IB-23C650
SETUP
Table 2. Input Setup Menu
Middle
Display
Bottom
Display
Entry Description
UNITS HI xxxx
–3000 to 30000 for mV, V, mA, and slidewire
(minimum span = 2)
For thermocouple range limits, see thermo-
couple input specification on page 12.
(minimum span for:
types B, R, and S = 300°C, 540°F
types E, J, K, N, and T = 100°C, 180°F)
For RTD range limits, see RTD input
specifications on page 13.
(minimum span = 20°C, 36°F)
See description on Process Input Engineering
Units High, Step 3.5.
UNITS LO xxxx –3000 to 30000
Notes: Low value fixed at 0 when input 2
linearization type is SQR ROOT.
Hi and Lo units decimal points are
positioned at xxx.xx when a remote
ratio is configured.