Micromod MOD: 30ML Controller Operation and Maintenance Tra Instrukcja Użytkownika Strona 42

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 74
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 41
Training Manual
Single Loop Template Lab
3 - 20
3.3.10 SETPOINT Setup
1 Press DOWN to enter setpoint section.
2 Press NXT until SETPOINT HI LIMIT
is displayed on lines 1 and 2.
Setpoint values to the PID algorithm are limited
to this number or below
3 Set the high limit at 200. Then
press ENT.
4 Press NXT until INITIAL VALUE is
displayed.
5 Set the value at 100.0. Then press
ENT.
Setpoint value when configuration is complete.
6 Press NXT until lines 2 and 6 are blank
and only the up arrow is on.
COMPOUND will be displayed on Line 1
7 Press UP This completes the Setpoint section
8 Press NXT This takes you to the top of the Control section.
Line 2 will display CONTROL.
Figure 3 .20.
Przeglądanie stron 41
1 2 ... 37 38 39 40 41 42 43 44 45 46 47 ... 73 74

Komentarze do niniejszej Instrukcji

Brak uwag