-23C650INSTALLATIONINSTALLATIONGENERALRead these instructions thoroughly before starting installation. Installationpersonnel should be qualified te

Strona 14 - WIRING GUIDELINES

IB-23C650SETUPTable 10. Integrator/Totalizer MenuStep Step DescriptionTopDisplay1Totalizer Menu.UP moves to RAMPSOAK **MENU** if ramp/soakis enabled,

Strona 15 - S-3017-7A(3)

IB-23C650SETUPTable 10. Integrator/Totalizer MenuMiddleDisplayBottomDisplayEntry Description**MENU**None.PRED CNT NOYES= Counts until turned off or un

Strona 16 - POWER CONNECTIONS

IB-23C650SETUPTable 10. Integrator/Totalizer MenuStep Step DescriptionTopDisplay7Totalizer Scale Decimal Point.UP or DN sets decimal point.SCRL to adv

Strona 17 - Electrical Noise

IB-23C650SETUPTable 10. Integrator/Totalizer MenuMiddleDisplayBottomDisplayEntry DescriptionDEC PT0.0.00.000.000Sets decimal location for scale factor

Strona 18 - REMOTE SET-POINT CONNECTIONS

IB-23C650SETUPTable 11. Alarm Settings MenuStep Step DescriptionTopDisplay1Alarms Menu.UP moves to TOTALIZE **MENU** if totalizer is enabled, or to RA

Strona 19

IB-23C650SETUPTable 11. Alarm Settings MenuMiddleDisplayBottomDisplayEntry Description**MENU**None.OCCUR OF NONEDGP1DG, P1P2DG, P2P1, P2DG,P1,P2= Beep

Strona 20

IB-23C650SETUPTable 11. Alarm Settings MenuStep Step DescriptionTopDisplay5Priority 1 Relay Action. UP or DN selects action.SCRL to advance to:Step 6

Strona 21 - RTD INPUT

IB-23C650SETUPTable 11. Alarm Settings MenuMiddleDisplayBottomDisplayEntry DescriptionACTION LATCHINGNO LATCH= Relay assigned to alarm will trip (deen

Strona 22

IB-23C650SETUPTable 11. Alarm Settings MenuStep Step DescriptionTopDisplay7.1.3Alarm 1 Priority.UP or DN selects 1 or 2.SCRL to advance to Step 7.1.4.

Strona 23

IB-23C650SETUPTable 11. Alarm Settings MenuMiddleDisplayBottomDisplayEntry DescriptionPRIORITY 21= Lower priority= Higher priorityHYST xxxx 0 to 1000,

Strona 24 - VOLT INPUT

IB-23C650 INTRODUCTION 6 Notes: 1. When mounting housing in panel cutout or rack and panel mounting bezel, turn retaining screws until point of

Strona 25 - MILLIVOLT INPUT

IB-23C650SETUPTable 12. Tune MenuStep Step DescriptionTopDisplay1Tune Menu.UP moves to ALARMS **MENU**.DN moves to DISPLAYS **MENU**.SCRL to begin set

Strona 26 - DIGITAL INPUT

IB-23C650SETUPTable 12. Tune MenuMiddleDisplayBottomDisplayEntry Description**MENU**None.NAME xxxxxxxx x= any of the following characters:Letters ‘A’

Strona 27 - No External Parts: 500 ohms

IB-23C650SETUPTable 12. Tune MenuStep Step DescriptionTopDisplay7Reset Enable.UP selects YES or DN selects NO.SCRL to advance to:Step 7.1 from YES if

Strona 28 - OUTPUT SIGNAL CONNECTIONS

IB-23C650SETUPTable 12. Tune MenuMiddleDisplayBottomDisplayEntry DescriptionENABLE YESNO= Enable integral response= Don’t enable integral response HEA

Strona 29

IB-23C650SETUPTable 12. Tune MenuStep Step DescriptionTopDisplay8(cont’d)Preact Value.Step 13 if A/M ratio bias is not enabled and output type is POS

Strona 30 - Maximum Value: 400 ohms

IB-23C650SETUPTable 12. Tune MenuMiddleDisplayBottomDisplayEntry DescriptionRATIO xxx.xx-300.00 to 300.00Ratio value applied to remote set-point. If r

Strona 31

IB-23C650SETUPTable 12. Tune MenuStep Step DescriptionTopDisplay13Position Proportioning Deadband.UP or DN sets value.SCRL to advance to Step 14.POS P

Strona 32 - Blank Page

IB-23C650SETUPTable 12. Tune MenuMiddleDisplayBottomDisplayEntry DescriptionDEADBAND xx.x0.0 to 50.0%Percent difference in calculated output andvalve

Strona 33 - GENERAL PREPARATIONS

IB-23C650SETUPBlank Page122

Strona 34 - DATA BASE REFERENCE TABLES

IB-23C650BASIC OPERATIONBASIC OPERATIONINTRODUCTIONOperator activities related to ongoing operations are performed in theDISPLAYS MENU. Some operator

Strona 35

IB-23C650INSTALLATIONMOUNTINGThe controller must be installed in an approved enclosure or installed in ameans acceptable to the authority having juris

Strona 36

IB-23C650 INTRODUCTION 124 Alarm Light Alarm Scroll Key Loop Tag Display Tag Key Process Variable Display Manual Key Auto Key Status Dis

Strona 37

IB-23C650BASIC OPERATIONCONTROL KEYSThe operator control keys are:Alarm: Press to stop flashing and beeping alarm indication.Press repeatedly to view

