BASIC OPERATION
4. Manually adjust output of controller to bring process variable up to final
value. Ramping the output should be slow enough to allow the process to
respond without overshooting the required control point.
An alternate procedure in Step 4 is to bring the process variable up part way,
to see that the control application responds in a controllable manner, then
switch to the automatic mode early in the startup and bring the process
variable up to the operating point under automatic control by adjusting the set-
point.
152