Remote I/O Modules
ELECTRICAL CONNECTIONS
Technical Characteristics
General
Power supply 24 VDC 230 VAC/120 VAC
Number of inputs per unit 12 12
Number of outputs per unit 8 8
Isolated power supply no yes (1500 VAC)
Maximum consumption 0.3 A 10 VA
Inputs
Signal level of the input, nominal value 24 VDC 24 VDC
0 - OFF signal –3 to +5V –3 to +5V
1 - ON signal +15 to +30V +15 to +30V
Opto isolated inputs no no
Input current for 24 VDC 5 mA 5 mA
Input delay 8 ms 8 ms
Outputs
Opto isolated outputs yes yes
Switching capacity under 2 A (resistive or
inductive load)
120/230 VAC 50/60Hz 2 A 2 A
DC 60 W (2A) 60 W (2A)
Nominal current 2 A AC-1 2 A AC-1
Minimum power for the contacts 12 VDC 10 mA 12 VDC 10 mA
24 VDC internal power supply no
yes (±5%) 100 mA
Total current Common M-Q
120/230 VAC 50/60Hz 6 A 6 A
24 VDC 6 A 6 A
Total current Common R-T
120/230 VAC 50/60Hz 4 A 4 A
24 VDC 4 A 4 A
Short-circuit protection no no
Over voltage protection Varistor Varistor