Strona 38

IB-23C650BASIC OPERATIONUp (UP): Used in the configuration mode to answer promptsby toggling between YES and NO or other option,and to increment value

Strona 39

IB-23C650BASIC OPERATIONBottom: Lower EngineeringDisplayIndicates engineering unitvalues for output,set-point,ratio and bias as indicatedby the third

Strona 40

IB-23C650BASIC OPERATIONMIDDLE DISPLAYRemote: Set-point is derived from a remote location andis brought into the instrument through theremote set-poin

Strona 41

IB-23C650BASIC OPERATIONTotalize: The totalized count is being displayed in thelower engineering display. See operation ofTotalizer.Autotune: Autotu

Strona 42

IB-23C650BASIC OPERATIONBAR GRAPHSThree 50-segment bar graphs provide visual indication of process, set-pointand either output or deviation.Process Va

Strona 43

IB-23C650BASIC OPERATIONRESTARTPower up mode, set-point and output conditions can be defined so that at aninstrument power up condition the controller

Strona 44

IB-23C650BASIC OPERATIONOPERATION IN AUTOMATIC MODEThis section describes operations for local set-points, remote or multiple set-points, and A/M rati

Strona 45

IB-23C650BASIC OPERATIONAutomatic Operation with Remote or Multiple Set-PointsThe controller may be in either auto or manual as selected in the power

Strona 46

IB-23C650INSTALLATIONWIRING GUIDELINESThe power wiring connections and input/output (I/O) connections are madewith the controller installed in its ope

Strona 47

IB-23C650BASIC OPERATIONTo perform a set-point bumpless transfer, complete the following steps:1) With set-point displayed, press theR/L key to advan

Strona 48

IB-23C650BASIC OPERATIONAutomatic Operation with A/M Ratio BiasIf ratio, bias or ratio/bias was enabled in the RAT BIAS MENU, the instrumentdisplay wi

Strona 49

IB-23C650BASIC OPERATIONAUTO/MANUAL TRANSFERTransfer from auto to manual is accomplished by pressing the manual key.Either of the digital inputs may b

Strona 50

IB-23C650BASIC OPERATIONAuto/Manual Transfer for On-Off ControlIf the controller is set up for on-off control, the bumpless transfer feature doesnot a

Strona 51

IB-23C650BASIC OPERATIONOPERATION IN MANUALThis section describes operations for local set-points, remote or multiple set-points, and A/M ratio bias w

Strona 52

IB-23C650BASIC OPERATIONWhen the controller is set up for on/off control, the manual output is a timeproportioning signal. This gives the output infi

Strona 53

IB-23C650BASIC OPERATIONPress the scroll key to display theoutput in percent in the lowerengineering display.[OUT] appears in the third statusdisplay.

Strona 54 - to advance to Step 3.5

IB-23C650BASIC OPERATIONUse the following steps to prepare to switch from a local to a remote set-point:1) Press the R/L key until [REM] isdisplayed

Strona 55 - Table 2. Input Setup Menu

IB-23C650BASIC OPERATIONManual Operation with A/M Ratio BiasIf ratio, bias, or ratio/bias was enabled in the RAT BIAS MENU, the instrumentdisplay will

Strona 56

IB-23C650BASIC OPERATIONOPERATION USING DIGITAL INPUTSDigital inputs 1 and 2 can be used to control auto/manual transfer,acknowledge alarms, start tot

Strona 57

IB-23C650INSTALLATIONFigure 2. Controller Power and Signal TerminationsTX PowerVolt InputRTD SrcmA Inpt +Input –mA OutputCOMTX Power 2Volt Input 2RT

Strona 58

IB-23C650BASIC OPERATIONIf the digital input action is configured to be REVERSE, a closed contact willbe treated as an open contact and vice versa.Not

Strona 59

IB-23C650BASIC OPERATION2. Select whether to lock out the front panel from making set-point transfers,whether transitions are allowed between local an

Strona 60 - to advance to Step 4.7

IB-23C650BASIC OPERATIONA transition in the state of either digital input (opened to closed, or closed toopened) will now cause a set-point transfer.

Strona 61

IB-23C650BASIC OPERATIONcombination of the four display alarms. Monitoring and acknowledging alarmsare basic operator activities. Acknowledgment of

Strona 62

IB-23C650BASIC OPERATIONFigure 16b. Controller Alarm Display and Relay Status Conditions (Sheet 2)Alarm Ceases beforeACKALARM AND RELAY STATUS WITH A

Strona 63

IB-23C650BASIC OPERATIONAlarm MessagesAn alarm is active when the process input (PROC), input 2 (INP2), controloutput (OUT), or deviation value (DEV)

Strona 64

IB-23C650BASIC OPERATIONWhen the alarm finally stops, the alarm indicator will go out. If there is analarm at one limit that has not been acknowledge

Strona 65

IB-23C650BASIC OPERATIONSTARTUPProcedures may vary from application to application, depending uponindividual requirements and controller setup. The i

Strona 66

IB-23C650BASIC OPERATION4. Manually adjust output of controller to bring process variable up to finalvalue. Ramping the output should be slow enough

Strona 67

IB-23C650TUNINGTUNINGMANUAL TUNINGThe controller response parameters: Gain (P), Integral (I), and Derivative (D)are adjustable over a wide range of v

Strona 68

IB-23C650INSTALLATIONPOWER CONNECTIONSWARNINGAvoid electrical shock. AC power wiring must not beconnected at the distribution panel (ac source) until

Strona 69

IB-23C650TUNINGTuning ProcedureThe following procedure for tuning a controller is applicable to controllers setup for P (gain), PI (gain plus integral

