Micromod MOD: Modcell 2050R Users Guide Instrukcja Użytkownika Strona 186

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 185
IB-23C650
TOTALIZER OPERATION
EXAMPLES OF TOTALIZER COUNT FACTORS
There are three configurable factors that affect what one totalized count equals
in actual engineering units and how quickly the totalizer counts. The first
factor is the engineering units configured in the TOTALIZE MENU. The other
factors are the rate (engineering units time base), and the totalizer scale factor.
Table 14 and its notes give several flow examples of how these factors affect
the totalizer count. Flow is normalized to zero (engineering units low is 0 for
a nonlinear flow input using square root).
If you are totalizing on a temperature signal, the configured engineering low
value becomes your zero based process value and is subtracted from the
process value to get the difference for count. For example, a 75°C process
value with a 50°C low value and a 100°C high value will produce a count of 25
in one minute if the time base is minutes and the scale factor is 1.
180
Przeglądanie stron 185
1 2 ... 181 182 183 184 185 186 187 188 189 190 191 ... 227 228

Komentarze do niniejszej Instrukcji

Brak uwag