Micromod MOD: 30ML Controller Operation and Maintenance Tra Instrukcja Użytkownika Strona 33

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 74
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 32
Training Manual
Single Loop Template Lab
3 - 11
Figure 3 .11.
.
7
Press NXT to access System Scan
Groups.
Scan groups defined update intervals for
loops.
8 Press DOWN SYSTEM SCANGRPS should be displayed on
lines 1 and 2. See the figure above.
The arrow key will change the Scan Group
time by 50 mSec steps. Scan groups 1
through 5 are user defined intervals for loops
Leave at 0:00.100. The fastest group has
the highest priority. The lower numbered
group has a higher priority if the interval is
the same
9 Press NXT SCAN GROUP 2 will be displayed on lines 1
and 2.
10 Press UP to select 0:00.300
All loops included in Scan Group 2 will
execute every 300 milliseconds
11 Press ENT
12
Press NXT until SYSTEM is displayed in
line 1, Lines 2 and 6 are blank and the
UP arrow is on.
13 Press UP System (Tasks Exit)
14
Press NXT SYSTEM PASWORDS on Lines 1 and 2.
Przeglądanie stron 32
1 2 ... 28 29 30 31 32 33 34 35 36 37 38 ... 73 74

Komentarze do niniejszej Instrukcji

Brak uwag