Strona 70

IB-23C650TUNINGFigure 17. Process Recovery Cycle with OptimumResponse SettingsIncreasing the gain setting increases cycle B relative to cycle A. If

Strona 71

IB-23C650TUNINGb. Controller with P and D responses:D = P (Minutes)8c. Controller with P, I, and D responses:I = 1.5P (Minutes)D = P (Minutes)69. Acce

Strona 72

IB-23C650TUNINGAUTOMATIC TUNINGAutomatic tuning (autotune) is an on-demand user activated feature whichautomatically calculates either PI or PID respo

Strona 73

IB-23C650TUNINGTable 13. Autotune ProcedureStep Step DescriptionTopDisplay1Displays Menu.UP moves to TUNE **MENU**.DN moves to BASE CFG **MENU**.SCRL

Strona 74

IB-23C650TUNINGTable 13. Autotune ProcedureMiddleDisplayBottomDisplayEntry Description**MENU**Installation and Setup Check. Installation,and Setup mu

Strona 75

IB-23C650TUNINGTable 13. Autotune ProcedureStep Step DescriptionTopDisplay4Autotune Activation. UP enters autotune setup.SCRL to return to Step 2.TAG

Strona 76

IB-23C650TUNINGTable 13. Autotune ProcedureMiddleDisplayBottomDisplayEntry DescriptionxxxProcessValueATN is displayed to indicate the Autotunepoint o

Strona 77

IB-23C650TUNINGTable 13. Autotune ProcedureStep Step DescriptionTopDisplay7Process High Trip-Point. UP or DN adjusts process high trip-point value.SCR

Strona 78

IB-23C650TUNINGTable 13. Autotune ProcedureMiddleDisplayBottomDisplayEntry DescriptionPROC HI 100Valid values are: -2997 or PROC LO+3 to 30000.Rememb

Strona 79 - (i. e. ,100% = 20 mA dc)

IB-23C650INSTALLATIONGROUND CONNECTIONSThe primary power ground system consists of the plant electrical ground(equipment grounding conductors). AC gr

Strona 80

IB-23C650TUNINGTable 13. Autotune ProcedureStep Step DescriptionTopDisplay11.1Increase Step. SCRL to Step 11.2 for a response limitedmessage.Otherwis

Strona 81

IB-23C650TUNINGTable 13. Autotune ProcedureMiddleDisplayBottomDisplayEntry DescriptionINCREASE STEP SIZThe ratio of process oscillation to hysteresisv

Strona 82

IB-23C650TUNINGAutotune CompletionAutotune will generally result in successful calculation of tuning constants.When a completely successful autotune c

Strona 83

IB-23C650TUNINGCancellation During ExecutionPress the manual key to cancel the autotune cycle during execution by thecontroller. This will prevent co

Strona 84

IB-23C650TUNINGBlank Page168

Strona 85

IB-23C650RAMP/SOAK OPERATIONRAMP/SOAK OPERATIONDESCRIPTION OF RAMP/SOAK PROFILEThe Ramp/Soak Profile option complements any type of controlimplementat

Strona 86 - Table 6. RS-485 Setup Menu

IB-23C650RAMP/SOAK OPERATIONFigure 19. Typical Six-Segment Ramp/Soak Profile170

Strona 87

IB-23C650RAMP/SOAK OPERATIONOPERATION IN AUTOMATICThe ramp/soak sequence is initiated and monitored in the DISPLAYS MENUwhere the instrument display a

Strona 88

IB-23C650RAMP/SOAK OPERATIONAfter selecting RUN or HOLD at the beginning of the ramp/soak displaysequence, scrolling accesses the segment status displ

Strona 89

IB-23C650RAMP/SOAK OPERATIONIf the [SKIP] or [RESET] prompts do not appear, a password has beenconfigured in the BASE CFG MENU and is required to acce

Strona 90

IB-23C650INSTALLATIONThe combination device suppresses transients and effectively reducesother noise forms such as electromagnetic (EMI) and radio fre

Strona 91

IB-23C650RAMP/SOAK OPERATION• If the skipped segment is the last segment in the profile and the cycle isconfigured to repeat, the skip returns the pro

Strona 92

IB-23C650RAMP/SOAK OPERATIONRamp or Soak HysteresisThe hysteresis function provides for setting up a band of process variablevalues relative to the se

Strona 93 - Table 8. Set-Point Setup Menu

IB-23C650RAMP/SOAK OPERATIONmanual set-point is not at the same value as the ramp/soak profile set-point(the ramp/soak profile is paused at its curren

Strona 94

IB-23C650TOTALIZER OPERATIONTOTALIZER OPERATIONDESCRIPTION OF INTEGRATION/TOTALIZATION FUNCTIONThe integrator/totalizer provides the capability to int

Strona 95

IB-23C650TOTALIZER OPERATION• Scale FactorThis feature allows custom scaling of the totalized value. The reciprocalof the entered value (0.001 to 300

Strona 96

IB-23C650TOTALIZER OPERATIONPreset ValueThe preset value is the number from which the totalizer starts counting after awrap or when the totalizer was

Strona 97

IB-23C650TOTALIZER OPERATIONEXAMPLES OF TOTALIZER COUNT FACTORSThere are three configurable factors that affect what one totalized count equalsin actu

Strona 98 - to return to Step 1

IB-23C650TOTALIZER OPERATION Table 14. Examples of Totalizer Count Factors ActualFlow at100%ConfiguredEngineeringUnits(Note 1)Scale(Disp.Mult.)Confi

