Micromod MOD: 30ML Operation and Template Setup Instrukcja Użytkownika Strona 82

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 84
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 81
MOD 30ML Operation
APPENDIX A - EVENT CODES
A-20
Table A-2. Event Codes, Description and Action
Block
Type
Codes Full Message Text Description/Action
WDOM
4 BLOCK MODE SET TO AUTO Information only.
WDOM
5 BLOCK MODE SET TO MANUAL Information only.
WDOM
6 I/O MISMATCH A slot configured for a digital module contains
an intelligent module (analog input, analog
output, ICN, MSC or RIO).
NOTE: This diagnostic cannot distinguish
between an empty slot and a digital I/O module
or between different types of digital modules.
WDOM
7 WDO_MODULE_ERROR One of the following conditions was detected:
The module readback value is not the same
as the previous result value.
The select circuit, which is used to
communicate with the module blocks, has a
diagnostic error. In this case, all modules
report this diagnostic.
WRIM 4 BLOCK MODE SET TO AUTO Information only.
WRIM 5 BLOCK MODE SET TO MANUAL Information only.
WRIM 6 I/O MISMATCH A configured slot is either empty or the installed
module does not match the slot configuration.
WRIM 7 I/O COMMUNICATIONS ERROR One of the following conditions was detected:
There is a checksum error in the
communications between this block and the
module.
The select circuit, which is used to
communicate with the module, has a
diagnostic error. In this case, all modules
report a communications error.
WRIM 8 WRIM MODULE ERROR The module has reported an error which is
identified by an extended error code. The
error codes can be viewed via Attribute No.18,
Extended Error (EXTERR).
Przeglądanie stron 81
1 2 ... 77 78 79 80 81 82 83 84

Komentarze do niniejszej Instrukcji

Brak uwag