Strona 99

IB-23C650TOTALIZER OPERATION2.) Configured scale factors are 0.001 to 30000. The unscaled total is dividedby the configured scale factor to get the s

Strona 100

IB-23C650RATIO BIAS CONTROLRATIO BIAS CONTROLRATIO BIAS CONTROLLERRatio bias control systems maintain two or more process variables at apredetermined

Strona 101

IB-23C650INSTALLATIONPROCESS INPUT SIGNAL CONNECTIONSProcess input connections are shown as follows: • Thermocouple Inputs - see Figure 3• RTD Inputs

Strona 102

IB-23C650RATIO BIAS CONTROLThe independent (wild) flow changes from time to time, and in order tomaintain the correct proportions of the blend the oth

Strona 103

IB-23C650RATIO BIAS CONTROLcorrect ratio value. When the streams do not have the same flow range, thevariables must be expressed in engineering units

Strona 104

IB-23C650RATIO BIAS CONTROLFigure 22. Effect of Ratio Adjustment in an Inverse Ratio Control SystemFigure 23. Effect of Bias Adjustment on a Ratio R

Strona 105

IB-23C650RATIO BIAS CONTROLA/M RATIO BIAS STATIONThe A/M ratio bias station applies a ratio or bias to the process input. Theoutput of the station is

Strona 106

IB-23C650RATIO BIAS CONTROLA typical A/M Ratio Station application where a plant master steam flowcontroller provides an input to two boiler masters (

Strona 107

IB-23C650RATIO BIAS CONTROLInstrument Set-upTo implement an A/M Ratio Bias Station, enter into the BASE CFG **MENU**, Table 1, and enable A/M Ratio Bi

Strona 108 - to advance to Step 7.10.8

IB-23C650RATIO BIAS CONTROLBlank Page190

Strona 109 - (Step 3 or 4)

IB-23C650TIME PROPORTIONING CONTROLTIME PROPORTIONING CONTROLDESCRIPTIONTime proportioning control permits PID control to be used in applicationswhere

Strona 110

IB-23C650TIME PROPORTIONING CONTROLFigure 26. Output Relay Duty Cycle for Time Proportioning ControlPID Output% of SpanCycle Time10 SecondsS-1107-41B

Strona 111

IB-23C650CURRENT PROPORTIONING CONTROLCURRENT PROPORTIONING CONTROLDESCRIPTIONThe controller provides an adjustable dc current output signal for curre

Strona 112

MicroMod Automation, Inc. The Company MicroMod Automation is dedicated to improving customer efficiency by providing the most cost-effective, applica

Strona 113

IB-23C650INSTALLATIONFigure 3. Thermocouple Input ConnectionsGROUNDED++ –THERMOCOUPLE INPUT Twisted or ShieldedPair ThermocoupleWireThermocoupleUNGR

Strona 114

IB-23C650CURRENT PROPORTIONING CONTROLblank page194

Strona 115 - Table 11. Alarm Settings Menu

IB-23C650DUAL OUTPUT CONTROLDUAL OUTPUT (HEAT/COOL) CONTROLDESCRIPTIONThe controller can provide dual output (heat/cool) control with each of thethree

Strona 116

IB-23C650DUAL OUTPUT CONTROLFigure 27. Dual Output (Heat/Cool) Output TransitionTransitionBandwidth75%Cool Output100%or CoolHighLimit100%or HeatHigh

Strona 117

IB-23C650ON/OFF CONTROLON/OFF CONTROLDESCRIPTIONThe on/off output calculation diagram is shown in Figure 29. The local set-point adjustment is made u

Strona 118

IB-23C650ON/OFF CONTROLFigure 29. On/Off Output CalculationProcessOutputSwitchCalcu-latedOutputManualAutoS-1107-265(1)On/OffControlAlgorithmActiveSet

Strona 119

IB-23C650POSITION PROPORTIONING CONTROLPOSITIONING PROPORTIONING CONTROLDESCRIPTIONPositioning proportioning control permits PID control to be used in

Strona 120

IB-23C650POSITION PROPORTIONING CONTROLReasonable values for Position Proportioning Deadband and Preact can bedetermined using the following procedure

Strona 121 - Table 12. Tune Menu

IB-23C650DIAGNOSTICSDIAGNOSTICSINPUT FAILURE AND POWER FAILURE DETECTIONThe fault detection level for volt inputs is determined by the percent of volt

Strona 122

IB-23C650DIAGNOSTICSconditions using the UP key. Input Failure Messages• [OPEN TC1 (2)] Open Thermocouple 1 (or 2) (upscale burnout)• [HIGH TC1 (2)]

Strona 123

IB-23C650DIAGNOSTICSThe following messages may indicate a failure of a component. If themessage is temporary, the cause may be some other electrical

Strona 124

IB-23C650INSTALLATIONFigure 4. RTD Input Connectionst°NoteRTD INPUTt°2-WIRE RTDShield3-WIRE RTDShieldNote: 4-Wire RTD connectedsame as 3-wire RTDwith

Strona 125

IB-23C650DIAGNOSTICS Problem Possible Cause ActionNo display a. No power to controller.b. Controller not fullyseated in housing.c. Incorrect powerconn

Strona 126

IB-23C650CALIBRATION DATACALIBRATION DATAINTRODUCTIONThe 2050R base controller (main board) is factory calibrated and does notrequire calibration data

Strona 127

IB-23C650CALIBRATION DATATable 15. Main/Option Board Calibration (Base Configuration Menu)Step Step DescriptionTopDisplay16Main Board Calibration.UP

Strona 128

IB-23C650CALIBRATION DATATable 15. Main/Option Board Calibration (Base Configuration Menu)MiddleDisplayBottomDisplayEntry DescriptionCALIBRATNOTE:

Strona 129 - BASIC OPERATION

IB-23C650CALIBRATION DATATable 15. Main/Option Board Calibration (Base Configuration Menu)Step Step DescriptionTopDisplay16.3Process Input Ma. Resis

Strona 130

IB-23C650CALIBRATION DATATable 15. Main/Option Board Calibration (Base Configuration Menu)MiddleDisplayBottomDisplayEntry DescriptionMR RATIO xxxxx

Strona 131 - CONTROL KEYS

IB-23C650CALIBRATION DATATable 15. Main/Option Board Calibration (Base Configuration Menu)Step Step DescriptionTopDisplay17Option Board Calibration.

Strona 132 - ENGINEERING DISPLAYS

IB-23C650CALIBRATION DATATable 15. Main/Option Board Calibration (Base Configuration Menu)MiddleDisplayBottomDisplayEntry DescriptionCALIBRATNOTE:

Strona 133 - STATUS DISPLAYS

IB-23C650CALIBRATION DATATable 15. Main/Option Board Calibration (Base Configuration Menu)Step Step DescriptionTopDisplay17.3Input 2 Ma. Resistance

Strona 134

IB-23C650CALIBRATION DATATable 15. Main/Option Board Calibration (Base Configuration Menu)MiddleDisplayBottomDisplayEntry DescriptionMR RATIO xxxxx

Strona 135 - Top & Middle

IB-23C650INSTALLATIONFigure 5. 2- Wire Milliampere Input Connections External PowerSupplyMILLIAMPERE INPUT - 2-WIRE TRANSMITTERShield to be left un

Strona 136 - ALARM INDICATOR

IB-23C650PARTS AND MAINTENANCEPARTS AND MAINTENANCEPARTS AVAILABILITYThe MODCELL 2050 Controller parts available for purchase are:• Termination Assemb

Strona 137 - . If diagnostic

IB-23C650RECORD OF DATABASEDESCRIPTIONThis section provides tables of the database fields for planning and recordingyour configuration entries via the

Strona 138 - OPERATION IN AUTOMATIC MODE

IB-23C650Data Base RecordTopDisplayMiddleDisplayBot. Disp.EntryTopDisplayMiddleDisplayBot. Disp.EntryBASE CFG **MENU** * BRD CALIBRATMAIN PWR FREQ DEF

Strona 139

IB-23C650Data Base RecordTopDisplayMiddleDisplayBot. Disp.EntryTopDisplayMiddleDisplayBot. Disp.EntryRIGHT BAR DI SETPT SEL LISTDEV BAR FULL SCL MA. O

Strona 140

IB-23C650Data Base RecordTopDisplayMiddleDisplayBot. Disp.EntryTopDisplayMiddleDisplayBot. Disp.EntryRAT BIAS **MENU** SETPT 3 LO LIMITRAT BIAS TYPE S

Strona 141

IB-23C650100Data Base RecordTopDisplayMiddleDisplayBot. Disp.EntryTopDisplayMiddleDisplayBot. Disp.EntryRAMPSOAK **MENU** SEG * SETUP See BelowRAMPSOA

Strona 142 - AUTO/MANUAL TRANSFER

IB-23C650Data Base RecordTopDisplayMiddleDisplayBot. Disp.EntryTopDisplayMiddleDisplayBot. Disp.EntryALARMS **MENU** ALARM 4 PRIORITYBEEP ON OCCUR OF

Strona 144 - OPERATION IN MANUAL

The Company’s policy is one of continuous product improvement and the rightis reserved to modify the information contained

Strona 145

IB-23C650INSTALLATIONFigure 6. Non 2-Wire Milliampere Input Connections Note: Non 2-Wire Transmitter may also be ungrounded. MILLIAMPERE INPUT - N

Strona 146

IB-23C650INSTALLATIONFigure 7. Voltage Input Connections VOLT INPUTGROUNDEDShield to be left un-connected at this end.VSource– + GUNGROUNDEDVSource–

Strona 147

IB-23C650INSTALLATIONFigure 8. Millivolt Input ConnectionsShield to be left uncon-nected at this end.Note: Terminals 12 & 13must be wiredtogether

Strona 148

IB-23C650INSTALLATIONFigure 9. Digital Input Connections 1.2KTo Micro-processor4.5KSame as#31Note: External devicesinks current. CONTROLLER+5VDIGITA

Strona 149 - Enabling Digital Inputs

IB-23C650INSTALLATIONPOSITION FEEDBACK (SLIDEWIRE) INPUTFigure 10. Motorized Valve and Slidewire ConnectionsWiperCloseOpenInst.ACPowerAutoFwdRevNote:

Strona 150

IB-23C650INSTALLATIONOUTPUT SIGNAL CONNECTIONSOutput connections are shown as follows:• mA Outputs - see Figure 11• Voltage Outputs - see Figure 12• R

Strona 151 - One Digital Input

IB-23C650INSTALLATIONMILLIAMPERE OUTPUTFigure 11. Milliampere Output Connections –+Output LoadMilliampere Output specifications are: Range: 0 to 54

Strona 152 - CONTROL OUTPUT LIMITING

IB-23C650CONTENTS CONTENTSPageIntroductionFeatures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1Description . . . . . . . . .

Strona 153

IB-23C650INSTALLATIONVOLT OUTPUT (0 to 10 Volts dc)Figure 12. Voltage Output Connections –+Output ReceiverPrecision Dropping Resistor Typical Val

Strona 154

IB-23C650INSTALLATIONDIGITAL OUTPUTFigure 13. Digital Output Connections+ –OutputLoadExternalPower SupplyCONTROLLERNONCNote: Connections shown are f

Strona 155 - Alarms with Acknowledgment

IB-23C650INSTALLATIONBlank Page26

Strona 156 - Alarm Type Messages

IB-23C650SETUPSETUPCAUTIONBe sure the process can be maintained in safe conditions before turning oncontroller power. The controller may not be prope

Strona 157

IB-23C650SETUPSETUP FUNCTIONSFor ease of use, the firmware has been divided into functional groups. Thefirst group is for daily continuing operation,

Strona 158

IB-23C650SETUPDISPLAYS **MENU**Displays MenuBASE CFG **MENU**Base Configuration MenuINPUTS **MENU**Inputs MenuDIG INPT **MENU**Digital Inputs MenuMA.

Strona 159 - MANUAL TUNING

IB-23C650SETUPTable 1. Base ConfigurationStep Step DescriptionTopDisplay1Base Configuration Menu.UP moves to DISPLAYS **MENU**. DN moves to INPUTS *

Strona 160 - key to set

IB-23C650SETUPTable 1. Base ConfigurationMiddleDisplayBottomDisplayEntry Description**MENU**None.FREQ 60 HERTZ50 HERTZOptimize input line frequency

Strona 161 - I = P (Minutes)

IB-23C650SETUPTable 1. Base ConfigurationStep Step DescriptionTopDisplay3.2.1(cont’d)Process Calibration Correction. 4 Input 2 Enable. (Requires Op

Strona 162

IB-23C650SETUPTable 1. Base ConfigurationMiddleDisplayBottomDisplayEntry Description3. Be sure that any length of thermocoupleextension wire or RTD

Strona 163 - Setup Procedure

IB-23C650CONTENTSCONTENTS (Cont’d)PageEngineering Displays . . . . . . . . . . . . . . . . . . . . . . . . . 126Status Displays . . . . . . . . . . .

Strona 164

IB-23C650SETUPTable 1. Base ConfigurationStep Step DescriptionTopDisplay4.1.2.1Input 2 Calibration Correction. UP or DN sets correction temperature.

Strona 165

IB-23C650SETUPTable 1. Base ConfigurationMiddleDisplayBottomDisplayEntry Descriptionxxx.x xx.xWhere xxx.x = input 2 temperature and xx.x= temperatu

Strona 166

IB-23C650SETUPTable 1. Base ConfigurationStep Step DescriptionTopDisplay5.4Cool Band Output Action. UP or DN selects cool band output action. SCRL

Strona 167 - Table 13. Autotune Procedure

IB-23C650SETUPTable 1. Base ConfigurationMiddleDisplayBottomDisplayEntry DescriptionACTION DIRECTREVERSE= relay output is open or mA output #2 isMA

Strona 168 - STEP SIZ (Step 5)

IB-23C650SETUPTable 1. Base ConfigurationStep Step DescriptionTopDisplay5.5.5Repeat Calibration. UP selects YES or DN selects NO. SCRL advances to:

Strona 169 - Table 13. Autotune Procedure

IB-23C650SETUPTable 1. Base ConfigurationMiddleDisplayBottomDisplayEntry DescriptionCALIBRAT NOYES= Don’t repeat the procedure.= Repeat the calibra

Strona 170 - to advance to:

IB-23C650SETUPTable 1. Base ConfigurationStep Step DescriptionTopDisplay11Totalizer Enable. UP selects YES or DN selects NO. SCRL advances to Step

Strona 171

IB-23C650SETUPTable 1. Base ConfigurationMiddleDisplayBottomDisplayEntry DescriptionENABLE NOYES= Don’t allow TOTALIZE **MENU** setup orTOT variabl

Strona 172

IB-23C650SETUPTable 1. Base ConfigurationStep Step DescriptionTopDisplay16Main Board Calibration Data.UP begins calibration. See Calibration Datasec

Strona 173

IB-23C650SETUPTable 1. Base ConfigurationMiddleDisplayBottomDisplayEntry DescriptionCALIBRATEntry point for main board calibration. SeeCalibration

Strona 174

IB-23C650CONTENTSCONTENTS (Cont’d)PageDiagnosticsInput Failure and Power Failure Detection . . . . . . . . . . 201Diagnostic Messages . . . . . . . .

Strona 175 - RAMP/SOAK OPERATION

IB-23C650SETUPTable 1. Base ConfigurationStep Step DescriptionTopDisplay18.2Configuration has Changed. SCRL advances to Step 19. CONFIG 19 Lock con

Strona 176

IB-23C650SETUPTable 1. Base ConfigurationMiddleDisplayBottomDisplayEntry DescriptionCHANGEDThis is just a reminder that the instrumentneeds to be r

Strona 177 - OPERATION IN AUTOMATIC

IB-23C650SETUPTable 2. Input Setup MenuStep Step DescriptionTopDisplay1Inputs Menu.UP moves to BASE CFG **MENU**.DN moves to DIG INPT **MENU**.SCRL t

Strona 178

IB-23C650SETUPTable 2. Input Setup MenuMiddleDisplayBottomDisplayEntry Description**MENU**None.POINT 0.0.00.000.000= Display units= Display tenths= D

Strona 179 - CONTROLLING RAMP/SOAK PROFILE

IB-23C650SETUPTable 2. Input Setup MenuStep Step DescriptionTopDisplay3.4Process Input Linearization Type.UP or DN selects type.SCRL to advance to St

Strona 180

IB-23C650SETUPTable 2. Input Setup MenuMiddleDisplayBottomDisplayEntry DescriptionLIN TYPE NONESQR ROOTUNITS HI xxxx–3000 to 30000 for mV, V, mA, and

Strona 181 - Ramp/Soak Hold

IB-23C650SETUPTable 2. Input Setup MenuStep Step DescriptionTopDisplay3.6Process Input Engineering Units, Low. UP or DN sets engineering units.SCRL

Strona 182

IB-23C650SETUPTable 2. Input Setup MenuMiddleDisplayBottomDisplayEntry DescriptionUNITS LO xxxx–3000 to 30000Note: Fixed at 0 when process inputlinea

Strona 183 - TOTALIZER OPERATION

IB-23C650SETUPTable 2. Input Setup MenuStep Step DescriptionTopDisplay3.10Recovery Option. UP or DN selects option.SCRL to advance to:Step 4 if inpu

Strona 184 - Totalizer Reset Display

IB-23C650SETUPTable 2. Input Setup MenuMiddleDisplayBottomDisplayEntry DescriptionOPTION MANUALLAST= Makes instrument return to the manualmode after

Strona 185 - Predetermined Count

IB-23C650CONTENTSILLUSTRATIONS (Cont’d) Figure Page21 Effect of Ratio Adjustment in a Direct Ratio Control System . . . . . . . . . . . . . . . . .

Strona 186

IB-23C650SETUPTable 2. Input Setup MenuStep Step DescriptionTopDisplay4.5Input 2 Engineering Units, High. UP or DN sets engineering units.SCRL to ad

Strona 187

IB-23C650SETUPTable 2. Input Setup MenuMiddleDisplayBottomDisplayEntry DescriptionUNITS HI xxxx–3000 to 30000 for mV, V, mA, and slidewire (minimum s

Strona 188

IB-23C650SETUPTable 2. Input Setup MenuStep Step DescriptionTopDisplay4.7Input 2 Fault Action. UP or DN selects action.SCRL to advance to: Step 4.8

Strona 189 - RATIO BIAS CONTROL

IB-23C650SETUPTable 2. Input Setup MenuMiddleDisplayBottomDisplayEntry DescriptionACTIONNONELOCALNONEHOLD POSCLSD POSOPEN POSOutput type is NOT Posi

Strona 190 - Ratio Function

IB-23C650SETUPTable 2. Input Setup MenuStep Step DescriptionTopDisplay5Engineering Units Label. UP to begin label entry.SCRL to advance to Step 6.1.

Strona 191 - Bias Function

IB-23C650SETUPTable 2. Input Setup MenuMiddleDisplayBottomDisplayEntry DescriptionLABEL xxxWhere x = any of the characters listed underTag Name in th

Strona 192

IB-23C650SETUPTable 3. Digital Input Setup MenuStep Step DescriptionTopDisplay1Digital Input Menu.UP moves to INPUTS **MENU**.DN moves to MA. OUTP **M

Strona 193 - A/M RATIO BIAS STATION

IB-23C650SETUPTable 3. Digital Input Setup MenuMiddleDisplayBottomDisplayEntry Description**MENU**None.INPUT 1 None.FUNCTION NONEAUTO/MANALRM ACKTOTAL

Strona 194

IB-23C650SETUPTable 3. Digital Input Setup MenuStep Step DescriptionTopDisplay2.1.3Manual to Auto Transition Allowed. UP or DN selects YES or NO.SCRL

Strona 195 - A/M Switching

IB-23C650SETUPTable 3. Digital Input Setup MenuMiddleDisplayBottomDisplayEntry DescriptionALLOWED NOYES= Allows digital input to switch control modeon

Strona 196

IB-23C650INTRODUCTIONINTRODUCTIONFEATURES• Isolated universal process and remote set-point input• Four internal set-points• No jumpers required to def

Strona 197 - TIME PROPORTIONING CONTROL

IB-23C650SETUPTable 3. Digital Input Setup MenuStep Step DescriptionTopDisplay2.1.7Totalizer Command Lockout. UP or DN selects YES or NO.SCRL to adva

Strona 198 - S-1107-41B

IB-23C650SETUPTable 3. Digital Input Setup MenuMiddleDisplayBottomDisplayEntry DescriptionLOCKOUT YESNO= Locks out the front panel totalizercommands i

Strona 199 - CURRENT PROPORTIONING CONTROL

IB-23C650SETUPTable 3. Digital Input Setup MenuStep Step DescriptionTopDisplay3.1Digital Input 2 Function.UP or DN selects function.SCRL to advance to

Strona 200

IB-23C650SETUPTable 3. Digital Input Setup MenuMiddleDisplayBottomDisplayEntry DescriptionFUNCTION NONEAUTO/MANALRM ACKTOTALIZERAMPSOAKSETP SELOUTP TR

Strona 201 - DESCRIPTION

IB-23C650SETUPTable 3. Digital Input Setup MenuStep Step DescriptionTopDisplay3.1.5Ramp/Soak Digital Input 2 Command Lockout. UP or DN selects YES or

Strona 202 - S-1107-52A

IB-23C650SETUPTable 3. Digital Input Setup MenuMiddleDisplayBottomDisplayEntry DescriptionLOCKOUT YESNO= Locks out the front panel ramp/soakcommands i

Strona 203 - ON/OFF CONTROL

IB-23C650SETUPTable 3. Digital Input Setup MenuStep Step DescriptionTopDisplay3.1.9Local to Remote Transition Allowed. UP or DN selects YES or NO.SCR

Strona 204

IB-23C650SETUPTable 3. Digital Input Setup MenuMiddleDisplayBottomDisplayEntry DescriptionALLOWED NOYES= Digital input transition selects any set-poin

Strona 205

IB-23C650SETUPTable 4. Milliamp Output Setup MenuStep Step DescriptionTopDisplay1Milliamp Output Menu.UP moves to DIG INPT **MENU**.DN moves to RELAYS

Strona 206

IB-23C650SETUPTable 4. Milliamp Output Setup MenuMiddleDisplayBottomDisplayEntry Description**MENU**None.MA. HIGH xx.x 01.0 to 54.0 mA dcThe current p

Strona 207 - DIAGNOSTICS

IB-23C650INTRODUCTIONRanging of the RTD and Thermocouple is automatic. The process input isisolated from the rest of the instrument. A 24V dc transm

Strona 208 - Operational Failure Messages

IB-23C650SETUPTable 4. Milliamp Output Setup MenuStep Step DescriptionTopDisplay9.1Fixed Output Value.UP or DN sets fixed initial power up output valu

Strona 209 - TROUBLESHOOTING

IB-23C650SETUPTable 4. Milliamp Output Setup MenuMiddleDisplayBottomDisplayEntry DescriptionUP OUTPT xx.x–8.0 to 110.0. Limited by output high and lo

Strona 210 - Problem Possible Cause Action

IB-23C650SETUPTable 5. Output Relays Setup MenuStep Step DescriptionTopDisplay1Output Relays Menu.UP moves to MA. OUTP **MENU**.DN moves to RAT BIAS *

Strona 211 - CALIBRATION DATA

IB-23C650SETUPTable 5. Output Relays Setup MenuMiddleDisplayBottomDisplayEntry Description**MENU**None.SETUP None.FUNCTION NONEALARMSTOTALIZERAMPSOAKR

Strona 212

IB-23C650SETUPTable 5. Output Relays Setup MenuStep Step DescriptionTopDisplay3.1.1Relay B Alarm Trip Action.UP or DN selects alarm combination.SCRL t

Strona 213

IB-23C650SETUPTable 5. Output Relays Setup MenuMiddleDisplayBottomDisplayEntry DescriptionTRIP ACT 1234•••123415 possible combinations of the four dis

Strona 214

IB-23C650SETUPTable 6. RS-485 Setup MenuStep Step DescriptionTopDisplay1RS-485 Menu. (requires option board)UP moves to RELAYS **MENU**.DN moves to R

Strona 215

IB-23C650SETUPTable 6. RS-485 Setup MenuMiddleDisplayBottomDisplayEntry Description**MENU**None.81

Strona 216

IB-23C650SETUPTable 7. Auto/Manual Ratio Bias Setup MenuStep Step DescriptionTopDisplay1A/M Ratio Bias Menu.UP moves to RELAYS **MENU**.DN moves to TO

Strona 217

IB-23C650SETUPTable 7. Auto/Manual Ratio Bias Setup MenuMiddleDisplayBottomDisplayEntry Description**MENU**None.TYPE RATIOBIASRAT BIAS= Ratio only sta

Strona 218

IB-23C650 INTRODUCTION 3 Data Plate

Strona 219

IB-23C650SETUPTable 7. Auto/Manual Ratio Bias Setup MenuStep Step DescriptionTopDisplay7Ratio Source for Ratio and Bias Type.UP or DN selects source.S

Strona 220 - MAINTENANCE

IB-23C650SETUPTable 7. Auto/Manual Ratio Bias Setup MenuMiddleDisplayBottomDisplayEntry DescriptionSOURCE LOCALREMOTEInitial value can be set in "

Strona 221 - RECORD OF DATABASE

IB-23C650SETUPTable 8. Set-Point Setup MenuStep Step DescriptionTopDisplay1Set-Point Menu.UP moves to RELAYS **MENU**.DN moves to RAMPSOAK **MENU** if

Strona 222

IB-23C650SETUPTable 8. Set-Point Setup MenuMiddleDisplayBottomDisplayEntry Description**MENU**None.None.FIXED NOYES= Allows changes in Displays menu=

Strona 223

IB-23C650SETUPTable 8. Set-Point Setup MenuStep Step DescriptionTopDisplay3.4Local Set-Point 2 Low Limit.UP or DN sets value.SCRL to advance to Step 3

Strona 224

IB-23C650SETUPTable 8. Set-Point Setup MenuMiddleDisplayBottomDisplayEntry DescriptionLO LIMIT xxxx–3000 to high limitINIT VAL xxxx Low limit to high

Strona 225

IB-23C650SETUPTable 8. Set-Point Setup MenuStep Step DescriptionTopDisplay5.2Local Set-Point 4 Fixed.UP or DN selects YES or NO.SCRL to advance to Ste

Strona 226

IB-23C650SETUPTable 8. Set-Point Setup MenuMiddleDisplayBottomDisplayEntry DescriptionFIXED NOYES= Allows changes in Displays menu= This local set-poi

Strona 227

IB-23C650SETUPTable 8. Set-Point Setup MenuStep Step DescriptionTopDisplay6.1Input 2 is Missing.This warning will time out in 1 second and return to s

Strona 228

IB-23C650SETUPTable 8. Set-Point Setup MenuMiddleDisplayBottomDisplayEntry DescriptionMISSING REM SETPNone.UP SETPT xxxx –3000 to 30000, within local